1. Introduction

The TOMZN TOB9-50LW is a compact, high-performance WiFi smart circuit breaker designed for comprehensive electrical circuit management. This device integrates multiple functionalities, allowing for precise measurement and protection within your electrical system.

It can measure various parameters including voltage, current, active power, energy consumption (kWh), frequency, power factor (PF), leakage current, and environmental temperature. The TOB9-50LW offers robust protection features such as overvoltage, undervoltage, overcurrent, overtemperature, and leakage protection, along with a current limiting function. All parameters can be viewed and modified directly on the device's display or remotely via a dedicated mobile application.

A notable design feature is its external NTC interface for temperature measurement, which ensures accurate ambient temperature readings by isolating the sensor from the device's internal heat generation. Its ultra-small form factor reduces its size by 40% compared to similar devices, making it suitable for installations where space is a premium.

2. Safety Information

WARNING: To avoid danger of suffocation, keep packaging away from babies and children. Do not use this bag in cribs, beds, carriages, or playpens. This bag is not a toy.

General Safety Precautions:

  • After receiving the product, ensure that an electrical professional performs the installation and initial operation.
  • Connect the equipment strictly in accordance with the provided wiring diagram specifications.
  • Adjust all equipment parameters according to the instructions in this manual.
  • Do not place the device near flammable materials.
  • Ensure adequate ventilation around the device during operation to prevent overheating.
  • Disconnect the device from power and store it properly when not in use for extended periods.

3. Product Features

The TOB9-50LW smart circuit breaker offers a wide array of features for enhanced control and monitoring:

  • Remote Control: Turn the device ON/OFF anytime, anywhere via your smartphone.
  • Real-time Monitoring: View current, voltage, power, leakage current, total kWh, temperature, power factor (PF), and frequency directly on the device's TFT screen or through the mobile app.
  • Adjustable Protection Settings: Customize thresholds for overvoltage, undervoltage, overcurrent, leakage current, and over-temperature protection via the app or manually on the device.
  • Overcurrent Threshold Levels: Configure up to three distinct overcurrent protection groups with adjustable current ranges (1A-63A) and time settings (00:00-23:59).
  • Automatic Reconnect: Adjustable delay on time (1s-500s) for automatic reconnection after a fault.
  • Measurement Calibration: Voltage, current, and power readings can be calibrated within a range of -20% to +20%.
  • Fast Action Time: Protection action time is adjustable from 1-30 seconds (default 1s).
  • Low Power Consumption: The device consumes less than 2W.
  • Smart Home Integration: Compatible with Tuya Smart Life app, Amazon Alexa, Google Assistant, IFTTT, and Google Nest.
  • External NTC Interface: Provides accurate ambient temperature measurement.
  • Compact Design: Ultra-small size (23mm width) for space-saving installation.
Multifunction overview of the TOMZN TOB9-50LW smart circuit breaker, highlighting its various protective and measurement functions.
Multifunction overview of the TOMZN TOB9-50LW smart circuit breaker, highlighting its various protective and measurement functions.
8-in-1 Multi-function Electricity Meter display, showing Voltage, Current, Power, Energy, Leakage, Frequency, Power factor, and Temperature.
8-in-1 Multi-function Electricity Meter display, showing Voltage, Current, Power, Energy, Leakage, Frequency, Power factor, and Temperature.
Overview of protection features including Leakage Protection, Overvoltage protection, Undervoltage protection, Overcurrent protection, 8-in-1 display, and WIFI Smart networking.
Overview of protection features including Leakage Protection, Overvoltage protection, Undervoltage protection, Overcurrent protection, 8-in-1 display, and WIFI Smart networking.

4. Specifications

The following table details the technical parameters of the TOB9-50LW smart circuit breaker:

Product parameter table showing various functions and their technical specifications.
Product parameter table showing various functions and their technical specifications.
Technical Parameters
FunctionTechnical ParameterFunctionTechnical Parameter
Input voltageAC 80-300VPower-on delay time1-500s (default 10s)
Voltage/current/kW calibration-20% ↔ +20%Display interval delay time1-500s (default 15s)
Over-voltage protection value120-300V (default 270V)Over-voltage recovery value115-265V (default 225V)
Under-voltage protection value80-210V (default 170V)Under-voltage recovery value85-215V (default 175V)
Over-current protection1-63A (default 40A)Over-current recovery0.5-59.5A
Over Temperature protection value40-100°C (default 80°C)Over Temperature recovery value35-95°C (default 75°C)
Leakage protection value10-99mA (default 30mA)Continuous over current / leakage faults times1-20 times (default OFF)
Recovery delay time1-500s (default 30s)Action time1-30s (default 1s)
WiringTop in Bottom outPower consumption≤2W
Electrical and mechanical life≥100000 cyclesBoundary dimension88 × 22 × 68 MM

Physical Dimensions:

Diagram showing the dimensions of the TOMZN TOB9-50LW smart circuit breaker: 88mm height, 22mm width, 68mm depth.
Dimensions of the TOMZN TOB9-50LW: 88mm (H) x 22mm (W) x 68mm (D).

5. Installation and Setup

Professional installation by a qualified electrician is highly recommended.

Wiring Instructions:

The device is designed for 'Top in Bottom out' wiring. When connecting the power input through the Line (L) and Neutral (N) terminals, ensure to properly penetrate the insulating layer of the power lines for secure connections.

Wiring diagram for the TOMZN TOB9-50LW Multi-Function Protector, showing connections with a Power Switch and an Air Circuit Breaker.
Wiring diagram for the TOMZN TOB9-50LW Multi-Function Protector. Connect Power In to the top terminals (L, N) and Power Out from the bottom terminals (L, N).

Initial Setup:

After physical installation, adjust the equipment parameters according to the instructions provided in this manual and the mobile application.

6. Operation

Manual Controls:

The device features a clear TFT display and rubber buttons for direct interaction:

Diagram of the device's display and buttons, indicating functions like manual switch, set key, adjustment keys, test key, and NTC interface.
Device display and button functions.
  1. Manual switch (ON/OFF button): Red button to manually turn the device on or off.
  2. Set key: Long press for 3 seconds to enter the setting interface. Long press for 5 seconds to configure WiFi.
  3. Adjustment key +: Increases value in setting menu.
  4. Test key: Press to test leakage protection.
  5. Adjustment key -: Reduces value in setting menu.
  6. NTC interface: Connect the external sensor wire to measure temperature.

Display Information:

The TFT screen provides real-time data:

  • Actual voltage display
  • Actual current display
  • Active power display
  • Kilowatt-hour (kWh) display
  • Leakage value display
  • WiFi network status
  • Frequency display
  • Power factor (PF) display
  • Sensor temperature
  • Power output status

Mobile App Control (Tuya Smart Life):

The TOB9-50LW can be conveniently controlled and monitored using the Tuya Smart Life app (supports 2.4G Wireless Network only, not 5G).

TOMZN smart circuit breaker with a smartphone displaying the Tuya app interface, showing real-time electricity data.
View device data and control remotely via the mobile app.
  • Remote ON/OFF: Control the circuit breaker from anywhere.
  • Real-time Data: Access all measured parameters instantly.
  • Historical Data: View electricity statistics (current, voltage, power) over time.
  • Timed Operations: Set schedules, timers, or loop timers for appliances.
  • Protection Settings: Adjust over/under voltage, overcurrent, and leakage protection thresholds.
Smartphone screen showing the 'Add Schedule' interface for timed appliance control.
Set schedules and timers for connected appliances.
Multiple smartphone screens displaying electricity statistics, including current, voltage, and power over various time periods.
Real-time and historical data of the circuit are clearly displayed in the app.
Smartphone screens showing app settings for over-current, over-voltage, under-voltage, and leakage alarms and controls.
App interface for setting various protection thresholds.

Setting Parameters:

Parameters can be adjusted via the device's buttons or the mobile app. Refer to the 'Product setting' table for detailed options.

Product setting table detailing various parameters, their setting ranges, default values, and adjustment steps.
Product setting table for detailed parameter configuration.

General Setting Procedure:

  1. Long press the SET button for 3 seconds to enter the settings menu.
  2. If there is no operation within 30 seconds, the device will automatically save and return to the display screen.
  3. Manual switch: Connect/disconnect the circuit line by pressing the ON/OFF key.
  4. Adjust the setting value by pressing the + and - keys.
  5. During the setting process, it is not necessary to press to the last step, but long press the SET key to save.

Overcurrent Protection with Time Period Rate Limiting:

The overcurrent value can be set differently for various time periods. The device supports three groups of overcurrent protection settings.

Diagram illustrating three levels of overcurrent protection settings with adjustable current ranges and time periods.
Configure up to three levels of overcurrent protection with specific time ranges.

Example 1:

  • Level 1 [5.0] A + TIME [08:00] (08:00 to 12:00, 5A overcurrent protection is implemented).
  • Level 2 [10.0] A + TIME [12:00] (12:00 to 17:00, 10A overcurrent protection is implemented).
  • Level 3 [15.0] A + TIME [17:00] (17:00 to 08:00 (the next day), 15A overcurrent protection is implemented).

Note: The time setting in Level 1/2/3 corresponds to the 24-hour time sequence. You must set time from morning to night (e.g., from early to late). Otherwise, the settings of Level 2/3 will not work, and the device will only implement Level 1 setting.

Example 2:

  • Level 1 [5.0] A + TIME [14:00] (the device only implements Level 1 setting).
  • Level 2 [10.0] A (5A overcurrent protection is implemented as default).
  • Level 3 [15.0] A + TIME [05:00].

Temperature Measurement and Over-Temperature Protection:

The external NTC interface provides accurate temperature measurement. If the measured temperature exceeds the set threshold, the equipment will automatically shut off to prevent damage.

Image showing the device display with a high temperature threshold setting of 80 degrees Celsius.
Temperature measurement and over-temperature protection settings.

7. Maintenance

  • Ensure adequate ventilation around the device to prevent dust accumulation and maintain optimal operating temperature.
  • Regularly check for any loose connections or signs of wear.
  • Disconnect from power before cleaning. Use a dry, soft cloth for cleaning.
  • If the device is not in use for extended periods, disconnect it from the power supply and store it in a dry, cool place.

8. Troubleshooting

Automatic Circuit Cut-off:

The device is designed to automatically cut off the circuit under certain conditions:

  • Over/Under Voltage Protection: If the circuit voltage is too high or too low, the equipment will automatically cut off the circuit to protect connected appliances. The product will cut off the power supply and wait until the voltage returns to a stable level before allowing recovery.
  • Overcurrent Protection: When electrical appliances draw too much current, wires may overheat and cause a fire. The protection disconnects power in 1 second to prevent fire, and self-recovers after troubleshooting.
  • Leakage Protection: When a leakage fault occurs in the system, this product can quickly cut off the power supply. It will automatically restart the power supply once the leakage fault disappears.
  • Over-Temperature Protection: If the ambient temperature measured by the NTC sensor exceeds the set threshold, the device will shut off.
Image showing the device display with over current protection time set to 001s.
Overcurrent protection can be set by yourself. Long press the setting button for 5 seconds, then press the up and down keys to adjust the required current according to your power consumption.
Image showing the device display with leakage protection settings.
Leakage Protection can be set by yourself. When a leakage fault occurs, the device cuts off power and restarts when the fault disappears.
Image showing the device display with over/under voltage protection settings.
Over/under voltage protection value can be set by yourself. The device will cut off power if voltage is outside normal range.

9. User Tips

  • Installation: Many users find the installation process super easy. The device works with both 110V and 220V systems.
  • Home Assistant Integration: The module is compatible with Home Assistant for automation. However, note that the temperature sensor data might only be available in the Tuya app and not directly displayed in Home Assistant.
  • Monitoring Speed: Real-time monitoring of parameters is generally fast with almost no delay.
  • Space Saving: The narrower design of the unit can save space on DIN rails, although it might still be wider than some standard components.
  • Power Outage Recovery: After a power outage, the switch typically needs to be turned on manually.
  • Self-Consumption: Be aware that this product has a higher self-consumption (around 1.27W) compared to some similar devices (e.g., 0.46W). This might be a consideration for off-grid systems.

10. Warranty and Support

Applicable Regulations and Harmonized Standards:

  • Low Voltage Directive 2014/35/EU
  • Electromagnetic compatibility Directive 2014/30/EU
  • Restriction of the use of certain hazardous substances (RoHS) Directive 2011/65/EU

For further assistance or detailed information, please refer to the official user manual PDF available at: TOMPD-63SW User Manual (PDF).

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.