1. Introduction
The GEYA GPS8-18 is a three-way AC220V (L1, L2, L3-N) automatic transfer switch designed for efficient and safe power management. It features integrated overvoltage, undervoltage, and overcurrent monitoring and protection functions. The device includes a digital display for real-time voltage and current values, along with an LED fault indicator. Key protection values and power switching priority are fully configurable.
This device is ideal for power conversion among photovoltaic inverters, mains power, and generators. It also supports electricity usage scenarios in three-phase power systems where different phases can be selected as single-phase power sources, effectively functioning as a phase selector.
The GPS8-18 enhances safety and reliability by integrating overvoltage and overcurrent protection, reducing the need for additional external protection equipment and saving installation space.
2. Safety Information
- The products must be installed by qualified electricians.
- All and any electrical connections of the time relay shall comply with the appropriate safety standards.
- This product does not have an isolation function. Always disconnect the superior MCB (Miniature Circuit Breaker) during maintenance to ensure safety.
- Ensure proper grounding according to local electrical codes.
3. Setup and Installation
3.1 DIN Rail Mounting
The GPS8-18 is designed for 35mm standard DIN rail installation and can be directly installed in household lighting distribution boxes. It features securing clips for easy installation and tunnel-type wiring ports for secure wiring.

Image: GEYA GPS8-18 installed in a distribution box, demonstrating 35mm standard rail installation.
Installation Steps:
- Ensure the back panel display is visible.
- Press the latch on the device.
- Insert the device into the DIN rail.
- Release the latch to secure the device.

Image: Step-by-step guide for simple DIN rail installation.
3.2 Wiring Diagram
The GPS8-18 model accepts three input power sources (L1, L2, L3) and a neutral wire (N). The output is L-N. Connect the upper end terminal to the neutral wire of the three-phase power supply. L1, L2, and L3 are connected to the live wires of three separate power supplies. Connect the lower end to the output load.

Image: Wiring diagram for the GPS8-18, illustrating connections for three-phase power inputs and load output.
NOTE: This product does not have an isolation function. Always disconnect the superior MCB during maintenance.
4. Operating Instructions
4.1 Panel Diagram and Controls

Image: Detailed panel diagram with labels for indicators and buttons.
- Select Phase Indicator (L1, L2, L3): Indicates the currently selected phase.
- Operating Voltage Value: Digital display showing voltage for each phase.
- Operating Current Value: Digital display showing load current.
- Fault Indicator (FLT): LED to indicate fault conditions.
- Power Button (✅): Used to manually turn on or off the load.
- 'M' Key: Press and hold for 3 seconds to enter parameter settings. Press and hold for 3 seconds again to save settings.
- Up Arrow Key (▲): Used to increase values when setting parameters.
- Down Arrow Key (▼): Used to reduce values when setting parameters.
4.2 Automatic Transfer Logic
The device automatically selects the phase with normal voltage to supply power to the load. If a priority phase is set (e.g., L1), the product will first attempt to use L1. If L1 is not normal, it will automatically switch to the next available normal phase. If the priority phase is set to AUTO, the product will automatically select any voltage-normal phase as the input.
The video below demonstrates the automatic transfer functionality:
Video: Demonstration of the GEYA GPS8-18 automatic transfer switch in action, showing power source switching and load operation.
4.3 Manual On/Off
Under normal operation, the load can be switched on or off manually by pressing the power button (✅) for 0.5 seconds.
5. Parameter Settings
The GPS8-18 allows for customization of various operational parameters to suit specific power management needs. To enter the setting mode, press and hold the 'M' key for 3 seconds. Use the Up (▲) and Down (▼) arrow keys to adjust values. After modifying, press and hold the 'M' key for 3 seconds to save the settings. If no key is operated for 60 seconds, the device will automatically exit the setting mode.

Image: Flowchart detailing the parameter setting process, including over/under voltage, overcurrent, and various delay settings.
5.1 Adjustable Parameters:
| Parameter | Range | Step Value | Factory Settings |
|---|---|---|---|
| Over voltage value (oU) | OFF, 230V-300V | 1V | 275V |
| Over voltage recovery value (oUr) | 225V-295V | 1V | 265V |
| Under voltage value (UU) | 140V-210V, OFF | 1V | 175V |
| Under voltage recovery value (UUr) | 145V-215V | 1V | 180V |
| Voltage fault action time (Ut) | 0.1s-10s | 0.1s | 0.5s |
| Over current value (oC) | OFF, 1A-63A, 80A | 0.1A | 60A, 80A |
| Over current action delay (ocT) | 2s-600s | 1s | 5s |
| Power on delay time (tP) | 2s-600s | 1s | 5s |
| Reset time (tr) | 2s-900s | 1s | 10s |
| Switching time (tS) | 0s-900s | 0s | |
| Fault reset (rSt) | ON-OFF | ON | |
| Priority phase (PrP) | L1-L2-L3-AUTO | L1 |
6. Maintenance
6.1 Disconnecting for Maintenance
As this product does not have an isolation function, it is crucial to disconnect the superior MCB (Miniature Circuit Breaker) before performing any maintenance or inspection on the device or connected circuits.
6.2 Disposal of Electrical Waste
All electrical waste should be disposed of in compliance with current WEEE (Waste Electrical and Electronic Equipment) regulations. Do not dispose of this product with general household waste.
7. Troubleshooting
7.1 Fault Indicators
The device features an FLT (Fault) LED indicator. When this LED is on, it signifies a fault condition. Refer to the parameter settings and functional diagrams for specific fault types and their corresponding actions.
- LED: L1/L2/L3: Indicates if a phase is not selected or has been selected.
- LED: FLT: Indicates voltage is normal, L1, L2, L3 voltage are all faulty, or contact disconnection fault.
7.2 Common Issues and Solutions
- Load not switching: Check if the input power sources are within the set voltage and current parameters. Verify the priority phase settings.
- FLT LED is ON: Identify the specific fault indicated by the LED status. Check for over/under voltage, overcurrent, or contact disconnection. Adjust parameters or inspect wiring as needed.
- Device not responding to button presses: Ensure the device is powered correctly. If in setting mode, ensure changes are saved by long-pressing 'M'.
8. Specifications
| Parameter | Specification |
|---|---|
| Function | Automatic transfer switch |
| Rated supply voltage | AC220V (L1, L2, L3-N) |
| Rated supply frequency | 45~65Hz |
| Operation voltage range | 80V~400V (L1, L2, L3-N) |
| Rated operational current | 63A, 80A (AC1) |
| Burden | AC max. 3VA |
| Electrical life | 1x104 |
| Mechanical life | 1x106 |
| Operating temperature | -20°C ~ +60°C |
| Storage temperature | -35°C ~ +75°C |
| Mounting/DIN rail | Din rail EN/IEC 60715 |
| Protection degree | IP40 for front panel/IP20 terminals |
| Operating position | Any |
| Overvoltage category | III |
| Pollution degree | 2 |
| Dimensions | 82 x 72 x 68 mm |
| Weight | 320g |
8.1 Dimensions

Image: Dimensions of the GPS8-18 device (82mm x 72mm x 68mm).
9. User Tips
- The device performs reliably and works as described for automatic power transfer and protection.
- This model does not include Wi-Fi or Smart Life (Tuya) compatibility for remote control. If smart home integration is required, consider external smart relays or contact GEYA for alternative models.
10. Warranty and Support
For warranty information, technical support, or further inquiries, please refer to the official GEYA documentation or contact GEYA customer service directly. A detailed user manual in PDF format is available for download from the seller's website: User Manual (PDF).