1. Product Overview
The VaneAims FXB8L-40 RCBO (Residual Current Circuit Breaker with Overcurrent Protection) is an advanced electrical protection device designed for residential and commercial applications. It integrates the functions of a miniature circuit breaker (MCB) and a residual current device (RCD), providing comprehensive protection against overload, short circuit, and earth leakage faults.
This device is suitable for lighting and distribution circuits in residential buildings, villas, apartments, offices, hospitals, and factory assembly lines. It ensures personal safety by immediately cutting off power in case of leakage and protects electrical circuits from damage due to excessive current.

Figure 1: VaneAims FXB8L-40 RCBO with key protection features
2. Safety Information
- WARNING: Disconnect the power supply before any installation, wiring, or maintenance work to prevent electric shock.
- Installation and maintenance must be carried out by qualified professional electricians.
- Do not use the circuit breaker beyond its rated current to avoid product damage and safety hazards.
- Ensure all connections are secure and tightened properly.
- This device is designed for indoor use in dry environments.
3. Setup and Installation
3.1. Panel Introduction

Figure 2: RCBO Panel Introduction
- Wiring Terminal: Points for connecting incoming and outgoing wires.
- Flame Retardant Housing: High-density, flame-retardant, and insulating material for safety.
- Test Button (T): Used to manually test the leakage protection function.
- Operating Handle: Toggles the circuit breaker ON or OFF.
- Rated Current: Indicates the maximum continuous current the device can safely carry.
- Product Model: FXB8L-40.
- Brand Name: VaneAims.
- Breaking Capacity: Maximum fault current the device can interrupt.
- Tighten Screws: Secure wire connections.
3.2. Installation Instructions
- Mounting: The FXB8L-40 RCBO is designed for 35mm DIN rail installation. It can be easily placed in standard household distribution boxes.
- Space-Saving Design: With a width of only 18mm, this 1P+N RCBO is equivalent in size to a regular 1P circuit breaker, saving valuable installation space.

Figure 3: 35mm DIN Rail Installation
3.3. Wiring Instructions
- Power Disconnection: Ensure the main power supply is completely disconnected before proceeding with any wiring.
- Wire Connection:
- The upper terminal is for incoming wires.
- The lower terminal is for outgoing wires.
- Connect the live wire (L) to the 'L' terminal.
- Connect the neutral wire (N) to the 'N' terminal.
- Secure Connections: Firmly tighten the terminal screws to ensure a reliable electrical connection and prevent loose contacts. The galvanized terminal blocks are rust-resistant and corrosion-resistant for stable conductivity.

Figure 4: Galvanized Terminal Blocks
3.4. Pre-Use Check
After installation and wiring are complete, but before restoring full power:
- Toggle the operating handle up and down several times.
- Confirm that the ON/OFF indicators (red/green) operate correctly.
- Ensure all circuit connections are secure and reliable.
4. Operating Instructions
4.1. Working Status Indication

Figure 5: Visualized Work Status
- ON State (Working Condition): When the operating handle is in the UP position, a RED indicator is visible. The circuit breaker is in working state, and the circuit is connected, allowing power to flow.
- OFF State (Power Off State): When the operating handle is in the DOWN position, a GREEN indicator is visible. The circuit breaker is in power off state, and the circuit is disconnected, interrupting power flow.
4.2. Testing the Leakage Protection
The RCBO is equipped with a 'Test' button (marked 'T') to verify the functionality of the residual current device (RCD) component. It is recommended to press this button monthly to ensure the leakage protection is working correctly. When pressed, a healthy RCBO should trip (switch to OFF position).
5. Maintenance
- Regular Inspection: Periodically check the physical condition of the circuit breaker for any signs of damage, discoloration, or loose connections.
- Functionality Test: Press the 'Test' button monthly to ensure the leakage protection mechanism is operational. If the RCBO does not trip when the test button is pressed, it may be faulty and should be replaced by a qualified electrician.
- Cleaning: Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquids or abrasive cleaners.
6. Troubleshooting
If the RCBO trips (switches to the OFF position), it indicates that a fault has been detected. Follow these steps:
- Identify the Cause:
- Overload: Too many appliances or devices are drawing power from the circuit.
- Short Circuit: A direct connection between live and neutral/earth wires, often due to faulty wiring or appliances.
- Earth Leakage: Current flowing to earth through an unintended path, often due to faulty insulation or equipment.
- Rectify the Fault:
- For overload, unplug some appliances from the circuit.
- For short circuit or earth leakage, disconnect all appliances from the affected circuit. Inspect appliances and wiring for damage.
- Reset the RCBO: Once the fault is rectified, switch the operating handle back to the ON position.
- If it Trips Again: If the RCBO trips immediately after resetting, or trips frequently, there is a persistent fault in the circuit or an issue with the RCBO itself. Do not attempt to repeatedly reset it. Contact a qualified electrician for diagnosis and repair.
- RCBO Does Not Reset: If the RCBO cannot be switched back to the ON position after rectifying the fault, it may be damaged internally and requires replacement by a professional.
7. Specifications

Figure 6: Product Parameters and Dimensions
| Parameter | Value |
|---|---|
| Model | FXB8L-40 |
| Product Type | RCBO (Residual Current Circuit Breaker with Overcurrent Protection) |
| No. of Poles | 1P+N |
| Rated Current | 6A / 10A / 16A / 20A / 32A / 40A |
| Standard | IEC61009-1, IEC60898-1 |
| Rated Frequency | 50/60Hz |
| Rated Voltage | AC230V |
| Rated Breaking Capacity | 6000A |
| Rated Residual Action Current (I△n) | 30mA |
| Residual Current Off-time Under I△n | ≤0.1s |
| Overall Dimensions (Front View) | 84.5mm × 18mm |
| Overall Dimensions (Side View) | 88mm × 75.3mm |
| Installation Width | 18mm |
| Operating Temperature | -20°C to +60°C |
| Housing Material | Thermosetting, Flame-Retardant, Insulating |
8. User Tips
- Prioritize Safety: Always ensure the main power is off before touching any wiring or the circuit breaker itself. If unsure, consult a professional electrician.
- Regular Testing is Key: Make it a habit to press the 'Test' button monthly. This simple action confirms your leakage protection is active and ready to protect.
- Understand Your Load: Be aware of the total power consumption of appliances connected to a circuit. Avoid overloading circuits to prevent nuisance tripping and ensure the longevity of your electrical system.
- Professional Help: For any complex electrical issues, persistent tripping, or if you are uncomfortable performing electrical work, always call a certified electrician.
9. Warranty and Support
For warranty information, please refer to the terms and conditions provided by your retailer or the point of purchase. Keep your proof of purchase for any warranty claims.
For technical support or further assistance, please contact the seller or your local VaneAims distributor.