1. Introduction
1.1. About This Manual
This manual describes the assembly, installation, operation, and troubleshooting of the Aninerel 4.2KW Hybrid Solar Inverter. Please read this manual carefully before installation and operation. Keep this manual for future reference.
1.2. Scope
This manual provides safety and installation guidelines as well as information on tools and wiring for the inverter.
1.3. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION – To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION – Only qualified personnel can install this device with a battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow the required specifications to select appropriate cable size. It is very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts, which could cause an explosion.
- Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for details.
- A fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS – This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input short-circuited. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to a local dealer or service center for maintenance.
2. Product Overview
The Aninerel 4.2KW Hybrid Solar Inverter (Model ANL-4200T-24L-W-PRO) is designed for efficient solar energy management. It features a dual output for smart load management, lithium battery activation, and a colored LCD with RGB lights for easy monitoring.


2.1. Component Identification

The inverter features:
- LCD display: Shows operational status and information.
- Function buttons: For navigation and settings.
- RGB indicator: Provides visual status feedback.
- Grounding terminal: For safety grounding.
- RS232 communication port: For data communication.
- RS485 communication port: For data communication, especially with LiFePo4 batteries.
- AC input: Connection for utility grid or generator.
- Main out: Primary AC output.
- Second out: Secondary AC output for smart load management.
- Battery input: Connection for battery bank.
- PV input: Connection for solar panels.
- Power on/off switch: To power the unit on or off.
3. Setup
3.1. Unpacking and Inspection
Before installation, inspect the unit to ensure nothing inside the package is damaged. The package should contain:
- The inverter unit x 1
- User manual x 1
3.2. Preparation
Before connecting all wirings, remove the bottom port cover by unscrewing the two retaining screws.
3.3. Mounting the Unit
Consider the following points when selecting an installation location:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install the inverter at eye level for easy reading of the LCD display.
- The ambient temperature should be between 0°C and 55°C for optimal operation.
- The recommended installation position is vertically on a wall.
- Ensure sufficient clearance around the unit for heat dissipation and wiring access.
CAUTION: Suitable for mounting on concrete or other non-combustible surfaces only.

3.4. Battery Connection
CAUTION: For safety and regulation compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. It is still required to have over-current protection installed.
WARNING: All wiring must be performed by qualified personnel. It is very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce the risk of injury, use the proper recommended cable.

WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.
CAUTION!! Do not place anything between the flat part of the inverter terminal. Otherwise, overheating may occur.
CAUTION!! Do not apply anti-oxidant substance on the terminals before terminals are connected tightly.
CAUTION!! Before making the final DC connection or closing the DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).
Recommended Battery Cable & Terminal Size:
| Model | Maximum Amperage | Battery Capacity | Wire Size | Cable mm2 | Terminal Size (mm) L x W x D | Torque Value |
|---|---|---|---|---|---|---|
| 4.2KVA | 175A | 200AH | 1AWG | 50 | 37 x 15.3 x 6.4 | 4~6 Nm |
| 6.2KVA | 130A | 200AH | 2AWG | 35 | 37 x 15.3 x 6.4 | 4~6 Nm |
Battery Connection Steps:
- Make positive and negative cables based on the recommended terminal size.
- Connect all battery packs as required by the unit. It is suggested to use the recommended battery capacity.
- Insert the battery cable flatly into the battery connector of the inverter and ensure the bolts are tightened with a torque of 4~6Nm. Ensure correct polarity at both the battery and the inverter/charger, and that battery cables are tightly screwed to the battery connector.
3.5. AC Input/Output Connection
CAUTION: Before connecting to an AC input power source, install a separate AC breaker between the inverter and the AC input power source. This ensures the inverter can be securely disconnected during maintenance and is fully protected from over-current of AC input. A 50A AC breaker is recommended.
CAUTION: There are two terminal blocks with "IN" and "OUT" markings. Do NOT mis-connect input and output connectors.
WARNING: All wiring must be performed by qualified personnel. It is very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce the risk of injury, use the proper recommended cable size.
Suggested Cable Requirement for AC Wires:
| Model | Gauge | Torque Value |
|---|---|---|
| 4.2KVA | 10AWG | 1.4~1.6Nm |
| 6.2KVA | 10AWG | 1.4~1.6Nm |
AC Input/Output Connection Steps:
- Before making AC input/output connections, ensure the DC protector or disconnector is open.
- Remove 10mm of insulation sleeve for six conductors. Shorten phase L and neutral conductor N by 3mm.
- Insert AC input wires according to the polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor (yellow-green) first.
- PE: Ground (yellow-green)
- L: LINE (brown or black)
- N: Neutral (blue)
- WARNING: Be sure that the AC power source is disconnected before attempting to hardwire it to the unit.
- Insert AC output wires according to the polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor first.
- PE: Ground (yellow-green)
- L: LINE (brown or black)
- N: Neutral (blue)
- Make sure the wires are securely connected.
CAUTION: Important: Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are operated in parallel.
CAUTION: Appliances such as air conditioners require at least 2-3 minutes to restart to balance refrigerant gas. If a power shortage occurs and recovers quickly, it can damage connected appliances. Check if your air conditioner has a time-delay function. Otherwise, the inverter may trigger an overload fault to protect the appliance, but internal damage could still occur.
3.6. PV Connection
CAUTION: Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.
WARNING: All wiring must be performed by qualified personnel. It is very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce the risk of injury, use the proper recommended cable size.
Recommended Cable Size for PV Modules:
| Model | Typical Amperage | Cable Size | Torque |
|---|---|---|---|
| 4.2KVA | 27A | 10 AWG | 1.4~1.6 Nm |
| 6.2KVA | 27A | 10 AWG | 1.4~1.6 Nm |
PV Module Selection Parameters:
- Open circuit Voltage (Voc) of PV modules must not exceed the maximum PV array open circuit voltage of the inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than the minimum battery voltage.
Solar Charging Mode Specifications:
| Parameter | Value |
|---|---|
| INVERTER MODEL | 4.2KVA / 6.2KVA |
| Max. PV Array Open Circuit Voltage | 500VDC |
| PV Array MPPT Voltage Range | 60VDC~500VDC |
| Max. PV INPUT CURRENT | 27A |
PV Module Wire Connection Steps:
- Remove 6mm of insulation sleeve for positive and negative conductors.
- Check the correct polarity of the connection cable from PV modules and PV input connectors. Connect the positive pole (+) of the connection cable to the positive pole (+) of the PV input connector. Connect the negative pole (-) of the connection cable to the negative pole (-) of the PV input connector.
- Make sure the wires are securely connected.
3.7. Final Assembly
After connecting all wirings, reinstall the bottom port cover by screwing in the two screws.
4. Operation
4.1. Power ON/OFF
Once the unit has been properly installed and the batteries are connected, simply press the On/Off switch (located on the side of the case) to turn on the unit.
4.2. Operation and Display Panel
The operation and display panel on the front of the inverter includes three indicators, four function keys, and an LCD display, showing operating status and input/output power information.
RGB Indicator Messages:
| Mode | RGB Indicator | Message |
|---|---|---|
| Inverter mode | Green (Solid On) | Output is powered by battery or PV; Battery fully charged or not charged. |
| Green (Flashing) | Battery is charging (2s-on and 1s-off). | |
| AC mode | Blue (Solid On) | Output is powered by AC or PV in AC mode; Battery fully charged or not charged. |
| Blue (Flashing) | Battery is charging (2s-on and 1s-off). | |
| Standby mode | Cyan (Solid On) | Battery is fully charged or not charged. |
| Cyan (Flashing) | Battery is charging (2s-on and 1s-off). | |
| Fault mode | Red (Solid On) | Fault occurs in the inverter. |
| Bypass mode | Purple (Solid On) | Working in AC mode without charging. |
| Charging mode | Yellow (Solid On) | Battery is fully charged, when switch is off. |
| Yellow (Flashing) | Battery is charging, when switch is off. |
Function Keys:
| Function Key | Description |
|---|---|
| ESC | To exit setting mode. |
| UP | To go to previous selection. |
| DOWN | To go to next selection. |
| ENTER | To confirm the selection in setting mode or enter setting mode. |
4.3. LCD Display Description
The LCD display information cycles through different screens by pressing the function keys. Information is shown across five areas:
- Area 1: PV data (voltage, current, power).
- Area 2: Battery data (voltage, current, power, SOC).
- Area 3: AC output data (voltage, current, power, percentage, frequency).
- Area 4: AC input data (voltage, current, power, percentage, frequency).
- Area 5: Setting program code, Eco mode, buzzer status, error, or warning.
LCD Data Polling Display Mode:
- Simultaneously polling data: Press "UP" or "DOWN" to show all data from Area 1 to Area 4 simultaneously. All data updates with each press. Press "ESC" to return to the initial data.
- Independent polling data: Data for Areas 1-4 can be displayed independently:
- Press "Enter"; the circle icon of Area 1 will flash. Use "UP" or "DOWN" to display data for Area 1.
- Continue pressing "Enter"; the circle icon of Area 2 will flash. Use "UP" or "DOWN" to display data for Area 2.
- Repeat for Area 3 and Area 4.
- After Area 4, pressing "Enter" again will make the circle icon of Area 1 flash, returning to Area 1.
4.4. LCD Settings
To enter setting mode, press and hold the "Enter" key for 3 seconds. Use "UP" or "DOWN" to select programs, then "ENTER" to confirm or "ESC" to exit. The LCD will show the setting program code (Area 5), minimum value (Area 1), maximum value (Area 4), program item (Area 2), and current settable value (Area 3).
Detailed settings are available for various parameters, including output source priority, charging current, AC input voltage range, battery type, auto-restart functions, output voltage/frequency, bypass mode, buzzer mode, display settings, and battery equalization parameters. Refer to the full PDF manual for a comprehensive list of all setting programs and their options.
4.5. Battery Equalization
The equalization function in the charge controller helps reverse negative chemical effects like stratification and removes sulfate crystals from battery plates, extending battery lifecycle. It is recommended to equalize batteries periodically.
How to Apply Equalization Function:
Enable the battery equalization function in monitoring LCD setting program 33. Then, you can apply this function by:
- Setting the equalization interval in program 37.
- Activating equalization immediately in program 39.
When to Equalize:
In the float stage, when the set equalization interval (battery equalization cycle) is reached, or if equalization is activated immediately, the controller will enter the Equalize stage.
Equalize Charging Time and Timeout:
In the Equalize stage, the controller charges the battery until its voltage reaches the battery equalization voltage. Constant-voltage regulation maintains this voltage. The battery remains in the Equalize stage until the set battery equalized time is reached.
If the battery equalized time expires and the battery voltage does not reach the equalization voltage, the charge controller extends the equalized time until the battery voltage achieves the equalization voltage. If the battery voltage is still lower than the equalization voltage when the battery equalized timeout setting is over, the charge controller will stop equalization and return to the float stage.
4.6. Setting for Lithium Battery
If using a lithium battery with this inverter, only configured lithium batteries are supported. There are two connectors on the lithium battery: an RS485 port for BMS and a power cable.
Lithium Battery Connection Steps:
- Assemble the battery terminal based on recommended battery cable and terminal size (same as Lead-acid battery connection).
- Connect the RS485 port of the battery to the BMS (RS485) communication port of the inverter.
Lithium Battery Communication and Setting:
Ensure the BMS communication cable is connected between the battery and the inverter. This cable transmits information and signals. The inverter will re-configure charging voltage, charging current, and battery discharge cut-off voltage according to the lithium battery parameters and will start or stop charging based on the battery status.
RS485 Port Pin Assignment:
| Pin Number | RS485 Port |
|---|---|
| PIN1 | RS485-B |
| PIN2 | RS485-A |
| PIN7 | RS485-A |
| PIN8 | RS485-B |
LCD Setting for Lithium Battery:
After connecting, finish and confirm settings:
- Select program 05 as the lithium battery type.
- If communication is successful, the LCD will display:
- Communication successful icon: "Li" flashing.
- Max lithium battery charging voltage.
- Max lithium battery charging current.
- Lithium battery discharging forbidden: "Li" flashes once every 1 second.
- Lithium battery charging forbidden: "Li" flashes once every 2 seconds.
- Lithium battery SOC (%).
Setting for Lithium Battery Without Communication:
This method is for lithium battery applications without BMS communication. Follow these steps:
- Recommended method 1: Set battery type as "LIB" in program 05.
- Recommended method 2: Setting as follows:
- Before starting, obtain the battery BMS specification (Max charging voltage, Max charging current, Discharging protection voltage).
- Set battery type as "LIB" in program 05.
- Set C.V voltage as Max charging voltage of BMS-0.5V in program 26.
- Set floating charging voltage as C.V voltage in program 27.
- Set Low DC cut-off voltage ≥ discharging protection voltage in program 29.
- Set Max charging current in program 02, which must be less than the Max charging current of BMS.
- Set voltage point back to utility source when selecting "SBU priority" in program 12.
The setting value must be ≥ Low DC cut-off voltage + 2V, otherwise the inverter will show a warning for low battery voltage.
Remark:
- It is best to finish setting without turning on the inverter (just let the LCD show, no output).
- When you finish setting, please restart the inverter.
5. Specifications
5.1. Table 1 Line Mode Specifications
| INVERTER MODEL | 4.2KVA | 6.2KVA |
|---|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) | |
| Nominal Input Voltage | 230Vac | |
| Low Loss Voltage | 170Vac±7V (UPS); 90Vac±7V (Appliances) | |
| Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) | |
| High Loss Voltage | 280Vac±7V | |
| High Loss Return Voltage | 270Vac±7V | |
| Max AC Input Voltage | 300Vac | |
| Nominal Input Frequency | 50Hz / 60Hz (Auto detection) | |
| Low Loss Frequency | 40±1Hz | |
| Low Loss Return Frequency | 42±1Hz | |
| High Loss Frequency | 65±1Hz | |
| High Loss Return Frequency | 63±1Hz | |
| Output Short Circuit Protection | Battery mode: Electronic Circuits | |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) | |
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) | |
5.2. Table 2 Inverter Mode Specifications
| INVERTER MODEL | 4.2KVA | 6.2KVA |
|---|---|---|
| Rated Output Power | 4.2KVA / 4.2KW | 6.2KVA / 6.2KW |
| Dual output function | Yes | Yes |
| Max. main output power | 4.2KVA | 6.2KVA |
| Max. second output power | 4.2KW | 6.2KW |
| Output Voltage Waveform | Pure Sine Wave | |
| Output Voltage Regulation | 230Vac±5% | |
| Output Frequency | 50Hz or 60Hz | |
| Peak Efficiency | 94% | |
| Surge Capacity | 2* rated power for 5 seconds | |
| Nominal DC Input Voltage | 24Vdc | 48Vdc |
| Cold Start Voltage | 23.0Vdc | 46.0Vdc |
| Low DC Warning Voltage (Just for AGM and Flooded) @ load < 20% | 22.0Vdc | 44.0Vdc |
| Low DC Warning Voltage (Just for AGM and Flooded) @ 20% ≤ load < 50% | 21.4Vdc | 42.8Vdc |
| Low DC Warning Voltage (Just for AGM and Flooded) @ load ≥ 50% | 20.2Vdc | 40.4Vdc |
| Low DC Warning Return Voltage (Just for AGM and Flooded) @ load < 20% | 23.0Vdc | 46.0Vdc |
| Low DC Warning Return Voltage (Just for AGM and Flooded) @ 20% ≤ load < 50% | 22.4Vdc | 44.8Vdc |
| Low DC Warning Return Voltage (Just for AGM and Flooded) @ load ≥ 50% | 21.2Vdc | 42.4Vdc |
| Low DC Cut-off Voltage (Just for AGM and Flooded) @ load < 20% | 21.0Vdc | 42.0Vdc |
| Low DC Cut-off Voltage (Just for AGM and Flooded) @ 20% ≤ load < 50% | 20.4Vdc | 40.8Vdc |
| Low DC Cut-off Voltage (Just for AGM and Flooded) @ load ≥ 50% | 19.2Vdc | 38.4Vdc |
5.3. Table 3 Charge Mode Specifications
| Utility Charging Mode | 4.2KVA | 6.2KVA |
|---|---|---|
| Max Charging Current (PV+AC) (@ VI/P=230Vac) | 120Amp | 120Amp |
| Max Charging Current (AC) (@ VI/P=230Vac) | 120Amp | 120Amp |
| Bulk Charging Voltage (Flooded Battery) | 29.2Vdc | 58.4Vdc |
| Bulk Charging Voltage (AGM / Gel Battery) | 28.2Vdc | 56.4Vdc |
| Floating Charging Voltage | 27Vdc | 54Vdc |
| Overcharge Protection | 32Vdc | 63Vdc |
| Battery reverse connection protection | No | No |
| Charging Algorithm | 3-Step | |
Solar Input Specifications:
| Parameter | 4.2KVA | 6.2KVA |
|---|---|---|
| Rated Power | 6200W | 9000W |
| Max. PV Array Open Circuit Voltage | 500Vdc | |
| PV Array MPPT Voltage Range | 60Vdc~500Vdc | |
| Max. Input Current | 27A | |
| Max. Charging Current (PV) | 120A | |
5.4. Table 4 General Specifications
| INVERTER MODEL | 4.2KVA | 6.2KVA |
|---|---|---|
| Operating Temperature Range | -10°C to 55°C | |
| Storage temperature | -15°C ~ 60°C | |
| Humidity | 5% to 95% Relative Humidity (Non-condensing) | |
| Dimension (D*W*H), mm | 368x328x120 | |
| Net Weight, kg | 7.0 | 8.0 |
6. Troubleshooting
6.1. Fault Reference Code
| Fault Code | Fault Event | What to do |
|---|---|---|
| 01 | Over temperature of inverter module | Check for proper ventilation and ambient temperature. |
| 02 | Over temperature of DCDC module | Check for proper ventilation and ambient temperature. |
| 03 | Battery voltage is too high | Check battery charging settings and battery health. |
| 04 | Over temperature of PV module | Check PV module temperature and ventilation. |
| 05 | Output short circuited. | Check for short circuits in the output wiring and connected loads. |
| 06 | Output voltage is too high. | Contact qualified service personnel. |
| 07 | Overload time out | Reduce connected load. |
| 08 | Bus voltage is too high | Contact qualified service personnel. |
| 09 | Bus soft start failed | Contact qualified service personnel. |
| 10 | PV over current | Check PV input current and panel configuration. |
| 11 | PV over voltage | Check PV input voltage and panel configuration. |
| 12 | DCDC over current | Contact qualified service personnel. |
| 13 | Over current or surge | Reduce connected load or check for surge events. |
| 14 | Bus voltage is too low | Contact qualified service personnel. |
| 15 | Inverter failed (Self-checking) | Contact qualified service personnel. |
| 18 | Op current offset is too high | Contact qualified service personnel. |
| 19 | Inverter current offset is too high | Contact qualified service personnel. |
| 20 | DC/DC current offset is too high | Contact qualified service personnel. |
| 21 | PV current offset is too high | Contact qualified service personnel. |
| 22 | Output voltage is too low | Contact qualified service personnel. |
| 23 | Inverter negative power | Contact qualified service personnel. |
| 24 | Op2 current offset is too high | Contact qualified service personnel. |
6.2. Warning Indicator
| Warning Code | Warning Event | Audible Alarm |
|---|---|---|
| 02 | Temperature is too High | Beep three times every second |
| 04 | Low battery | Beep once every second |
| 07 | Overload | Beep once every 0.5 second |
| 10 | Output power derating | Beep twice every 3 seconds |
| 14 | Fan blocked | None |
| 15 | PV energy is low | Beep twice every 3 seconds |
| 19 | Lithium Battery communication is failed | Beep once every 0.5 second |
| 21 | Lithium Battery over current | None |
| 22 | The load exceeds the set value of program 47 | None |
| E9 | Battery equalization | None |
| 6P | Battery is not connected | None |
7. Maintenance
Regular maintenance is crucial for the longevity and optimal performance of your Aninerel Hybrid Solar Inverter. Always ensure the unit is powered off and all power sources (AC, DC, PV) are disconnected before performing any maintenance.
- Cleaning: Periodically clean the exterior of the inverter and ensure ventilation openings are free from dust and debris. The detachable dust cover can be removed for cleaning in harsh environments.
- Connections: Regularly check all electrical connections (battery, AC input/output, PV input) for tightness and signs of corrosion. Re-tighten connections to the specified torque values if necessary.
- Battery Health: Monitor battery voltage and performance. Utilize the battery equalization function as recommended to optimize battery performance and extend its lifecycle.
- Environmental Check: Ensure the installation environment remains within the specified operating temperature and humidity ranges. Verify that there is adequate airflow around the unit.
- Firmware Updates: Check the manufacturer's website or contact support for any available firmware updates that may improve performance or add features.
WARNING: Only qualified personnel should perform internal maintenance or repairs. Incorrect procedures can lead to electric shock or fire.
8. User Tips
- Remote Monitoring: Utilize the built-in WiFi and smart app to monitor your inverter's status and performance remotely. This can help in early detection of issues.
- Battery Management: Pay close attention to battery settings, especially for lithium batteries. Ensure correct battery type selection (Program 05) and proper communication via RS485 for optimal performance and protection.
- Load Management: Take advantage of the dual output for smart load management to prioritize critical appliances.
- Generator Compatibility: If using a generator as an AC input source, be aware that unstable generator output might affect inverter stability. Ensure your generator provides a stable power supply.
- Appliance Protection: For sensitive appliances like air conditioners, ensure they have a built-delay function to prevent damage from rapid power fluctuations.
9. Warranty and Support
For detailed warranty information, please refer to the warranty card included with your product or contact the Aninerel Official Store directly. Keep your purchase receipt as proof of purchase for any warranty claims.
If you encounter any issues that cannot be resolved using the troubleshooting guide in this manual, please contact the seller or a qualified service center for assistance. The full user manual in PDF format is available for download from the product page or by contacting customer support.
This manual is for informational purposes only. Specifications are subject to change without notice.