SONGGER ST3PF

Contents

ST3PF Power-Off Delay Timer Relay User Manual

Model: ST3PF

1. Introduction

The SONGGER ST3PF is an industrial time delay relay designed for power-off delay control in automation systems. It maintains output for a preset duration after input power is removed, enabling controlled shutdown sequences for machinery, HVAC systems, and lighting circuits. The device features an adjustable timing range and compact DIN rail installation.

ST3PF relay controlling fan, pump, and lighting applications

Figure 1: ST3PF relay in a multi-application setup, demonstrating use for fans, pumps, and lighting.

ST3PF relay installed in an industrial control cabinet

Figure 2: ST3PF relay integrated into an industrial control cabinet, highlighting its industrial-grade stability.

2. Safety Information

WARNING! Risk of Electric Shock

  • Installation and maintenance must be performed by qualified personnel only.
  • Ensure power is disconnected before wiring or servicing the device.
  • Do not touch live terminals during operation.
  • Use appropriate circuit protection devices in the installation.
  • Keep out of reach of children.
  • Proper disposal: Follow WEEE directives for electronic waste.

Note: This warning information is for reference only. Final warning language must comply with the official language requirements of the destination EU country.

3. Package Contents

The product package typically includes:

  • 1 x ST3PF Power-Off Delay Relay Unit
  • 1 x 8-pin Socket/Base

4. Specifications

Parameter Specification
Product Name ST3PF Power-Off Delay Relay
Model Number ST3PF
Power Supply AC
Rated Voltage 220 V AC (EU LVD: High voltage: Above 50Vac or 75Vdc)
Operation Mode Power-Off Delay
Time Range Selectable ranges: 1s, 3s, 6s, 10s, 30s, 60s, 3min, 6min, 10min
Contact Capacity 3A (Resistive Load)
Contact Configuration One delay contact with reset
Terminal Type 8-pin base
Material Flame-retardant PVC housing with metal internal components
Product Weight 0.087 kg
Socket/Base Weight 0.035 kg
Origin Mainland China
High-concerned chemical None
ST3PF relay dimensions: 90mm length, 50mm height, 40mm width

Figure 3: Dimensions of the ST3PF Power-Off Delay Relay.

5. Setup and Installation

5.1. Preparation

  • Ensure the rated supply voltage matches AC 220 V before installation.
  • Mount the relay onto a standard DIN rail.
  • Connect wiring according to the terminal diagram provided below.
  • Confirm all connections are secure.

5.2. Wiring Diagrams

Wiring diagram for ST3PF relay controlling resistive loads under 800W

Figure 4: Wiring diagram for controlling 220V resistive loads under 800W directly. Note the reset button functionality during power-off delay.

Wiring diagram for ST3PF relay controlling loads over 800W with a contactor

Figure 5: Wiring diagram for controlling loads over 800W, requiring the use of an external contactor. Note the reset button functionality during power-off delay.

6. Operation

6.1. Setting the Delay Time

  • Select the desired time range using the range selector on the device.
  • Adjust the specific delay time within the selected range using the front dial.
ST3PF relay panel overview showing voltage, time range, seconds, power indicator, and model

Figure 6: ST3PF Panel Overview, indicating the Voltage, Time Range dial, Seconds (SEC) indicator, Power Indicator Light, and Model type.

6.2. Power-Off Delay Function

  • Apply power to the relay. The device will operate in power-off delay mode.
  • When input power is removed, the relay output remains active for the preset delay time.
  • After the delay expires, the contact returns to its default state.
  • The dial scale indicates approximate delay time and and should be calibrated if precise timing is required.

7. Maintenance

  • Store the device in a dry, ventilated environment away from direct sunlight and moisture.
  • Clean the exterior with a dry cloth. Do not use solvents or water.
  • Periodically inspect terminals and connections for looseness or corrosion.
  • Replace the unit if abnormal operation or visible damage occurs.

8. Troubleshooting

If you encounter issues with your ST3PF relay, consider the following:

  • No Power/No Operation: Check the power supply voltage to ensure it matches the rated 220V AC. Verify all wiring connections are secure and correct according to the diagrams.
  • Incorrect Delay Time: Ensure the time range selector and front dial are set correctly. If precise timing is critical, calibrate the dial setting.
  • Relay Not Switching: Check the contact capacity to ensure the connected load does not exceed 3A (resistive). For loads over 800W, confirm a contactor is properly installed and wired.
  • Device Damage: Inspect the unit for any visible damage. If damage is present or operation is abnormal, replace the unit.

For further assistance, refer to the official user manual PDF available from the seller.

9. User Tips

  • The ST3PF relay is effective for controlling ventilation fans, offering smooth and reliable operation.
  • For applications requiring precise timing, it is recommended to calibrate the dial setting against a known timer, especially for longer delay durations.

10. Frequently Asked Questions (FAQs)

Q1: Can I adjust the delay time?
A1: Yes, the delay time is adjustable and highly accurate, especially within smaller ranges.
Q2: Does this relay support adjustable delay time settings?
A2: Yes, the delay time can be easily adjusted according to your needs. The shorter the time range you select, the higher the adjustment accuracy.
Q3: Is the base socket included?
A3: Yes, the relay comes with a socket base for easy installation (weighing 0.035KG).

11. Warranty and Support

For warranty information, technical support, or bulk order inquiries, please contact the seller directly. You can find contact details on the product page or through the seller's store.

ST3PF relay with contact information for WhatsApp and Email

Figure 7: Contact information for support and inquiries.

12. Compliance Disclaimer

This document is provided for product instruction purposes only. It does not constitute legal advice. The seller is responsible for ensuring compliance with destination market regulations.

Documents and downloads

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.