1. Introduction
The SINOTIMER STVP-930 is a three-phase automatic over-voltage and under-voltage protective device designed for AC 380V, 50/60Hz electrical systems. This device is crucial for safeguarding electrical equipment from damage caused by voltage anomalies.
Its primary function is to instantaneously cut off the power supply when the circuit experiences over-voltage or under-voltage conditions. Once the circuit voltage returns to normal, the protector automatically restores the power supply, ensuring continuous operation and protection.
For detailed information, please refer to the official user manual PDF: STVP-930 User Manual (PDF).
2. Safety Information
- Installation and maintenance should only be performed by qualified electricians.
- Ensure the main power supply is disconnected before any installation or wiring work.
- Verify correct wiring connections (L1, L2, L3, N) to prevent damage to the device and connected equipment.
- Do not operate the device if it appears damaged or malfunctioning.
- This device is designed for indoor use in a dry environment.
- The device operates at high voltage (above 50Vac or 75Vdc); exercise extreme caution.
3. Product Features
- Three-phase over-voltage protection
- Three-phase under-voltage protection
- Phase loss protection
- Neutral wire break protection
- Phase sequence protection
- Phase unbalance protection
- Automatic recovery of power supply after voltage normalization
- Fast response time for protection activation
- DIN rail mounting for easy installation
4. Specifications
| Parameter | Value |
|---|---|
| Model Number | STVP-930 |
| Power Supply | AC 230/400V 50/60Hz (Three Phase) |
| Max Load Current | 63A / 80A (selectable) |
| Over-voltage Protection Value | 285V +/- 5V |
| Under-voltage Protection Value | 160V +/- 5V |
| Off Time (Protection Response) | <0.1s |
| Recovery Delay Time | <60s +/- 1s |
| Dimensions (L*W*H) | 72mm * 65mm * 80mm |
| Installation | 35mm DIN Rail |
| Certification | CE |
5. Installation and Setup
5.1 Mounting
The STVP-930 is designed for 35mm DIN rail mounting. Snap the device onto a standard DIN rail within your electrical distribution box or control panel. Ensure it is securely fastened.
5.2 Wiring Diagram
Connect the device according to the following diagram. Ensure all connections are tight and correctly phased (L1, L2, L3, N).
- Input (IN): Connect the three-phase power supply (L1, L2, L3, N) from your main power switch or circuit breaker to the 'IN' terminals of the STVP-930.
- Output (OUT): Connect the 'OUT' terminals of the STVP-930 to the input of your load's circuit breaker or directly to the equipment requiring protection.
- Ensure the neutral wire (N) is correctly connected for proper operation of the under-voltage protection.
6. Operating Instructions
The STVP-930 operates automatically once installed and powered. It continuously monitors the three-phase voltage for anomalies.
- Over-voltage Protection: If any phase voltage exceeds 285V +/- 5V, the device will trip and cut off the power supply within 0.1 seconds.
- Under-voltage Protection: If any phase voltage drops below 160V +/- 5V, the device will trip and cut off the power supply within 0.1 seconds.
- Phase Loss/Sequence/Unbalance/Neutral Break Protection: The device also monitors for these conditions and will trip if detected.
- Automatic Recovery: After a trip, the device will wait for approximately 60 seconds (+/- 1 second) after the voltage returns to its normal operating range before automatically re-establishing the power supply. This delay prevents rapid cycling during unstable conditions.
7. Troubleshooting
- Device not powering on: Check the incoming power supply and all wiring connections. Ensure the voltage is within the normal operating range.
- Device trips frequently: This indicates persistent voltage issues (over-voltage, under-voltage, phase problems) in your electrical system. Consult an electrician to diagnose the root cause of the voltage instability.
- Device does not recover automatically: Ensure the voltage has stabilized within the normal range for the recovery delay period. If it still doesn't recover, check for persistent fault conditions or consult the manufacturer.
- No output power: Verify that the device is powered, not in a tripped state, and that the downstream circuit breaker is not tripped.
8. Maintenance
- Periodically inspect the device and its connections for any signs of wear, damage, or loose wiring.
- Keep the device clean and free from dust and debris.
- Ensure adequate ventilation around the device to prevent overheating.
- Do not attempt to open or repair the device yourself. Refer to qualified personnel for service.
9. User Tips
- Consider installing a main circuit breaker upstream of the protective device for easy isolation during maintenance.
- If you experience frequent power fluctuations, this device can help protect your sensitive equipment.
- Always ensure the selected current rating (63A or 80A) matches or exceeds the maximum expected load of your circuit.