SINOTIMER DDS6619

Contents

SINOTIMER DDS6619 Digital Electricity Usage Monitor

Instruction Manual

1. Introduction

Thank you for choosing the SINOTIMER DDS6619 Digital Electricity Usage Monitor. This device is designed for accurate measurement of single-phase AC active energy, providing real-time data on electricity consumption, voltage, current, power, frequency, and power factor. Its compact design and DIN rail installation make it suitable for various indoor fixed installations in homes and businesses.

2. Safety Information

  • Installation and maintenance should only be performed by qualified personnel.
  • Ensure the main power supply is disconnected before any installation, wiring, or maintenance work to prevent electric shock.
  • Verify that the voltage and current ratings of the device match your electrical system.
  • Do not operate the device if it appears damaged.
  • Keep the device away from moisture, dust, and extreme temperatures.

3. Package Contents

  • 1 x SINOTIMER DDS6619 Digital Electricity Usage Monitor

4. Product Overview

4.1 Front View and Display

Front view of SINOTIMER DDS6619 Digital Electricity Usage Monitor showing LCD display with kWh and Voltage readings.
Front view of the DDS6619 Energy Meter. The display shows total kWh consumption on the upper line and other parameters (Voltage, Current, Power) rotating on the lower line.

4.2 Display Modes

Diagram showing three display modes: kWh + Voltage, kWh + Current, and kWh + Power.
The meter cycles through different display modes, showing kWh combined with Voltage, Current, or Power.

4.3 Dimensions

Diagram showing the dimensions of the energy meter: 7.8cm height, 3.5cm width, and 6.5cm depth.
Dimensions of the SINOTIMER DDS6619 Energy Meter: Height 7.8cm (3.07in), Width 3.5cm (1.38in), Depth 6.5cm (2.56in).

5. Setup and Installation

The DDS6619 is designed for 35mm DIN rail installation. Ensure all power is off before proceeding with installation.

5.1 Wiring Diagram

Wiring diagram showing connections for Power switch, Energy Meter, and Air circuit breaker. Live (L) and Neutral (N) wires connect from the power switch to the meter, and then from the meter to the air circuit breaker.
Wiring Diagram: Connect the Live (L) and Neutral (N) wires from your power source (e.g., Power switch) to the corresponding L and N terminals on the top of the Energy Meter. Then, connect the L and N terminals on the bottom of the Energy Meter to your load protection device (e.g., Air circuit breaker) and subsequently to your electrical load.

Important: Always ensure correct polarity (Live and Neutral) and secure all connections to prevent loose contacts and potential hazards.

6. Operating Instructions

Once correctly installed and powered on, the DDS6619 will automatically begin measuring and displaying electrical parameters.

6.1 Display Functionality

  • The device features an LCD backlit digital display for clear readability.
  • The upper line of the display consistently shows the total power consumption in kWh.
  • The lower line of the display automatically rotates through various parameters: Voltage (V), Current (A), Power (KW), Frequency (Hz), and Power Factor.
  • No user interaction is typically required for basic operation; the display cycles automatically.

7. Maintenance

  • The DDS6619 is designed for maintenance-free operation.
  • To clean the device, gently wipe the exterior with a soft, dry cloth. Do not use abrasive cleaners or solvents.
  • Ensure the device remains free from dust and moisture for optimal performance and longevity.
  • Periodically check electrical connections for tightness, especially after initial installation.

8. Troubleshooting

  • No Display: Check if the power supply is connected correctly and if there is power to the circuit. Ensure all wiring is secure.
  • Incorrect Readings: Verify that the wiring is correct according to the diagram, especially Live and Neutral connections. Ensure the device is rated for your system's voltage and current.
  • Device Not Functioning: If the device does not operate after checking power and connections, disconnect power and contact customer support.

9. Specifications

CertificationCE
OriginMainland China
DIY SuppliesElectrical
Display TypeDigital Only (LCD backlit)
Model NumberDDS6619 (Energy Meters)
PhaseSingle-phase
MaterialPlastic
AccuracyLevel 1
Reference Voltage220V/230V 50/60Hz
Reference Current (Max)5(80) A
Insulation PerformanceAC voltage 4KV for 1min, pulse voltage of 1.2/50us 6KV waveform
Installation35mm DIN rail
Wiring MethodUp and down / Up and down
Max Power17000W
Current Rate1600imp/kWh
Ambient Temperature-20°C ~ +50°C
Pole Width17.5mm / 0.7in
FunctionsDisplay power, voltage, current, frequency, power factor
DimensionsApprox. 78x65x35mm / 3.07x2.55x1.37inch

10. Warranty and Support

The SINOTIMER DDS6619 Digital Electricity Usage Monitor comes with a standard manufacturer's warranty. For warranty claims, technical support, or any inquiries regarding your device, please contact the seller or the manufacturer directly with your purchase details.

© 2023 SINOTIMER. All rights reserved.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.