BRIGHTWIN BRT 510SG-D2

Contents

BRIGHTWIN BRT 510SG-D2 DIN Rail Adjustable Voltage Signal Generator

User Instruction Manual

1. Introduction

The BRIGHTWIN BRT 510SG-D2 is a DIN Rail-mounted adjustable voltage signal generator designed for industrial control applications. It provides a stable 0-10V (or other configurable ranges) output signal and features MODBUS RS485 communication for integration into control systems. This manual provides detailed instructions for the safe and effective use of the device.

BRT 510SG-D2 Signal Generator Front View

Figure 1: BRT 510SG-D2 Signal Generator Front View

2. Setup

2.1 Unpacking

Carefully remove the signal generator from its packaging. Inspect the device for any signs of damage during transit. If any damage is found, do not proceed with installation and contact your supplier.

2.2 Mounting

The BRT 510SG-D2 is designed for standard 35mm DIN Rail mounting. Ensure the mounting location is free from excessive vibration, moisture, and extreme temperatures. Allow adequate space around the device for ventilation and wiring.

BRT 510SG-D2 Dimensions Diagram

Figure 2: Device Dimensions (L x W x H: 87.50 x 36.50 x 58.70mm)

2.3 Wiring

Ensure all power is disconnected before performing any wiring. Refer to the wiring diagram below for correct connections. Use appropriate wire gauges for power and signal lines.

BRT 510SG-D2 Wiring Terminals Description and Functions

Figure 3: Wiring Terminals Description and Functions

Terminal Descriptions:

  • GND (Signal Output): Signal output Ground (-).
  • OUT: Signal output (+).
  • VCC: 24VDC Power supply (+).
  • GND (Power Supply): Power supply Ground (-) (Common ground with signal input GND).
  • ACL: 220VAC Power supply L (Optional, None for DC version).
  • ACN: 220VAC Power supply N (Optional, None for DC version).
  • B-: RS485 Communication B- terminal.
  • A+: RS485 Communication A+ terminal.

Power Supply Options:

  • DC24V (15-28VDC): Connect VCC to +24V and Power Supply GND to 0V.
  • AC 220V (Optional): Connect ACL to Live and ACN to Neutral.

3. Operating Instructions

3.1 Knob Functions

  • [Confirm/OK]: Press the knob to confirm selections or enter/exit parameter settings.
  • [+/Add]: Rotate the knob clockwise to increase values.
  • [-/Subtract]: Rotate the knob counter-clockwise to decrease values.

3.2 Parameters Setting

  1. Enter Setting Mode: In normal operating status, long press the knob for 2 seconds. The LED screen will display F01.
  2. Navigate Parameters: Rotate the knob to cycle through referential parameter codes (e.g., from F01 to Fnd).
  3. Adjust Parameter Value: Press the knob to enter the setting status for the displayed parameter. Rotate the knob to change the value. Press the knob again to save the new value and return to the parameter code display.

Key Parameters (Referential Code Definition - Table 1.1):

Referential Code Definition Table 1.1

Figure 4: Referential Code Definition (Table 1.1)

  • F01 (Fine or rough adjustment): 0=Rough adjustment, 1=Fine adjustment.
  • F02 (Add or subtract value in rough adjustment per pulse): Sets the output value change step (1 to 50).
  • F03 (Add or subtract value in fine adjustment per pulse): Sets the output value change step (1 to 50).
  • F04 (Pressing knob functions): 0=Manually save, 1=Quick switch adjustment, 2=Output ON/OFF, 3=Reset to min.
  • F05 (Output range): Configures the output range (e.g., 0=0-10V, 1=0-5V, 2=2-10V, etc.).
  • F08 (Display mode): Sets what is displayed (e.g., 0=Voltage value, 1=Percentage, 2=Frequency).
  • F12 (Slave Device ID): Sets the MODBUS slave address (1-127).
  • F13 (Baud rate value): Sets the MODBUS communication baud rate (e.g., 0=2400, 1=4800, 2=9600, etc.).

3.3 10V Output Accuracy Calibration (F18)

This procedure requires a high-precision multimeter.

  1. Adjust the BRT 510SG-D2 to 10V display mode (e.g., set F05 to 0 for 0-10V range).
  2. Connect a precision mV measuring multimeter to the signal generator's OUT (+) and GND (-) terminals.
  3. Adjust the signal generator knob until the multimeter accurately displays 10.0V.
  4. Press the knob to save the calibration setting.

3.4 MODBUS RS485 Communication

The device supports MODBUS RTU protocol for remote control and monitoring. Refer to the MODBUS Command Format and Register Table for details on communication protocols and register addresses.

MODBUS Command Format and Register Table

Figure 5: MODBUS Command Format and Register Table

Key MODBUS Registers:

  • Register 1: Current value display (Read-only).
  • Register 2: Set output signal range (Read/Write, refer to F01 parameters).
  • Register 3: Display Mode (Read/Write, refer to F02 parameters).
  • Register 4: Device ID (Read/Write, refer to F04 parameters).
  • Register 5: Baud rate (Read/Write, refer to F005 parameters).

4. Maintenance

The BRT 510SG-D2 is designed for reliable operation with minimal maintenance. Keep the device clean and free from dust and debris. Ensure proper ventilation and avoid exposing the unit to corrosive gases or liquids. Periodically check wiring connections for tightness and integrity.

5. Troubleshooting

  • No Display/No Power: Check the 24VDC power supply connections (VCC and Power Supply GND). Ensure the power supply is active and within the specified voltage range.
  • Incorrect Output Voltage: Verify wiring to the load. Check parameter settings (F05 for output range, F02/F03 for adjustment steps). Perform output accuracy calibration if necessary.
  • RS485 Communication Issues: Check RS485 wiring (A+ to A+, B- to B-). Verify Device ID (F12) and Baud Rate (F13) settings match the master device. Ensure proper termination resistors are used if required by the network.
  • Unresponsive Knob: Ensure the device is powered correctly. If the issue persists, power cycle the device.

6. Specifications

ParameterValue
Model NumberBRT 510SG-D2
Power Supply24VDC (±10%)
Power Consumption<2W
Current Signal OutputDefault 0-10V (Configurable: 0-5V, 1-5V, etc.)
Output Adjusting Accuracy0.1V
Error Grade<0.05V
Output Load<20mA
Display ModeActual current value 0.0-5.0/10.0
RS485 CommunicationYes (MODBUS RTU)
External Shell Size (L x W x H)87.50 x 36.50 x 58.70mm
Operating Temperature0-40°C, <80% R.H.
CertificationCE, RoHS

7. User Tips

  • For precise control, utilize the fine adjustment mode (F01=1) and set appropriate step values (F03).
  • When integrating with a PLC or other master device via RS485, ensure the Device ID (F12) and Baud Rate (F13) are correctly configured on both ends.
  • Always perform the 10V output accuracy calibration (F18) if high precision is critical for your application.

8. Warranty and Support

For warranty information, technical support, or service inquiries, please contact your original point of purchase or the manufacturer directly. Keep your purchase records for reference.