1. Introduction
This document provides essential information for the installation, operation, and maintenance of your ECGSOLAX Solar Hybrid Inverter. This multifunctional inverter integrates an MPPT solar charge controller, a high-frequency pure sine wave inverter, and a UPS function module. It is designed for off-grid backup power and self-consumption applications and can operate with or without batteries. The built-in WiFi module allows for remote monitoring of the PV system via a mobile phone or website.
Key Features:
- Rated power 5KW/6.5KW, power factor 1
- MPPT range 60V ~ 450V, 500Voc
- High frequency design with small size and light weight
- Pure sine wave AC output
- Supports simultaneous solar and grid power loads
- CAN/RS485 for Battery Management System (BMS) communication
- Ability to operate without a battery
- Built-in WiFi for remote monitoring
- Dual AC output
- Feed-in to grid capability

2. Package Contents
Please verify that all items are included in your package:
- Inverter: 1 unit
- Datasheet: 1 (English)
- User manual: 1 (English)
- Tubular terminal: 10 units (for AC input, AC output, PV input)
- OT terminal: 1 unit (for PE)

3. Setup and Installation
Before proceeding with installation, ensure you have read and understood all safety warnings in the complete user manual. Installation should be performed by qualified personnel.
Component Identification:

Front Panel:
- AC Indicator
- Invert Indicator
- Charging Indicator
- Fault Indicator
- LCD Display
- ESC Button
- Up Button
- Down Button
- Enter Button
Rear Panel:
- Power On/Off Switch
- AC Input
- AC Output 1
- AC Output 2
- PV Input
- Battery Input
- BMS Port
- COM Port
- AC Input Breaker
- PE (Protective Earth)
Installation Notes:
- The L (Live) and N (Neutral) cables of the AC Input port must not be reverse-connected. Use a voltage tester (test pen) or multimeter to correctly distinguish between L and N cables before connection.
- Ensure proper grounding (PE connection) for safety.
- Connect solar panels to the PV Input, batteries to the Battery Input, and AC loads to AC Output 1 and AC Output 2.
- The inverter supports various battery types including Lithium and Lead-acid (SLD, FLD, AGM, GEL, LI, SUER).


4. Operating Instructions
The inverter features an LCD display and buttons for easy configuration and monitoring.
LCD Display and Buttons:
Use the ESC, Up, Down, and Enter buttons (5, 6, 7, 8, 9 on the front panel diagram) to navigate through the LCD menu and adjust settings. The LCD display (5) shows real-time status and operational parameters.
Charging and Output Modes:
The inverter offers flexible charging and output modes to suit various energy management needs.

4 Charging Modes:
- Mains First: Prioritizes utility grid power for charging.
- Solar First: Prioritizes solar power for charging.
- Hybrid Charge: Uses a combination of solar and utility power for charging.
- Only Solar: Charges exclusively from solar power.
4 Output Modes:
- Solar First: Prioritizes solar power for loads.
- Mains First: Prioritizes utility grid power for loads.
- Inverter First: Prioritizes battery power (via inverter) for loads.
- Hybrid Output: Uses a combination of available power sources for loads.
WiFi Monitoring:
The built-in WiFi function allows for remote monitoring. Refer to the full user manual for detailed instructions on connecting the inverter to your WiFi network and setting up the monitoring application or web interface.
5. Maintenance
To ensure optimal performance and longevity of your ECGSOLAX Solar Hybrid Inverter, regular maintenance is recommended.
- Regular Inspection: Periodically check all connections for tightness and signs of corrosion. Ensure ventilation openings are clear of dust and debris.
- Cleaning: Keep the inverter's exterior clean and free from dust. Use a dry, soft cloth for cleaning. Do not use liquid cleaners or solvents.
- Environmental Conditions: Ensure the inverter operates within its specified temperature and humidity ranges to prevent damage.
- Firmware Updates: Check the manufacturer's website or monitoring application for any available firmware updates to improve performance and add new features.
6. Troubleshooting
This section provides general guidance for common issues. For detailed troubleshooting steps, please refer to the comprehensive user manual (PDF).
- No Power: Check the Power On/Off Switch (1 on rear panel diagram) and the AC Input Breaker (9 on rear panel diagram). Verify all power connections (AC input, battery, PV input).
- Inverter Not Charging: Ensure solar panels are receiving adequate sunlight and are correctly connected to the PV Input. Check battery connections and health. Verify charging mode settings.
- Fault Indicator On: Refer to the LCD display for specific error codes or messages. Consult the full user manual for the meaning of each fault code and recommended actions.
- WiFi Monitoring Issues: Ensure the inverter is within range of your WiFi network. Check network settings and ensure the monitoring application is up to date.
7. Specifications
Below are the detailed specifications for the ECGSOLAX 5KW and 6.5KW Solar Hybrid Inverters.

| Category | Parameter | ECG-HVM5K-24V | ECG-HVM6.5K-48V |
|---|---|---|---|
| AC Input | Rated Input Voltage (VAC) | 208/220/230/240; L+N+PE | |
| Voltage Range (VAC) | 90~280 (APP mode); 170~280 (UPS mode) | ||
| Frequency (Hz) | 50/60 (Auto Adaptive) | ||
| Phase | 1-phase | ||
| AC Output | Rated Capacity (kW) | 5 (Output Power rating will be reduced to 90% when setting Output Voltage to 208V) | 6.5 (Output Power rating will be reduced to 90% when setting Output Voltage to 208V) |
| Surge Power (kVA) | 10 | 12 | |
| Voltage (VAC) | 208/220/230/240 | ||
| Power Factor (PF) | 1 | ||
| Frequency (Hz) | 50/60 ± 0.1% | ||
| Switch Time (ms) | 10 (APP/UPS mode) / 20 (GEN mode) | ||
| Charger (PV/AC) | Solar Charger Type | MPPT | |
| Max PV Input Current/Power | 27A/9000W | 27A/9000W | |
| MPPT Range@Operating Voltage (VDC) | 60~450 | ||
| PV Start-up Voltage | 60Vdc | ||
| Max PV Open Circuit Voltage (VDC) | 500 | ||
| Max PV Charge Current (A) | 160 | 120 | |
| Max AC Charge Current (A) | 160 | 120 | |
| Battery | Normal Voltage (VDC) | 24 | 48 |
| Floating Charge Voltage (VDC) | 27 | 54 | |
| Overcharge Protection (VDC) | 30.5 | 61 | |
| General Data | HMI | LCD | |
| Interface | RS485/RS232/USB | ||
| Monitoring | WiFi (Built-in) | ||
| Ingress Protection | IP21 | ||
| Operating Temperature | -10°C ~ 60°C | ||
| Relative Humidity | 5% ~ 95% (Non-condensing) | ||
| Net Weight (kg) | 8.4 | 10 | |
| Dimensions (W*H*D) | 410*336*110mm | ||


8. User Tips
- Verify Screen Appearance: Be aware that the actual screen size or appearance might differ slightly from promotional images. Always refer to the physical product and the detailed user manual for accurate information.
- Battery Compatibility: The inverter supports various battery types (Lithium, Lead-acid). Ensure your battery system (24V or 48V) matches the inverter model and is correctly configured for optimal performance and safety.
- Application Suitability: For specific high-power applications, such as powering multiple air conditioners, consult the detailed specifications in the user manual or contact technical support to confirm the inverter's suitability.
9. Warranty and Support
For detailed warranty information, terms, and conditions, please refer to the complete user manual provided with your product. The manual also contains contact information for technical support and service inquiries.
A comprehensive user manual in PDF format is available for download: View User Manual (PDF)