1. Product Overview
The Gaqqee ETC-974 is a versatile digital temperature controller designed for precise temperature management in various applications, including refrigerators, cold storage, air conditioning systems, industrial chillers, and greenhouses. It features an intelligent digital display, intuitive controls, and independent management of compressor, defrosting, and fan functions.
Video: Product overview showing the temperature controller from various angles and its components.

Figure 1: Front view of the ETC-974 Digital Temperature Controller.
2. Setup and Installation
2.1 Mounting
- The ETC-974 features a rail-type buckle design for easy installation.
- No complex tools are required; simply snap the controller into place on a compatible rail.
- Ensure the mounting location allows for adequate ventilation and access to wiring terminals.
2.2 Wiring
Proper wiring is crucial for safe and correct operation. Refer to the wiring diagram below and ensure all connections are secure and match your power supply voltage.

Figure 2: ETC-974 Wiring Diagram.
| Terminal No. | Function | Rating |
|---|---|---|
| 1, 2 | Defrost (Def) | 250V 3A |
| 3 | Light | 250V 3A |
| 4 | Compressor (Comp) | 250V 14A |
| 5 | Fan | 250V 14A |
| 6, 7 | Power Supply Input | DC 12V/24V or AC 110V/220V (as selected) |
| 8, 9, 10 | Probe Connections (Pb1, Pb2) | N/A |
2.3 Probe Connection
- Connect the provided waterproof air probes to the Pb1 and Pb2 terminals (8, 9, 10).
- Position the probes in the area where temperature measurement is required. The probes are designed for rapid temperature collection and minimal drift.
3. Operating Instructions
3.1 Display and Controls
The ETC-974 features an intelligent digital display and a user-friendly button interface:
- Digital Display: Shows the current temperature in Celsius (°C).
- Up Arrow (▲): Used to increase values or navigate menus.
- Down Arrow (▼): Used to decrease values or navigate menus.
- FNC (Function) Button: Typically used to access function menus or switch modes.
- SET Button: Used to enter setting mode, confirm selections, or save parameters.
- Icons: Indicators for fan operation and cooling/defrost status (snowflake icon).
3.2 Basic Operation and Settings
Detailed operational procedures, including setting temperature setpoints, differential values, defrost cycles, and other advanced parameters, are typically found in the comprehensive user manual. Please refer to the PDF manual for full instructions.
The controller offers independent control over the compressor, defrosting element, and fan, allowing for efficient and customized operation based on your application's needs.
4. Maintenance
- Cleaning: Periodically wipe the controller's surface with a soft, dry cloth. Do not use abrasive cleaners or solvents.
- Probe Inspection: Regularly check the temperature probes for any physical damage or corrosion. Ensure they are securely connected and properly positioned.
- Ventilation: Ensure that the controller's housing has adequate airflow to prevent overheating.
5. Troubleshooting
- No Display: Check the power supply connection to terminals 6 and 7. Ensure the correct voltage (DC 12V/24V or AC 110V/220V) is being supplied.
- Incorrect Temperature Reading: Verify that the temperature probes (Pb1, Pb2) are correctly connected to terminals 8, 9, 10 and are positioned accurately in the environment being measured. Check for any damage to the probe cables.
- Controller Not Responding: Power cycle the device by disconnecting and reconnecting the power supply. If the issue persists, consult the full user manual for advanced troubleshooting or contact support.
6. Specifications
| Feature | Specification |
|---|---|
| Model Number | ETC-974 |
| Temperature Control Range | -50℃ to 110℃ |
| Display Resolution | 1℃ / 0.1℃ (between integer and decimal) |
| Temperature Accuracy | NTC ± 0.5℃ (-30-50℃), other ± 1℃ |
| Power Supply Options | DC 12V, DC 24V, AC 110V, AC 220V |
| Product Dimensions (L x W x H) | 77mm x 62mm x 35mm (3.03in x 2.44in x 1.38in) |
| Probe Cable Length | 2 meters |
| Certification | CE |
| Display Type | DIGITAL |
| Display Size | 1.9 Inches & Under |
| Data Record | Yes |

Figure 3: ETC-974 Product Dimensions.

Figure 4: ETC-974 Typical Applications.
7. User Tips
- Always double-check your power supply voltage (DC 12V/24V or AC 110V/220V) before connecting the controller to prevent damage.
- Ensure all wiring connections are tight and insulated to avoid short circuits or electrical hazards.
- For optimal temperature sensing, place the probe away from direct heat sources or extreme drafts.
8. Warranty and Support
For detailed warranty information, advanced operational guides, and technical support, please refer to the official Gaqqee ETC-974 user manual. A PDF version of the manual may be available for download from the seller or manufacturer's website.
You can access the full user manual PDF here: Gaqqee ETC-974 User Manual (PDF)