1. Product Overview

The VaneAims ATS Automatic Transfer Switch is designed to provide seamless power conversion and protection for various electrical systems. It acts as an Over/Under Voltage Protector and a PV Solar Phase Selector, ensuring stable and uninterrupted power supply.

Model Classification

The product series includes FXB-ATS-2R/2R-G, FXB-ATS-3D/3D-G/4D/4D-G/5D/5D-G. The '-G' suffix indicates a dark gray casing, while non-G models feature a white shell. Both versions offer identical function, size, and performance.

Model Classification and Features
ClassificationWhite Casing ModelDark Gray Casing Model
AC2*220V/110V (N1-L1/N2-L2) dual power automatic switching (L1→L2). Ideal for home photovoltaic systems.FXB-ATS-2RFXB-ATS-2R-G
AC 3*220V (N-L1/L2/L3) three-power priority switching (L1→L2→L3). Essential for factories.FXB-ATS-3DFXB-ATS-3D-G
FXB-ATS-4DFXB-ATS-4D-G
FXB-ATS-5DFXB-ATS-5D-G

WARNING: Disconnect the power supply before wiring.

2. Key Features & Functions

  • Automatic Transfer Switch with Priority Phase: Automatically switches between power sources (grid, solar, backup generator) based on voltage status, with configurable priority for the primary power supply to ensure uninterrupted power.
  • Microcontroller-Based Intelligent Control: High-precision MCU for stable, reliable operation and fast response to power anomalies.
  • Button-Adjustable Parameter Setting: All protection thresholds and delay times can be set directly via the front panel raised buttons, no external tools required.
  • Overvoltage & Undervoltage Protection: Customizable voltage protection ranges to prevent equipment damage from abnormal grid voltage.
  • Overcurrent Protection: Built-in overcurrent monitoring to protect circuits and connected loads from overload.
  • LED Digital Display & Indication: Real-time LED display of operating voltage/current, with clear status indicators for power source, protection events, and operation.
  • DIN-Rail Mounting: Standard 35mm DIN-rail design for easy installation in distribution cabinets, compatible with standard electrical enclosures.
Product Features: Icons for Over-voltage Protection, Under-voltage Protection, Over-current Protection, Phase Select, Automatic Reset, Action Time Adjustable, Reset Time Adjustable, Real Time Display of Current and Voltage, Flame Retardant Shell.

Figure 1: Key Product Features

3. Setup and Installation

Always ensure the power supply is disconnected before performing any wiring or installation procedures.

3.1. Product Appearance and Dimensions

FXB-ATS-2R Product Appearance and Size Drawing with dimensions: 90mm width, 95mm height, 66mm depth, 35mm DIN rail mount.

Figure 2: FXB-ATS-2R Dimensions

FXB-ATS-3D/4D/5D Product Appearance and Size Drawing with dimensions: 90mm width, 95mm height, 66mm depth, 35mm DIN rail mount.

Figure 3: FXB-ATS-3D/4D/5D Dimensions

3.2. Wiring Diagrams

Ensure correct wiring according to the diagrams below. Pay close attention to input (L1, L2, L3, N) and output (L-out, N) connections.

FXB-ATS-2R Two-Way Automatic Transfer Switch connection diagram showing L1 (Public Power) and L2 (Inverter/Generator) inputs and a single output.

Figure 4: FXB-ATS-2R Two-Way Wiring Diagram

FXB-ATS-3D/4D/5D Three-Way Automatic Transfer Switch connection diagram showing L1 (Public Power), L2 (Inverter), and L3 (Generator) inputs and a single output.

Figure 5: FXB-ATS-3D/4D/5D Three-Way Wiring Diagram

Detailed panel operation and wiring diagrams for FXB-ATS-3D, FXB-ATS-4D, and FXB-ATS-5D models, showing input terminals L1, L2, L3, N and output L-out, N. Includes button functions.

Figure 6: Detailed Wiring and Panel for FXB-ATS-3D/4D/5D

4. Operating Instructions

4.1. Panel Operation and Display

The device features a digital display panel that shows the working voltage in real-time. Status indicators provide information on the active power source, protection events, and overall operation.

  • L1, L2, L3 Output Indicator Light: Indicates which phase is currently active.
  • Fault Indicator Light: Illuminates when a fault is detected.

4.2. Button Functions

  • SET (Menu Key): Used to enter the settings menu and confirm selections.
  • ▲ (Up Key / Up Button): Used to navigate up in menus or increase parameter values.
  • ▼ (Down Key / Down Button): Used to navigate down in menus or decrease parameter values.
  • ⑉ (Power On/Off): Used to manually switch the device on or off.

4.3. Working Mode Demonstration

The device automatically switches between power sources based on configured priority and voltage status. For example, in FXB-ATS-2R, L1 is typically the main power, and L2 is the backup (e.g., inverter or generator). If L1 fails, the switch will instantly transfer to L2. When L1 returns to normal, the switch will automatically revert to L1.

FXB-ATS-2R Working Mode Demonstration: Shows normal operation with L1 active and fault status with L1 power-off, initiating a switch countdown to L2.

Figure 7: FXB-ATS-2R Working Mode

During a switch, the display will show a countdown. 'PL' indicates a power-off status, 'S' indicates a switch countdown, and 'FAULT' indicates fault detection in progress.

Video 1: Product Function Demonstration (Dual and Three Power Switch)

4.4. Parameter Settings

Parameters such as overvoltage/undervoltage protection ranges, overcurrent protection, and various delay times can be adjusted using the front panel buttons. Refer to the detailed technical specifications for default and adjustable ranges.

Priority Phase Setting and Automatic Switching parameters for FXB-ATS-2R, including Power-on delay time, Protection recovery delay, Overvoltage protection value, Undervoltage protection value, Overcurrent protection value, Overcurrent protection action time, and Continuous overcurrent protection frequency.

Figure 8: FXB-ATS-2R Parameter Settings

Overvoltage and Undervoltage Protection Ranges for 220V and 110V types, and Overcurrent Protection Range for FXB-ATS-2R and FXB-ATS-3D/4D/5D.

Figure 9: Protection Range Settings

5. Maintenance

The VaneAims ATS Automatic Transfer Switch is designed for reliable operation with minimal maintenance. However, regular checks are recommended to ensure optimal performance and safety:

  • Visual Inspection: Periodically inspect the device for any signs of physical damage, loose connections, or overheating.
  • Cleanliness: Keep the device free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquids or abrasive cleaners.
  • Connection Integrity: Ensure all wiring connections remain tight and secure. Loose connections can lead to poor performance or safety hazards.
  • Environmental Conditions: Ensure the device operates within the specified ambient temperature and humidity ranges to prevent premature failure.

6. Troubleshooting

This section addresses common issues you might encounter with your ATS. For problems not listed here, please contact customer support.

ProblemPossible CauseSolution
Device not powering on or displaying anything.No input power, incorrect wiring, or internal fault.Check input power supply. Verify all wiring connections are correct and secure. If problem persists, contact support.
Automatic transfer not occurring.Incorrect voltage/current settings, fault in primary source, or incorrect priority setting.Check the voltage and current of both power sources. Review parameter settings for over/undervoltage and priority. Ensure the fault indicator is not active.
Display shows incorrect values or missing segments (e.g., missing comma).Display malfunction or minor internal issue.While often cosmetic, if it affects readability or functionality, contact customer support for assistance.
Device appears damaged upon arrival.Shipping damage.Immediately document the damage with photos and contact the seller or shipping carrier. Do not attempt to install or use a damaged device.

7. Technical Specifications

ParameterFXB-ATS-2R / 2R-GFXB-ATS-3D/4D/5D / 3D-G/4D-G/5D-G
Supply TerminalsN1, L1, N2, L2N, L1, L2, L3
Rated Supply VoltageAC 2×220V (N1-L1 / N2-L2)AC 3×220V (N-L1 / L2 / L3)
Rated Frequency40 / 50 / 60 / 70Hz40 / 50 / 60 / 70Hz
Overvoltage Protection Range (220V Type)130-300V130-300V
Overvoltage Protection Range (110V Type)130-150VN/A
Undervoltage Protection Range (220V Type)80-210V80-210V
Undervoltage Protection Range (110V Type)80-100VN/A
Overcurrent Protection Range1A-63A / 80A / 100A1A-63A / 80A / 100A
Auto-reclosing Delay (Ton)1-600s (adjustable)1-600s (adjustable)
Power-on Delay Protection Time1-600s (adjustable)1-600s (adjustable)
Switch Delay to Reserve Phases<0.2s<0.2s
Voltage Hysteresis5V5V
Overvoltage Trip Delay0.1s; ≥350V: 0.02s0.1s; ≥350V: 0.02s
Undervoltage Trip Delay0.1s; ≥350V: 0.02s0.1s; ≥350V: 0.02s
Voltage Accuracy<1%<1%
Max. Operating Phase Voltage350V350V
Rated Operating Current63A / 80A / 100A63A / 80A / 100A
Pollution Degree33
Electrical Life105 cycles105 cycles
Mechanical Life106 cycles106 cycles
Altitude≤2000m≤2000m
Ambient Temperature-25℃ ~ +50℃-25℃ ~ +50℃
Relative Humidity≤50% at 40℃ (without condensation)≤50% at 40℃ (without condensation)
Storage Temperature-25℃ ~ +55℃-25℃ ~ +55℃
Conductor Size0.5mm2-1mm2N/A

8. User Tips

  • Switching Speed: While the device boasts a fast switching delay of <0.2 seconds, the auto-reclosing delay (Ton) is adjustable from 1 to 600 seconds. For sensitive equipment like computers, ensure this delay is set appropriately to prevent interruptions.
  • Proper Installation: Always ensure the device is assembled and wired correctly. Double-check all connections before applying power.
  • Neutral Wire Connection: For models with zero-break protection, the neutral wire must be connected for proper functionality.
  • Voltage Compatibility: Ensure the selected model (220V or 110V type, if applicable) matches your power supply voltage.

9. Warranty and Support

For warranty information, technical support, or any inquiries regarding your VaneAims ATS Automatic Transfer Switch, please refer to the official seller's documentation or contact their customer service directly. A user manual in PDF format is available for detailed guidance, which can be accessed via the provided link on the product page.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.