PowMr POW-LIO48100-3.5U

Contents

PowMr 51.2V 100Ah LiFePO4 Battery User Manual

Model: POW-LIO48100-3.5U

1. Overview

This manual provides essential information, operating instructions, and maintenance guidelines for the PowMr POW-LIO48100-3.5U low-voltage residential energy storage battery series. This lithium battery system is designed for compatibility with various inverter brands and is intended for professional technical personnel and end-users.

The POW-LIO48100-3.5U integrates PowMr's high-capacity and high-safety lithium iron phosphate battery cells. Its rack-mounted structure allows for vertical stacking, optimizing space. A high-precision Battery Management System (BMS) is integrated, offering multiple protection functions, continuous monitoring of voltage and temperature, intelligent temperature control, and cell balancing to enhance system efficiency and extend battery life.

The module features a cold-rolled sheet metal outer shell with a shock-resistant design, ensuring high safety and reliability. It also incorporates high stability and strong anti-interference design for safe and reliable operation.

Key Advantages:

  • Powerful Charging Capability: Max charging current of 100A for fast charging.
  • Sustained Discharge Support: Continuous discharge current of 100A for high-load demands.
  • Parallel Expansion Capability: Supports up to 16 batteries in parallel, achieving a maximum storage capacity of 81.92kWh.
  • Multiple Communication Interfaces: Equipped with RS232, RS485, CAN, and dry contact communication ports.
  • Comprehensive Protocol Integration: Compatible with various market-leading BMS communication protocols for seamless inverter integration.
  • Remote Monitoring and Management: Supports upper computer applications for remote access and configuration.
  • High-quality Battery Cells: Built with A+ grade cells for high performance and stability.
  • Built-in Balancing Module: Intelligent balancing module ensures up to 6000 cycles (0.2C, 25°C, 80% DOD).
  • Safe Power Design: Low-voltage switch design for safe power-on and reduced standby losses.
  • Scalable Rack-Mount Design: Modular stackable structure for flexible system expansion.
  • Space-Saving Installation: Vertical stacking maximizes space utilization.
  • Easy Deployment & Maintenance: Standardized rack-mount modules for quick installation and replacement.
  • Enhanced Structural Stability: Robust frame design for mechanical strength and vibration resistance.
  • Flexible Application Scenarios: Supports residential, commercial, and industrial energy storage needs.
Diagram illustrating the long-life, space-saving modular design of the PowMr battery.
Long-Life, Space-Saving Modular Design: The battery delivers over 6,000 cycles of reliable performance, featuring a vertical, rack-mount, stackable structure that saves space, simplifies installation and maintenance, and allows easy capacity expansion to match evolving energy needs.
Diagram showing smart balancing technology for extended battery life, comparing before and after balancing.
Safe, Efficient Operation with Smart Cell Balancing: Features a low-voltage soft-start design to ensure safe, stable power-on and reduced standby losses, combined with intelligent cell balancing that optimizes each lithium cell for longer life, higher efficiency, and more reliable performance.
Diagram illustrating ultra-long cycle life and stable output compared to lead-acid and ternary lithium batteries.
Ultra-Long Cycle Life, Consistent and Stable Output: Built with lithium iron phosphate (LiFePO4) core materials, the battery delivers over 6,000 cycles—more than three times the lifespan of traditional batteries. It maintains stable performance for daily energy storage or frequent charge-discharge applications.
Diagram showing 100A powerful current output and parallel connection for high-power loads.
High-Current Performance with Massive Scalability: Supports 100A fast charging and 100A continuous discharge for demanding loads, with up to 16 batteries in parallel delivering 81.92kWh of expandable capacity—ideal for stable, scalable residential, commercial, and industrial energy systems.
Diagram illustrating the PowMr BMS with comprehensive protection features including overvoltage, undervoltage, overcurrent, short circuit, and overtemperature.
A+ Grade Cells with Intelligent BMS Protection: Built with A+ grade cells for high consistency and long-term reliability, combined with an advanced Battery Management System (BMS) that continuously monitors, balances, and protects the battery. This ensures enhanced safety, stable performance, and an extended service life for dependable energy storage applications.

2. Safety Instructions

To ensure user safety, carefully read and adhere to all safety instructions and warnings provided in this manual.

2.1 Labeling Explanation

Symbols used in this manual:

  • ⚠ CAUTION: Signifies a low-level potential hazard. Failure to avoid may result in minor or moderate injury to personnel.
  • ⚡ DANGER: Indicates the presence of high voltage inside the battery module. Touching may lead to electric shock hazards.
  • ⏚ GROUND: This is the ground protection port (PE). It should be securely grounded to ensure the safety of operating personnel.

2.2 Operating Precautions

  • Do not use the battery in extreme hot environments (e.g., direct sunlight, hot car interiors).
  • In case of battery leakage or electrolyte entering eyes, immediately rinse with clean water and seek medical assistance.
  • Avoid submerging the battery in water or getting it wet.
  • Prohibit charging the battery near open flames or under extremely hot conditions.
  • Use a dedicated charger.
  • Do not reverse positive and negative terminals.
  • Do not directly connect the battery to wall outlets or car cigarette lighters.
  • Do not throw the battery into fire or heat it.
  • Prohibit short-circuiting positive and negative terminals with wires or other metal objects.
  • Prohibit puncturing the battery casing with nails or other sharp objects.
  • Avoid impacts, throwing, or subjecting the battery to mechanical vibrations.
  • Prohibit direct welding to the battery terminals.
  • Prohibit disassembling the battery in any way.
  • Prohibit placing the battery in microwaves or pressure containers.
  • Prohibit combining the battery with disposable batteries or batteries of different capacities/types.
  • If the battery emits an odor, heats up, deforms, changes color, or exhibits any other abnormal phenomena, discontinue use immediately.

3. Setup and Installation

3.1 Installation Tools

Before installation, prepare the following tools:

CategoryTools
General ToolsMultimeter, Protective gloves, Insulated safety shoes, Protective clothing, Safety goggles, Antistatic wrist strap
Installation ToolsElectric screwdriver, Socket wrench, Wire stripper, Phillips screwdriver (M4/M6), Electric drill, Hammer

3.2 Component Overview

Familiarize yourself with the battery components and accessories:

Labeled diagram of the battery components including power switch, terminals, circuit breaker, communication ports, handle, and stacking bracket.
Battery Component Diagram: 1. Power Switch, 2. Positive Terminal, 3. Negative Terminal, 4. Circuit Breaker, 5. Communication Port Panel, 6. Handle, 7. Stacking Bracket.

3.3 Battery Port Panel Details

No.ItemFunctionNotes
1Power SwitchUsed to start or shut down the battery
2Positive Terminal (+,M6)Battery Positive Output
3Negative Terminal (-,M6)Battery Negative Output
4Circuit BreakerOver Current ProtectionIn: 125A
5Reset Button (RESET)Battery ResetBriefly tap and release within 1-3 seconds.
6Operation Light (RUN)Battery Operation Indicator LightIlluminates once battery is operating normally.
7Alarm Light (ALM)Battery Alarm Indicator LightFor detailed information, refer to Section 8.2.
8Capacity Light (SOC)Battery Capacity Indicator LightFor detailed information, refer to Section 8.2.
9Dry ContactDry Contact CommunicationPIN1 to PIN2: Normally open, closed during fault protection; PIN3 to PIN4: Normally open, closed during low battery alarm.
10RS485A485 Communication InterfaceCommunication with inverter via RS485
11CANCAN Communication InterfaceCommunication with inverter via CAN
12RS232232 Communication InterfaceMonitor batteries and modify parameters; Perform software upgrades.
13RS485BCommunication between batteries.
14Grounding PortBattery Grounding
15DIP Switch (ADS)Define Battery Communication Code

3.4 Installation Notes

  • Installation Space: Ensure sufficient space for proper air circulation around the battery.
  • Installation Environment: Ambient temperature should be between 0°C and 40°C, and relative humidity between 25% and 85%.
  • Cable Specifications: Use cables that meet the maximum current requirements of equipment operation.
  • Project Layout: Ensure a reasonable layout of power equipment and batteries.
  • Wiring Layout: Ensure reasonable and orderly wiring, considering moisture-proof and corrosion prevention.
  • Personnel: At least two people should be present for installation.
  • Safety: Ensure the installation site is safe before beginning.

3.5 Battery Placement

  1. Unboxing: Upon receiving, open the wooden box and verify all accessories are complete. Contact the dealer if anything is missing.
  2. Handling: The battery pack is heavy. Use a forklift or multiple people to remove it from the wooden box.
  3. Location: Place the battery in a suitable installation location, ensuring the surface is flat, stable, and capable of bearing the battery pack's weight.
  4. Attaching Brackets: Attach the four stacking brackets to the four corners of the battery. Align the holes and tighten the screws to secure the brackets.

3.6 Battery Wiring

The installation, operation, and maintenance of the LiFePO4 Battery Energy Storage System should only be carried out by trained and qualified professionals. Ensure the power system and battery pack are turned off before installation. All power cables must have appropriate insulation.

Installation Video: This video demonstrates the process of attaching brackets, stacking batteries, connecting parallel power cables, setting DIP switches, and connecting communication cables for a multi-battery setup.

Single Battery Application:

  1. Inverter Connection: Use a power cable to connect the battery to the inverter. Pay attention to polarity.
  2. Inverter BMS Communication: Connect the RS485A or CAN port of the battery to the communication port on the inverter using a communication cable.
  3. Grounding: Connect the battery's grounding terminal to the system ground using a suitable ground cable.
  4. DIP Switch Setting: Set the battery ADS DIP switch to position 1. Refer to the DIP switch configuration rules below.
Diagram of a single battery connected to a hybrid solar inverter, showing positive, negative, BMS communication, and grounding cables.
Single Battery Wiring Diagram: Illustrates the connections for a single PowMr battery to a hybrid solar inverter, including power, communication, and grounding cables.

Multiple Batteries in Parallel (Example with Four Batteries):

If connecting more than 4 batteries in parallel, a busbar is recommended as the common connection point.

  1. Voltage Check: Manually press the low-voltage ON/OFF switch on each battery and use a multimeter to check if all battery voltages are consistent. If consistent, power off the batteries before proceeding.
  2. Parallel Communication Cable Connection: Use the battery parallel communication cable to connect each battery through the RS485B ports. The battery connected to the inverter is the first battery. Connect the cable from the Output port of the first battery to the Input port of the second battery, and so on.
  3. Grounding: Connect all batteries to ground using a grounding wire. The grounding terminal is on the bottom wiring panel of each battery.
  4. Power Cable Connection: Use positive and negative power cables to connect the batteries in parallel, then connect the entire battery bank to the inverter. Ensure correct polarity.
  5. Inverter BMS Communication: Use the BMS communication cable to connect the battery master (first unit) to the inverter through the RS485A or CAN port.
  6. DIP Switch Configuration: Define the master-slave relationship using the DIP switches. The master is set to 1, and slaves are 2 to 15. The host DIP switch must be set to 1 before powering on. Define DIP switches for other batteries sequentially from 2 to 15, avoiding duplicates.
Multiple PowMr LiFePO4 battery units stacked in a rack-mount setup.
Stacked Battery Units: Multiple PowMr LiFePO4 battery units can be stacked for space efficiency.
Front view of a single PowMr LiFePO4 battery unit, showing terminals and communication ports.
Front View of Battery Unit: Details of the front panel with terminals, switches, and communication interfaces.
Side view of a single PowMr LiFePO4 battery unit.
Side View of Battery Unit: Illustrates the side profile and handles for easy installation.

DIP Switch Definitions (ADS)

The DIP switches are used to assign a communication code to each battery in a parallel setup, defining master and slave configurations. The master unit is typically set to '1'.

Address#1#2#3#4Illustration
0OFFOFFOFFOFFDIP Switch setting for Address 0 (all OFF)
1ONOFFOFFOFFDIP Switch setting for Address 1 (1 ON, others OFF)
2OFFONOFFOFFDIP Switch setting for Address 2 (2 ON, others OFF)
3ONONOFFOFFDIP Switch setting for Address 3 (1,2 ON, others OFF)
..................
15ONONONONDIP Switch setting for Address 15 (all ON)

Note: The provided image for DIP switch settings is generic. Please refer to the full PDF manual for specific illustrations for each address.

4. Operation

4.1 Power-On Sequence

After completing all connections between the inverter, battery, and mains power:

  1. Initiate the battery by using the switch on the right side of the battery.
  2. Start the inverter.
  3. Verify the communication status of the inverter. Successful data transmission indicates proper communication.

4.2 SOC Indicator & Status Indicator Guides

The battery features LED indicators for operation (RUN), alarm (ALM), and State of Charge (SOC).

Battery LED Indicators:

The SOC indicator consists of 8 LEDs (L1-L8). The ALM indicator is a single LED. The RUN indicator is a single LED.

Battery Charging Level Indication (SOC LEDs L1-L6):

SOC(%)L6L5L4L3L2L1
0-16.6%OFFOFFOFFOFFOFFFlash2
16.6-33.2%OFFOFFOFFOFFFlash2light
33.2-49.8%OFFOFFOFFFlash2lightlight
49.8-66.4%OFFOFFFlash2lightlightlight
66.4-83%OFFFlash2lightlightlightlight
83-100%Flash2lightlightlightlightlight
RUN LEDlight

Battery Discharging Level Indication (SOC LEDs L1-L6):

SOC(%)L6L5L4L3L2L1
0-16.6%OFFOFFOFFOFFOFFlight
16.6-33.2%OFFOFFOFFOFFlightlight
33.2-49.8%OFFOFFOFFlightlightlight
49.8-66.4%OFFOFFlightlightlightlight
66.4-83%OFFlightlightlightlightlight
83-100%lightlightlightlightlightlight
RUN LEDFlash (flash3)

4.3 Inverter Matching Information

The battery supports various inverter communication protocols. The default RS485 protocol is Pylontech RS485 (V3.5), and the default CAN protocol is Pylontech CAN. If compatibility with other inverters is needed, the protocol can be changed via RS232 communication using the upper computer software (Pbms Tools).

Inverter BrandCommunication MethodInverter Communication PinBattery Communication PinRemarks
PowMrRS485PIN7:RS485A, PIN8:RS485BPIN2/7:RS485A, PIN1/8:RS485BDefault Battery Protocol Matching
ECGSOLAXRS485PIN7:RS485A, PIN8:RS485BPIN2/7:RS485A, PIN1/8:RS485BDefault Battery Protocol Matching
SMACANPIN4:CANH, PIN5:CANLPIN4:CANH, PIN5:CANLBattery Protocol Change
VICTRONCANPIN7:CANH, PIN8:CANLPIN4:CANH, PIN5:CANL1. Battery Protocol Change
2. Customized Network Cable
GrowattRS485PIN7:RS485A, PIN8:RS485BPIN2/7:RS485A, PIN1/8:RS485B1. Default Battery Protocol Matching
2. Inverter Protocol Setting Option 2
GOODWECANPIN4:CANH, PIN5:CANLPIN4:CANH, PIN5:CANLDefault Battery Protocol Matching
PYLONTECHRS485PIN7:RS485A, PIN8:RS485BPIN2/7:RS485A, PIN1/8:RS485BDefault Battery Protocol Matching
LUXPOWERRS485PIN2:RS485A, PIN1:RS485BPIN2/7:RS485A, PIN1/8:RS485B1. Battery Protocol Change
2. Customized Network Cable
Voltronic PowerRS485PIN5:RS485A, PIN3:RS485BPIN2/7:RS485A, PIN1/8:RS485B1. Default Battery Protocol Matching
2. Customized Network Cable
SOFARCANPIN1:CANH, PIN2:CANLPIN4:CANH, PIN5:CANL1. Battery Protocol Change
2. Customized Network Cable
SRNERS485PIN7:RS485A, PIN8:RS485BPIN2/7:RS485A, PIN1/8:RS485B1. Default Battery Protocol Matching
2. Inverter Protocol Setting PYL
DeyeRS485, CANPIN4:CANH, PIN5:CANLPIN4:CANH, PIN5:CANLDefault Battery Protocol Matching
MEGAREVOCANPIN4:CANH, PIN5:CANLPIN4:CANH, PIN5:CANLDefault Battery Protocol Matching
MUSTCANPIN6:CANH, PIN5:CANLPIN4:CANH, PIN5:CANL1. Battery Protocol Change
2. Customized Network Cable

5. Maintenance and Care

5.1 Precautions Before Using Lithium Batteries

  • Always read and keep this manual carefully.
  • Pay attention to all warning labels on the battery; do not tear or damage them.
  • Before use, confirm that the battery model matches the inverter being used. Mismatched components can cause damage.
  • Inspect the lithium battery for intact appearance, without obvious signs of damage, leakage, heating, immersion in water, or smoking.
  • If the battery emits odors, heats up, deforms, or shows any other abnormalities, stop using it immediately, move away from the battery, and contact the after-sales department.

WARNING!!

  • The battery is not a user-serviceable component. For any abnormalities, contact the after-sales department.
  • Disassembling the battery without authorization will void the warranty and may lead to heating, smoking, ignition, or explosion.

5.2 Charging Environment

  • Charge the battery in an environment with a temperature of 0°C to 60°C, ensuring no flammable materials are nearby and there is good ventilation.
  • During the initial stage of charging, rapid capacity increase is normal; the charging process slows down later as a safety measure.
  • In winter, if outdoor temperatures are below 0°C, the battery may stop charging. Place the battery in a suitable temperature environment for effective charging.

5.3 Storage Environment

  • For long-term storage (unused for more than 3 months), store batteries in a dry and cool environment (23±2°C, 45%-75% humidity).
  • For extended periods of disuse, recharge batteries every 3 months to maintain voltage.
  • Regular maintenance charging is crucial; complete discharge can lead to irreversible damage.
  • Safe Storage Self-Discharge Protection Mode:
    • When connected to a device, the safety period is a maximum of 3 months. Beyond this, battery feedback may occur and become irreparable.
    • When stored separately with capacity not less than 80%, the safety period is a maximum of 6 months. Beyond this, battery feedback may occur and become irreparable.
  • Avoid storing the battery in places with a risk of falling, which can cause internal damage, leakage, heating, smoking, ignition, or explosion.
  • Do not use cleaning solvents on the battery.
  • Prohibit storage and use in areas with strong static electricity and magnetic fields, as this may damage safety protection devices.

WARNING!!

  • Improper use leading to battery undervoltage and feedback is not covered under the warranty.

6. Troubleshooting

No.Fault SymptomsCause AnalysisSolution
1No DC OutputBattery Voltage Too Low, Protection ActivatedStartup after Charging Activation
2Short Power Supply TimeInsufficient Battery Capacity or Failure to Reach Full ChargeConfirm Maintenance or Replace Battery
3Battery Cannot Reach Full ChargeDC Voltage Output from Power System Lower than Minimum Charging VoltageAdjust Device's DC Output Voltage to Suitable Charging Voltage for Battery
4Unstable Battery Output Voltage with Significant FluctuationsInterference with Management System OperationRestart the System
5Temperature Monitoring Too LowDamage to Temperature-Sensing Crystal HeadReplace the Collection Line with a Temperature-Sensing Crystal Head
6Unable to ChargeSingle Cell Protection Activated upon Full Battery ChargeDischarge Protection Removal
7MOS temperature abnormalMOS tube damagedReplace BMS
8Discharge overcurrent protectionInverter power exceeds limitMatch the number of batteries according to the inverter power value

7. Technical Specifications

ParameterValue
Battery ModelPOW-LIO48100-3.5U
System Voltage51.2V
Rated Capacity100Ah
Nominal Energy5.12kWh
Constant Voltage Charging Voltage57.6V
Float Charging Voltage56V
Max. Discharge Cutoff Voltage43.2V
Recommended Discharge Cutoff Voltage48V
Max Charging Current (Icm)100A
Max Discharging Current100A
Max. No. of Parallel Connections16
Communication InterfaceRS232/RS485/CAN/Dry Contact
Cycle Life≥6000 Times @80%DOD, 25°C
Operating TempCharging: 0~55°C; Discharging: -10°C~60°C
Storage Temperature-10°C~30°C
Nominal Operation Altitude< 2000m
Nominal Operation Humidity<90%RH
IP GradeIP21
Recommended Operation EnvironmentIndoor
Dimensions (LxWxH)480×440×155mm
Net Weight~43kg

Note: If the battery does not have communication, it is recommended to set the inverter parameters according to the recommended values.

8. User Tips

  • Always ensure proper ventilation around the battery, especially during charging and discharging, to prevent overheating.
  • When connecting multiple batteries in parallel, double-check all cable connections and DIP switch settings before powering on the system.
  • For optimal performance and longevity, avoid consistently discharging the battery below 10% capacity.
  • If using the upper computer software (Pbms Tools) to change inverter protocols, ensure you follow the instructions carefully to avoid communication issues.
  • Regularly inspect the battery for any physical damage or unusual odors. Address any issues promptly by contacting support.

9. Warranty and Support

For technical support, warranty claims, or any inquiries regarding your PowMr LiFePO4 Battery, please contact:

SHENZHEN HEHEJIN INDUSTRIAL CO.,LTD
Tel/Fax: +86 755-28219903
Email: support@powmr.com
Web: www.powmr.com
Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China