1. Introduction
The BRIGHTWIN BRT 420SG-D2 is a versatile current signal generator and display meter designed for industrial control applications. It supports both manual operation and RS485 remote control, making it suitable for various uses such as valve control, inverter control, and constant pressure control systems.
Main Features:
- Current signal generator and display meter all in one.
- Standard 35mm DIN Rail-mounting shell for easy installation.
- Supports 24VDC power supply.
- Manual operation and output accuracy calibration.
- Adjustable 6-level LED display luminance.
- Equipped with MODBUS RS485 communication for remote control.
- Default 4-20mA output, adjustable to 0-20mA, 0-22mA, or 0-24mA via button.
2. Safety Warnings
- This signal generator requires a high voltage power supply. Always remove power supply first before performing any wiring connections.
- DO NOT connect input/output wires without removing power supply to avoid high voltage injury.
- Always operate the device according to this user manual. Do not exceed the rated limited values, as this may cause permanent damage to the device.
3. Product Overview and Dimensions
The BRT 420SG-D2 is housed in a compact DIN rail-mountable enclosure, designed for easy integration into control panels.
4. Technical Specifications
| Parameter | Specification |
|---|---|
| Power Supply | 24VDC (±10%) |
| Power Consumption | <2W |
| Current Signal Output | Default 4-20mA (adjustable to 0-20mA, Max 0-22mA) |
| Output Error Grade | <0.05mA, load sampling resistance <500 Ω |
| Output Adjusting Accuracy | 0.1mA |
| Input Feedback Accuracy | <0.05mA, internal sampling resistance 10 Ω |
| Display Mode | Actual current value (4.0-20.0mA), 0.0-100 (%), 0.0-50.0(Hz) |
| RS485 Communication | Standard MODBUS-RTU |
| External Shell Size (L x W x H) | 87.50 x 36.50 x 58.70mm |
| Operating Temperature | 0-40°C, <80% R.H. |
| Battery Included | No |
| Certification | CE, RoHS |
5. Installation and Wiring
Proper wiring is crucial for the safe and correct operation of the signal generator. Refer to the diagrams below for terminal descriptions and wiring configurations.
Wiring Terminals Description:
- GND (Signal output GND-): Signal output negative.
- OUT (Signal output +): Signal output positive.
- VCC (24VDC power supply +): Positive terminal for 24VDC power supply.
- GND (Power supply GND-): Negative terminal for power supply, common ground with signal input GND.
- ACL (220VAC power supply L): Live wire for optional 220VAC power supply.
- ACN (220VAC power supply N): Neutral wire for optional 220VAC power supply.
- B-/A+ (RS485 communication B-/A+): Terminals for RS485 communication.
6. Operation Instructions
6.1. Knob Functions Definition
- [Confirm/OK]: Press the knob.
- [+/Add]: Rotate the knob in a clockwise direction to increase values.
- [-/Subtract]: Rotate the knob in a counter-clockwise direction to decrease values.
6.2. Parameters Setting
- In normal operating status, long press the knob for 2 seconds to enter parameter setting mode. The LED screen will display "F01".
- Rotate the knob to navigate through referential parameter setting codes from F01 to Fnd.
- Press down the knob to enter the parameter setting status for the selected code. Then, rotate the knob to change the parameter value to your desired setting. Refer to Table 1.1 for parameter definitions.
- After selecting the value, press the knob again to save the parameter setting.
6.3. Referential Code Definition (Table 1.1)
| Referential Code | Parameters Setting | Value Description | Default Setting |
|---|---|---|---|
| F01 | Fine or rough adjustment | 0: Rough adjustment (F02 changes add/sub value times.) 1: Fine adjustment (F03 changes add/sub value times.) | 1 |
| F02 | Add or subtract value in rough adjustment per pulse | 1 to 50: output value changing step per pulse. No decimal points. Rotating knob one turn (360 degrees) equals 20 pulses. Can be ten times 10 x (1 to 50). | 1 |
| F03 | Add or subtract value in fine adjustment per pulse | 1 to 50: output value changing step per pulse. No decimal points. Rotating knob one turn (360 degrees) equals 20 pulses. | 1 |
| F04 | Pressing knob functions | 0: Manually save output value (fixed startup value) 1: Quickly switch between fine/coarse adjust (saves automatically in 3s) 2: Output ON/OFF (saves automatically in 3s) 3: Quickly reset to min. value (saves automatically in 3s) | 1 |
| F05 | Output range | 0: 0-20mA, 1: 4-20mA, 2: 0-22mA, 3: 0-24mA, -1: User-defined output | 0 |
| F06 | Customized min. output | 0-24.0mA | 0 |
| F07 | Customized max. output | 0-24.0mA | 10.0 |
| F08 | Display mode | 0: Actual current value display 1: 0-100.0 percentage display 2: 0-50Hz display 3: 0-90° display 4: 0-130 display 5: 0-150 display 6: 0-250 display 7: 0-400 display 8: 0-600 display -1: User-defined output | 0 |
| F09 | Customized min. display value | -199 to 999, decimal point setting in F11 | 0 |
| F10 | Customized max. display value | -199 to 999, decimal point setting in F11 | 200 |
| F11 | Decimal point setting | 0-3 (0/1: None, 2: 99.9, 3: 9.99) | 2 |
| F12 | Slave Device ID | 1-127 | 1 |
| F13 | Baud rate value | 0: 2400, 1: 4800, 2: 9600, 3: 19200, 4: 38400, 5: 57600 | 2 |
| F14 | Check-sum | 0: 8-N-1, 1: 8-N-2, 2: 8-ODD-1, 3: 8-EVEN-1 | 2 |
| F15 | LED luminance adjustment | 0 to 7 (7 max. luminance level) | 1 |
| F16 | 4mA output calibration | -999 to +999. Not recommended if output accuracy is normal. For professionals only. | -- |
| F17 | 12mA output calibration | For professionals only. | -- |
| F18 | 20mA output calibration | For professionals only. | -- |
6.4. Fine/Coarse Adjustment Setting Examples
The encoder knob rotates 20 grids per turn. F02 and F03 define the step size for rough and fine adjustments.
| Example Settings | F01 | F02 | F03 | Explanation |
|---|---|---|---|---|
| 0-20mA display 0-20.0, knob adjustment 1 turn | 0 | X | 1 | Set fine tuning, with a change of 1mA per grid |
| 0-20mA display 0-20.0, knob adjustment 5 turns | 1 | X | 2 | Set fine-tuning 2, one grid change of 0.2mA |
| 4-20mA display 0-100, knob adjustment 1 turn | 1 | X | 5 | Set fine adjustment 5, with a change of 0.5mA in one grid |
6.5. Example of Setting Output Range and Display Scale
The following table provides examples for configuring output range and display scale using parameters F05 to F11. 'X' indicates that the parameter does not need to be set or its setting does not affect the outcome for that specific example.
| Example Settings | F05 | F06 | F07 | F08 | F09 | F10 | F11 |
|---|---|---|---|---|---|---|---|
| 0-20mA display 0-20.0 (current value) | 0 | X | X | 0 | X | X | X |
| 0-20mA display 0-100 (% percentage) | 0 | X | X | 1 | X | X | X |
| 4-20mA display 0-100 (% percentage) | 1 | X | X | 1 | X | X | X |
| 4-20mA display 0-50 (HZ) | 1 | X | X | 2 | X | X | X |
| 4-20mA display 0-90 (° angle) | 1 | X | X | 3 | X | X | X |
| 4-20mA display 0-500 (speed) | 1 | X | X | -1 | 0 | 500 | 0 |
| 4-20mA display 0-1.60 (MPa pressure) | 1 | X | X | -1 | 0 | 160 | 3 |
| 4-20mA display -40 to 80 (°C temperature) | 1 | X | X | -1 | -40 | 80 | 0 |
| 3-21mA display 3-21.0 | -1 | 3.0 | 21.0 | 0 | X | X | X |
| 0.5-21.5mA display -20 to 200 | -1 | 0.5 | 10.5 | -1 | -20 | 200 | 0 |
Note: Due to the inability to display 1000 with 3 digital tubes, A00 is used instead of displaying it.
7. MODBUS RS485 Communication
The BRT 420SG-D2 supports standard MODBUS RTU protocol for remote control and data acquisition.
- The signal generator's meter address is 1-127 (factory default setting is 1).
- Baud rates supported: 2400-115200 (factory default setting is 9600).
- Checksum: None.
- 120Ω terminal resistance is NOT embedded in RS485 ports. For long-distance transmission, users need to add external terminal resistance for stable data transmission.
- It is recommended to use high-quality shielded twisted pair cable to enhance data communication anti-interference capability.
7.1. MODBUS Command Format
| Field | Size | Description |
|---|---|---|
| RS485 slave address | 1 byte | |
| Functional code | 1 byte | 03 or 06 |
| Data | N byte | |
| CRC check | 2 byte | Standard CRC16, initial value 0xFFFF |
7.2. 03 Inquire Multiple Register Command Example
Example: Inquire 3 registers starting with address 0.
- Send: 01 03 00 00 00 06 C5 CB
- Return: 01 03 0C 00 00 00 00 00 00 00 21 75
7.3. 06 Set a Single Register Command Example
Example: Set register 1 value to 100, return command directly.
- Send: 01 06 00 01 00 64 D9 E1
- Return: 01 06 00 01 00 64 D9 E1
7.4. Register Table
| Register Address | Description | Read/Write | Notes |
|---|---|---|---|
| 0 | None | -- | Some PLC data address starts from 1 |
| 1 | Current value display | R/W | No decimal point, E.g: 10=0.1mA, 1000=20.00mA |
| 3 | None | -- |
Note: Receiving one packet of data successfully will cause the communication LED indicator to flash once.
8. Calibration
8.1. 4mA Accuracy Calibration (F16)
- First, adjust the BRT 420SG-D2 signal generator to 4mA display mode.
- Connect a precision mV measuring multimeter to the BRT 420SG-D2 signal generator's output (+ and -) terminals.
- Adjust the BRT 420SG-D2 signal generator knob until the precision multimeter accurately displays 4.0mA.
- Finally, press down the BRT 420SG-D2 signal generator knob to save the parameter setting.
Important: When performing F16, F17, or F18 output precision calibration, a high-precision multimeter is required, connected to the signal generator's output terminals. For F16, F17, F18, adjust the output to make the signal generator display 4mA, 12mA, and 20mA respectively, then proceed with calibration.
9. Maintenance
- Keep the device clean and free from dust and moisture.
- Avoid exposing the device to extreme temperatures or direct sunlight.
- Do not use harsh chemicals or abrasive cleaners on the device. Use a soft, dry cloth for cleaning.
- Ensure all wiring connections are secure and free from corrosion.
10. Troubleshooting
- No Display/No Power: Check the 24VDC power supply connection and ensure it is within the specified voltage range (24VDC ±10%). Verify wiring according to the installation section.
- Incorrect Output: Verify the parameter settings (F01-F11) are correct for your desired output range and display scale. Perform calibration (F16, F17, F18) if necessary, using a precision multimeter.
- Unstable Output: Check for loose wiring connections. Ensure the load sampling resistance is within the specified range (<500 Ω).
- RS485 Communication Issues: Verify the slave device ID (F12) and baud rate (F13) settings. Ensure high-quality shielded twisted pair cable is used. For long-distance communication, add external 120Ω terminal resistance.
- Device Damage: If the device shows signs of physical damage or malfunction not covered by basic troubleshooting, discontinue use and contact technical support.
11. User Tips
- For critical applications, always double-check the output with a calibrated multimeter after setting parameters.
- When integrating with PLC systems, ensure the MODBUS register addresses align with your PLC's configuration, noting that some PLC data addresses start from 1.
- Utilize the adjustable LED luminance (F15) to optimize visibility in different lighting conditions.
12. Support and Resources
For further technical assistance or inquiries, please contact:
- Technical Support Email: info@brightwinelectronics.com
- Official Website: www.brightwinelectronics.com
- Additional Resources: A detailed user manual in PDF format is available for download.
The specifications are subject to change without notice.