1. Product Overview
The Adjustable AC Current Sensing Switch is a self-powered device designed for monitoring and detecting AC current in electrical equipment. It offers high accuracy, stable performance, and a long service life, making it suitable for various industrial automation and power monitoring applications.
For a comprehensive guide, please refer to the official user manual PDF: View PDF Manual
2. Setup and Installation
ATTENTION: BEFORE INSTALLATION, YOU MUST READ THE INSTRUCTIONS CAREFULLY TO ENSURE PROPER OPERATION.
2.1 Package Contents
- 1 x AC Current Sensing Switch
- 1 x User Manual (Chinese & English)
2.2 Mounting
The switch is designed for installation on a 35mm DIN guide rail. Ensure the mounting location is stable and free from excessive vibration or moisture.
2.3 Wiring
The device operates on the principle of electromagnetic mutual inductance and is self-powered, requiring no external power supply for its sensing function.
- Current Path: The AC current to be monitored should pass through the 8mm threading hole in the center of the switch.
- Control Output: Connect your control circuit (e.g., flashlight, buzzer, relay, microcontroller) to the K1 and K2 terminals. The switch contact capacity is a maximum of 0.5A@12-240VAC/DC.


3. Operating Instructions
3.1 Current Threshold Adjustment
The switch has an adjustable current sensing range from 0.2A to 30A. Use the 'L' (Low) and 'H' (High) knob on the front panel to set the desired current threshold. Turning towards 'H' increases the threshold, while turning towards 'L' decreases it.
3.2 Indicator Lights
- Green LED: Indicates the switch is in the 'OFF' state (current below threshold or no current).
- Red LED: Indicates the switch is in the 'ON' state (current above threshold).
3.3 Switch Type
This model is available in two types: Normally Open (NO) or Normally Closed (NC). Ensure you have the correct type for your application:
- Normally Open (NO): The output contacts are open when the current is below the threshold and close when the current exceeds the threshold.
- Normally Closed (NC): The output contacts are closed when the current is below the threshold and open when the current exceeds the threshold.
4. Maintenance
The AC Current Sensing Switch is designed for long-term, maintenance-free operation. To ensure optimal performance:
- Keep the device clean and free from dust and debris.
- Periodically inspect wiring connections to ensure they are secure.
- Avoid exposing the device to extreme temperatures or humidity outside its specified operating range.
5. Troubleshooting
If the device is not functioning as expected, consider the following:
- No Indication/Output: Verify that the AC current is flowing through the sensing hole and is within the 0.2-30A range. Check all wiring connections to K1 and K2.
- Incorrect Switching: Adjust the L/H knob to fine-tune the current threshold. Ensure the monitored current is stable.
- LEDs Not Lighting: Confirm that current is flowing through the sensing hole. The device is self-powered by the sensed current.
- Output Always On/Off: Check if the switch type (NO/NC) matches your application's requirements.
6. Specifications
| Feature | Specification |
|---|---|
| Model | GS22618 |
| Switch Type | Normally Open (NO) / Normally Closed (NC) (Optional) |
| Power Supply | Self-Powered (No External Power Required) |
| Starting Current / Frequency Range | 0.2 - 30A, 40 - 400Hz |
| Startup Time | < 0.1s |
| Switch Contact Capacity | Max: 0.5A @ 12-240VAC/DC |
| Overload Capacity | +100% @ 30A |
| Threading Hole Diameter | 8mm |
| Indicator Lights | Red (ON), Green (OFF) |
| Installation Form | Guide Rail 35mm DIN |
| Shell Material | Fireproof ABS |
| Working Temperature | -10 ~ 55 °C |
| Working Humidity | 0-95%, No Condensation |
| IP Rating | IP30 |
| Dimensions | 52 x 68 x 25mm / 2.05 x 2.68 x 0.98in |
| Rated Capacity | =1000VA |
| EU LVD Voltage | Below 50Vac or 75Vdc |
| Origin | Mainland China |
| Certification | GMP |
7. User Tips
- Always test the switch's functionality with a known current source after installation and before deploying it in a critical application.
- Ensure the current path through the sensing hole is clean and free of obstructions for accurate readings.
- When adjusting the threshold, make small increments and observe the indicator lights for precise calibration.
8. Warranty and Support
For technical support, warranty claims, or further inquiries, please contact the manufacturer or their authorized representative:
Manufacturer
Company Name: Shanghai Xuanyun Trading Co., Ltd.
Full Address: Room 273, No. 305 Qianxin Road, Jinshanwei Town, Jinshan District, Shanghai, China
Email: b156sumaitn2810@163.com
Telephone: +86-13876659210
EU Authorized Representative
AR Company Name: SOLID AUTHORITY LIMITED
Full Address: IE-51 Bracken Road, Sandyford, Dublin 18, D18 CV48, Ireland
Email: phoebe8706@gmail.com
Telephone: +33-761441379