ANENJI ANJ-12KW-110V-W

Contents

ANENJI 120/240V 12KW Hybrid Solar Inverter User Manual

Model: ANJ-12KW-110V-W

Brand: ANENJI

1. Safety Information

This manual contains important information, guiding principles, operation, and maintenance of the ANENJI Hybrid Solar Inverter. Users must follow these instructions during installation, use, and maintenance.

1.1 Symbols and Descriptions

SymbolDescription
DANGERDangerous situations that will lead to death or serious injury when ignored.
WARNINGDangerous situations that may lead to death or serious injury when ignored.
CAUTIONDangerous situations that may lead to mild or moderate injury when ignored.
NOTICEOperation tips.

1.2 Safety Matters

  • This chapter contains important safety matters. Please read and keep this Manual for future reference.
  • Please make sure to comply with local requirements and regulations when installing the inverter.
  • Be careful of high voltage. Before and during installation, please turn off the switch of each power supply to avoid electric shock.
  • In order to achieve optimal operation of the inverter, please select the appropriate cable size and necessary protective devices according to regulations.
  • Do not connect or disconnect any connections when the inverter is working.
  • Do not open the terminal cover when the inverter is working.

2. Product Overview

2.1 Description

The ANENJI Hybrid Solar Inverter is a new type of solar storage inverter that integrates PV storage, mains charge, and energy storage, outputting sinusoidal AC. Equipped with DSP control and advanced control algorithms, it offers high response speed and good reliability, suitable for industrial scenarios.

2.2 Features

  • Supports various energy storage batteries (lead-acid, lithium-ion).
  • Dual activation function for lithium-ion battery sleep (mains/PV power can activate).
  • Supports split-phase/single-phase pure sine wave output.
  • Adjustable phase voltage (100 VAC, 105 VAC, 110 VAC, 115 VAC, 120 VAC).
  • Two-channel PV input with simultaneous Maximum Power Point Tracking (MPPT) for charging/carrying capacity.
  • MPPT efficiency up to 99.9%, max single-channel current 22 A for high-power modules.
  • Four charge modes: only PV, mains first, PV first, and mains + PV.
  • Timed charge and discharge function for cost savings based on time-of-use prices.
  • Energy-saving mode to reduce no-load energy losses.
  • Two output modes: mains bypass output and inverter output for uninterrupted power supply.
  • LCD display of dynamic flowchart, system data, and operating status.
  • 360° protection: short circuit, overcurrent, overvoltage, undervoltage, overload.
  • Supports CAN, USB, RS485 communication.

2.3 System Connection Diagram

The inverter integrates solar power, battery storage, and utility/generator input to power home appliances.

System Connection Diagram

Image Description: A diagram illustrating the typical setup of the ANENJI solar inverter. Components include Solar Power (PV array), a Generator or Utility grid as AC input, a LifePO4 Battery (48V/51.2V), the ANENJI Inverter, and various Home Appliances (refrigerator, laptop, washing machine, TV, air conditioner) as loads. The inverter acts as the central hub connecting all power sources and loads.

2.4 Product Overview (Components)

The inverter features a clear display and accessible ports for easy setup and monitoring.

Inverter Front and Rear Panel Overview

Image Description: Top-down view of the inverter showing its dimensions (640.8mm H x 443.0mm W x 144.0mm D). The front panel features an LCD screen, set buttons, and LED indicators. The rear panel shows: AC input circuit breaker, USB port, WiFi port, RS485/CAN port, Dry contact, AC IN, AC OUT, Grounding screw, Parallel communication port, Battery (negative/positive electrode) terminals, and PV input terminals (PV1, PV2).

No.ComponentNo.ComponentNo.Component
1LCD screen2Set button3LED indicator
4Switch5PV input6Battery (positive electrode)
7Battery (negative electrode)8Dry contact9RS485/CAN port
10WIFI port11USB port12Grounding screw
13AC OUT14AC IN15AC input circuit breaker
16Parallel port

3. Setup and Installation

3.1 Installation Location

For indoor use only (protection level: IP20). Consider the following factors:

  • A solid wall.
  • Installation height: flush with the line of sight.
  • Sufficient heat dissipation space (minimum 500mm clearance above and below, 200mm on sides).
  • Ambient temperature: -10°C to 55°C (14°F to 131°F).

3.2 Inverter Installation

Drill 4 installation holes of specified sizes on the wall. Insert 2 expansion screws above and fix the inverter with 2 M5 screws below.

3.3 Removal of Terminal Cover and Insect-Proof Net

Remove the terminal cover and insect-proof net with a screwdriver for cleaning. Regularly clean the insect-proof net to prevent overheating and ensure proper airflow.

4. Wiring

4.1 Wiring Mode (Output Dependent)

Split-Phase Mode (Default)

Rated Output Voltage (L-N): 100-120 VAC (default 120 VAC)
Rated Output Line Voltage (L-L): 200-240 VAC (default 240 VAC)

Single-Phase Mode

Rated Output Voltage (L-N): 100-120 VAC (default 120 VAC)

4.2 Cable and Circuit Breaker Model

PV Input Wiring
Cable SizeMaximum Input CurrentCircuit Breaker Model
5 mm² / 10AWG22 A2P-25A
AC Input Wiring
Output ModeMaximum CurrentCable SizeCircuit Breaker Model
Split-phase mode63A (L1/L2/N)13 mm² / 6 AWG (L1/L2/N)3P-63A
Single-phase mode63A (L1/L2), 126 A (N)13 mm² / 6 AWG (L1/L2), 26 mm² / 3 AWG (N)2P-125A
Battery Wiring
Cable SizeMaximum CurrentCircuit Breaker Model
42 mm² / 1 AWG220 A2P-250A
AC Output Wiring
Output ModeMaximum CurrentCable SizeCircuit Breaker Model
Split-phase mode63A (L1/L2/N)13 mm² / 6 AWG (L1/L2/N)3P-63A
Single-phase mode63A (L1/L2), 84 A (N)13 mm² / 6 AWG (L1/L2), 26 mm² / 3 AWG (N)2P-125A

4.3 AC Input and Output Wiring

Connect the live wire, neutral wire, and ground wire according to the cable position and sequence. Before connecting, disconnect the circuit breaker to avoid electric shock. Ensure cables meet requirements.

4.4 Battery Wiring

Connect the positive and negative cables of the battery according to the cable position and sequence. Before connecting, disconnect the circuit breaker. Check positive and negative terminals for correct connection to avoid damage.

4.5 PV Wiring

Connect the positive and negative terminals of the two-channel PV modules. Disconnect the circuit breaker before connecting. Ensure open circuit voltage does not exceed 500 VDC.

4.6 Dry Contact Wiring

Use a small-sized screwdriver to push back and insert the communication cable (0.2 mm² - 1.5 mm² section) into the dry contact port.

4.7 Grounding

Ensure the grounding terminal is reliably connected to the grounding bus bar. The grounding cable size shall not be less than 4 mm² and be as close as possible to the grounding point.

4.8 Inverter Start

  1. Close the circuit breaker of the battery.
  2. Press the switch at the bottom of the inverter; screen and indicator will light up.
  3. Close the circuit breakers for PV input, AC input, and AC output in sequence.
  4. Start loads one by one, from small to large.

4.9 Parallel Wiring

The inverter supports parallel operation for up to six units. Use the provided parallel communication cable, ensuring correct and reliable connections.

4.9.1 Cautions for Parallel Connection

  • PV Wiring: Each inverter's PV array must be independent.
  • Battery Wiring: All inverters must connect to the same battery, ensuring correct polarity, wiring length, and cable size.
  • AC OUT Wiring: Connect L-to-L, N-to-N, PE-to-PE. For three-phase, L lines of the same phase connect together.
  • AC IN Wiring: Connect L-to-L, N-to-N, PE-to-PE. Only one AC source input is allowed.
  • Communication Wiring: Use DB15 shielded cables. Connect male (out) to female (in) of the next inverter. Tighten screws.

4.9.2 Parallel Wiring Diagrams

Below are examples of parallel wiring configurations. For detailed diagrams of all configurations (up to 6 units, single-phase, two-phase, split-phase, three-phase), please refer to the full PDF manual.

Single-Phase Parallel Connection (2 Inverters)
Single-Phase Parallel Connection Diagram (2 Inverters)

Image Description: A diagram showing two solar inverters connected in parallel for single-phase output. Each inverter has independent PV arrays (PV1+, PV1-, PV2+, PV2-). Both inverters share a common battery bank, utility grid connection, and loads. Communication cables link the parallel ports of the inverters. Output L1 and L2 are connected in parallel to the loads.

Two-Phase Parallel Connection (2 Inverters)
Two-Phase Parallel Connection Diagram (2 Inverters)

Image Description: A diagram showing two solar inverters (P1 and P2) connected for two-phase split-phase output. Each inverter has independent PV arrays. Both inverters share a common battery bank, utility grid connection, and loads. Communication cables link the parallel ports. P1 provides L1 and P2 provides L2, creating a 120V/240V split-phase system.

Three-Phase Parallel Connection (3 Inverters)
Three-Phase Parallel Connection Diagram (3 Inverters)

Image Description: A diagram showing three solar inverters (P1, P2, P3) connected for three-phase output. Each inverter has independent PV arrays. All inverters share a common battery bank, utility grid connection, and loads. Communication cables link the parallel ports. P1 provides L1, P2 provides L2, and P3 provides L3, creating a three-phase system.

5. Operating Instructions

5.1 Operation and Display Panel

The inverter's operation panel includes an LCD screen, three LED indicators, and four physical buttons.

Inverter Display Panel

Image Description: A close-up of the inverter's front panel showing the circular LCD screen, four navigation buttons (up, down, enter, exit), and three LED indicators (AC/INV, CHARGE, FAULT).

Physical Buttons

  • Exit/Enter: Enter/Exit the setup menu.
  • Up/Down: Navigate through options.
  • Confirm: Confirm/Enter the option in setup menu.

LED Indicators

  • AC/INV (Green): Normally ON for mains bypass output, Flashing for inverter output.
  • CHARGE (Yellow): Normally ON for charging completed, Flashing for charging.
  • FAULT (Red): Normally ON for level-1 fault, Flashing for level-2 fault, OFF for level-3 or level-4 fault.

5.2 Settings

The inverter settings can be accessed and modified via the LCD screen and physical buttons. A flowchart guides through the setting process: Touch Screen -> Enter Setting Item -> Touch UP/DOWN -> View Setting Parameter -> Touch ENTER -> Edit Setting Parameter -> Touch UP/DOWN -> Modify Parameter Content -> Touch ENTER -> Confirm Parameter Content.

Key settings include:

  • AC Output Mode (ID 01): UTI (default, PV/Mains mix), SBU (Inverter first), SOL (PV first).
  • Battery Charge Mode (ID 06): SNU (default, PV first, then Mains), OSO (PV only), CUB (Mains first), CSO (PV first).
  • Battery Type (ID 08): User-defined, Sealed Lead-Acid, Flooded Lead-Acid, Gel Lead-Acid, LFP (L14/L15/L16), Ternary Li-ion (N13/N14).
  • AC Output Voltage (ID 38): 100/105/110/115/120 VAC.
  • Parallel Mode (ID 31): SIG (Single), PAL (Parallel), 2P0/2P1/2P2 (Two-phase), 3P1/3P2/3P3 (Three-phase).

For a complete list of parameters and their options, refer to the Parameter Table section or the full PDF manual.

5.3 AC Output Mode

  • Mains First (UTI): Mains supplies power. PV and mains can supply power simultaneously. Battery powers loads only during mains unavailability. (Priority: Mains > PV > Battery)
  • Mix Loading (MIX LOD): PV and mains supply power to the load simultaneously. (Priority: PV > Mains > Battery)
  • PV First (SOL): PV supplies power. If PV is insufficient, mains supplements. Maximizes PV use. (Priority: PV > Mains > Battery)
  • Inverter Output (SBU): PV supplies power. If PV is insufficient, mains supplements. Switches to mains if battery voltage drops below threshold. (Priority: PV > Battery > Mains)

5.4 Battery Charge Mode

  • Mix Charge (SNU): PV charges first, mains supplements if PV is insufficient. Fastest charge. (Priority: PV > Mains)
  • Only-PV Charge (OSO): Only PV charges the battery. Most energy-saving.
  • Mains-First Charge (CUB): Mains charges first. PV charges only when mains is unavailable. (Priority: Mains > PV)
  • PV-First Charge (CSO): PV charges first. Mains charges only if PV fails. Maximizes PV use. (Priority: PV > Mains)

5.5 Timed Charge/Discharge Function

The inverter features timed power charge/discharge functions. Users can set different charge and discharge periods based on local time-of-use prices to optimize energy usage. This function can be enabled/disabled in settings (items 46 and 53), with periods set in parameters 40-45 and 47-52.

5.6 Battery Parameters

The inverter supports various battery types with configurable parameters. Below are typical settings:

Lead-Acid Battery Parameters

ParameterSealed (SLD)Gel (GEL)Flooded (FLD)User-Defined (USE)
Overvoltage Disconnect60 V60 V60 V60 V
Boost Charge Voltage57.6 V56.8 V57.6 V40 V-60 V (settable)
Floating Charge Voltage55.2 V55.2 V55.2 V40 V-60 V (settable)
Under-voltage Alarm44 V44 V44 V40 V-60 V (settable)
Discharge Limit Voltage40 V40 V40 V40 V-60 V (settable)

Li-ion Battery Parameters

ParameterTernary N13Ternary N14LFP L16LFP L15LFP L14User-Defined (USE)
Overvoltage Disconnect60 V60 V60 V60 V60 V60 V
Boost Charge Voltage53.2 V57.6 V56.8 V53.2 V49.2 V40 V-60 V (settable)
Floating Charge Voltage53.2 V57.6 V56.8 V53.2 V49.2 V40 V-60 V (settable)
Under-voltage Alarm43.6 V46.8 V49.6 V46.4 V43.2 V40 V-60 V (settable)
Discharge Limit Voltage36.4 V39.2 V46.4 V43.6 V40.8 V40 V-60 V (settable)

6. Communication

6.1 Overview

The inverter provides multiple communication ports for monitoring and control.

Communication Ports

  • USB-B Port: For connecting to a computer for parameter reading and modification.
  • WIFI Port: For connecting to a Wi-Fi/GPRS data acquisition module for mobile APP monitoring.
  • RS485/CAN Port: For connecting to the BMS of a Li-ion battery.
  • Dry Contact Port: Provides ON/OFF signal output, battery temperature sampling, and remote generator start/stop functions.
  • Parallel Port: For communication between multiple inverters in a parallel setup.

7. Maintenance

To maintain optimal long-term performance, perform the following checks twice a year:

  1. Ensure clear airflow around the inverter; remove dirt/debris from the heat sink.
  2. Check insulation of exposed wires for damage (sunlight, friction, dryness, pests); repair/replace as needed.
  3. Verify consistency of indications/display with device operation; address any faults.
  4. Check all wiring terminals for corrosion, insulation damage, signs of high temperature; tighten terminals.
  5. Clean dirt, nesting insects, and corrosion; clean insect-proof net regularly.
  6. If the arrester fails, replace it promptly to prevent lightning damage.

DANGER: Before any inspection or operation, ensure the inverter is disconnected from all power sources and capacitors are fully discharged.

The manufacturer is not responsible for damage due to improper use, incorrect installation, exceeding voltage/temperature limits, unauthorized dismantling, or force majeure.

8. Troubleshooting

8.1 Fault Codes and Response Measures

The inverter displays fault codes to indicate specific issues. Refer to the table below for common fault codes and their meanings. For a comprehensive list, consult the full PDF manual.

Fault CodeMeaningDescription
01BatVoltLowBattery under-voltage alarm
03BatOpenDisconnected battery alarm
05BatOverCurrHwBattery overcurrent hardware protection
09PvVoltHighPV overvoltage protection
14OverloadInverterInverter overload protection
17InvShortInverter short-circuit protection
20OverTemperInvInverter heat sink over-temperature protection
21FanFailFan fault

8.2 General Troubleshooting

Fault CodeMeaningCauseSolution
/No screen displayNo power input or device switch is OFFCheck battery/PV air-switch, ensure switch is ON, press any button to exit sleep mode.
01Battery under-voltageBattery voltage below set valueCharge battery until voltage exceeds set value.
03Disconnected batteryBattery not connected or BMS protectionCheck battery connection, circuit breaker, and BMS communication.
14Inverter overloadOutput power/current overloadedReduce load power and restart device.
19Over-high temp (PV input)PV input heat sink temp > 90°C for 3sWait until heat sink temp is below recovery temp.

8.3 Protection Functions

The inverter includes various protection mechanisms:

  • PV Current-Limiting: Charges at rated current/power if PV exceeds inverter's rating.
  • PV Overvoltage: Reports fault and stops step-up if PV voltage exceeds max.
  • Reverse Charge (Night): Prevents battery discharge to PV module at night.
  • Mains Input Overvoltage/Undervoltage: Stops charging/switches to inverter output if mains voltage is out of range.
  • Battery Overvoltage/Undervoltage: Stops charging/discharging if battery voltage is out of range.
  • Battery Overcurrent: Turns off output and stops discharging if battery current exceeds limits.
  • AC Output Short-Circuit: Turns off AC output immediately; requires manual restart.
  • Heat Sink Over-Temperature: Stops charging/discharging if internal temperature is too high.
  • Overload: Turns off output after a delay based on overload level; multiple attempts before permanent shutdown.

9. Specifications

AC Mode
Rated Input Voltage120Vac (L1/N, L2/N) / 240Vac (L1/L2)
Input Phase Voltage Range90Vac - 140Vac (L1-N/L2-N)
Frequency50Hz/60Hz
Overload/Short Circuit ProtectionCircuit breaker
Conversion Time (Bypass and Inverter)10ms (typical)
Inverter Mode
Output Voltage WaveformPure sine wave
Rated Output Power (VA)Split phase: 12000VA, Single phase: 6000VA
Rated Output Power (W)Split phase: 12000W, Single phase: 6000W
Rated Output Voltage (Vac)120Vac (L1/N, L2/N) / 240Vac (L1/L2)
Maximum Efficiency>91%
Rated Battery Input Voltage51.2V
Battery Voltage Range40.0Vdc - 58.4Vdc
AC Charging
Battery TypeLead acid or lithium battery
Maximum Charge Current120A
Charge Voltage Range40Vdc - 58.4Vdc
PV Charging
Number of MPPT Groups2
Maximum PV Open Circuit Voltage500Vdc
MPPT Voltage Range125Vdc - 425Vdc
Maximum PV Input Power5500W + 5500W
Maximum PV Input Current22A + 22A
PV Charge Current200A
Certified Specifications
Operating Temperature Range-10°C ~ 55°C
Storage Temperature Range-25°C ~ 60°C
Humidity Range5% to 95%
Noise≤60dB
Heat DissipationForced air cooling, variable speed of fan
Communication InterfaceUSB/RS485/CAN/WiFi/GPRS/ Dry node control
Permitted Parallel Number1-6
Size (L*W*D)610mm*443mm*144mm
Weight (kg)28kg

10. User Tips

No specific user tips are available from provided reviews or Q&A content.

11. Warranty and Support

For warranty information, technical support, or service inquiries, please contact ANENJI customer service or your authorized dealer. Keep your purchase receipt for warranty claims.

For the complete and most detailed instructions, including all wiring diagrams and advanced settings, please refer to the official PDF user manual: ANENJI MPPT Solar Inverter User Manual (PDF).

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.