Contents

Anern FGI-S6500/FGI-S5000 Hybrid Solar Inverter User Manual

Upgraded Version 5KW/ 6.5KW Hybrid Solar Inverter Off-grid Build-in MPPT 120A/160A 24V/48V Pure Sine Wave Solar Inverter

1. Introduction

This manual provides detailed instructions for the assembly, installation, operation, and troubleshooting of the Anern FGI-S6500/FGI-S5000 Hybrid Solar Inverter. Please read this manual carefully before installation and operation to ensure safe and efficient use.

1.1 Product Overview

The Anern Hybrid Solar Inverter is a multifunctional device integrating an MPPT solar charge controller, a high-frequency pure sine wave inverter, and a UPS function module. It is designed for off-grid backup power and self-consumption applications and can operate with or without batteries.

Anern FGI-S6500 Hybrid Solar Inverter with key features
Figure 1: Anern FGI-S6500 Hybrid Solar Inverter with key features including 5KW/6.5KW, 24V/48Vdc, 50Hz/60Hz, 220V/230V/240Vac output.

1.2 Key Features

  • Rated power: 6.5KW/6.5KVA, power factor 1
  • MPPT range: 60V~450V, 500Voc
  • High frequency inverter with small size and light weight
  • Pure sine wave AC output
  • Solar and utility grid can power loads simultaneously
  • CAN/RS485 for BMS communication
  • Ability to work without battery
  • WIFI remote monitoring (optional)
  • Dual AC output
  • Feed-in to grid
6500W Solar Inverter Off-Grid Features
Figure 2: Key features of the 6500W Off-Grid Solar Inverter, including 48V DC to 220/230/240VAC, 120A MPPT Controller, Max PV Array Power 9000W, 450V, 27A, compatible with 24V Lead-acid and Lithium Batteries, and supports Solar, Utility, or Generator Power.

1.3 Hybrid Solar Energy Storage System Diagram

Hybrid Solar Energy Storage System Diagram
Figure 3: Diagram illustrating the Hybrid Solar Energy Storage System, showing connections between Solar Panels, Grid, Generator, Inverter, Lithium/Lead-acid Battery, and Home Loads, with optional Cloud/APP monitoring.

2. Safety Instructions

This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

2.1 General Safety Warnings

  • WARNING! High voltage: Above 50Vac or 75Vdc. Electrical Hazard!
  • CAUTION! Do not disconnect under load!
  • Start maintaining the INVERTER at least 5 minutes after disconnecting from all external power supplies.
  • Read instructions carefully before performing any operation on the INVERTER.
  • Grounding: The system must be firmly grounded for operator safety.
  • Ensure correct battery system type (lithium or lead-acid) is selected for normal energy storage system operation.
  • All operations and connections must be performed by professional electrical or mechanical engineers.
  • All electrical installations must comply with local electrical safety standards.
  • When installing PV modules in the daytime, cover them with opaque materials to prevent danger from high terminal voltage.
  • CAUTION! To reduce risk of injury, charge only deep-cycle lead-acid type rechargeable batteries and lithium batteries. Other types of batteries may burst.
  • Do not disassemble the unit. Refer service and repair to a qualified service center.
  • Disconnect all wirings before any maintenance or cleaning. Turning off the unit will not reduce this risk.
  • NEVER charge a frozen battery.
  • Follow required specifications for appropriate cable size for optimum operation.
  • Be cautious when working with metal tools on or around batteries to avoid short circuits or sparks.
  • Strictly follow installation procedures for disconnecting AC or DC terminals.
  • This inverter should be connected to a permanent grounded wiring system.
  • NEVER short circuit AC output and DC input. Do NOT connect to the mains when DC input short circuits.
  • Ensure the inverter is completely assembled before operation.

3. Setup and Installation

3.1 Unpacking and Inspection

Upon receipt, inspect the product for any damage. If damaged, contact your local distributor. Verify that the outer packaging is intact and that no internal equipment is damaged.3.2 Installation Tools

The following tools are recommended for installation:

  • Multi-meter
  • Protective gloves
  • Insulated anti-smashing shoes
  • Safety glasses
  • ESD wrist strap
  • Hammer drill
  • Electric screwdriver
  • Cross screwdriver
  • Rubber mallet
  • Spirit level
  • Wire cutter / stripper
  • Terminal crimping tool

3.3 Packing List

Ensure all items are present in the package:

No.ItemQuantityDescriptionRemarks
1Inverter1
2User manual1English
3Tubular Terminal10E6010For AC input, AC output and PV input.
4OT terminal1For PE

3.4 Mounting Unit

The inverter is suitable for mounting on concrete or other non-combustible surfaces only. Mount the inverter at eye level on a solid surface to allow easy reading of the LCD display. The recommended ambient temperature is between -15°C and 50°C. Install the unit vertically, ensuring sufficient space for heat dissipation and wiring.

  1. Use an Ø8 drilling bit to drill holes on the mounting surface, 200mm apart. Insert M6 expansion screw tubes.
  2. Align the inverter's top screw holes with the installed expansion screw tubes and fix the inverter to the wall.
  3. Before connecting any wiring, remove the bottom cover by unscrewing the four retaining screws.
Inverter Mounting Dimensions
Figure 4: Inverter mounting dimensions, showing 30cm clearance on top and bottom, and 200mm distance between mounting holes.

3.5 AC Input / Output Connection

WARNING! All wiring must be performed by qualified personnel. Make sure AC power is disconnected before connecting. All operations must comply with local laws and regulations.

  1. Install a separate AC breaker between the inverter and the AC input power source. Recommended spec for 6.5KW inverter: 40A.
  2. Remove 12mm of insulation from cable ends, shorten conductor to 10mm, and crimp into tubular terminals.
  3. Insert AC input cables (L, N, PE) according to polarity and tighten screws. Connect PE (Protective Earth, yellow-green) first. L (LINE, brown or black), N (Neutral, blue).
  4. For AC output (OUT1/OUT2), follow the same steps for L and N cables.
AC Input and Output Connection Diagram
Figure 5: Diagram showing AC IN, AC OUT1, and AC OUT2 terminal blocks and proper wiring connections for L, N, and PE.

3.6 PV Connection

WARNING! Do not connect any DC switches or AC/DC circuit breakers before completing electrical connections. Do not ground positive or negative terminals of PV modules. Exposure to sunlight can generate lethal high voltages.

  1. Install a separate DC circuit breaker between the inverter and PV modules.
  2. Remove 12mm of insulation from cable ends, shorten conductor to 10mm, and crimp into tubular terminals.
  3. Use a multi-meter to check polarities.
  4. Insert PV cables (PV+ red, PV- black) according to polarity and tighten screws.
PV Connection Diagram
Figure 6: Diagram showing PV+ and PV- terminal blocks for solar panel input connection.

3.7 Battery Connection

The inverter supports both lead-acid and lithium batteries. Ensure compatibility of the protocol for lithium batteries.

3.7.1 Lead-acid Battery Connection

User can choose proper capacity lead acid battery with a nominal voltage at 48V. Battery type should be 'AGM or FLD(flooded)'.

  1. Install a separate DC over-current protector or disconnect device (recommended 150A).
  2. Prepare 2 DT terminals (for AWG2 cables). Remove 12mm insulation, shorten conductor to 10mm, and crimp into terminals.
  3. Pass battery cables through the installation hole, ensuring correct polarity (positive to positive, negative to negative) and tighten terminal screws.
  4. Connect all battery packs as required. A minimum of 200Ah capacity battery is suggested.
Battery Connection Diagram
Figure 7: Diagram showing BAT+ and BAT- terminals for battery connection.

3.7.2 Lithium Battery Connection

If using a lithium battery, check protocol compatibility. There are two connectors on the lithium battery: RJ45 port of BMS and power cable.

  1. Implement power cable connection as per section 3.7.1.
  2. Connect the RJ45 terminal of the battery communication cable to the BMS communication port of the inverter. The communication protocol should be RS485 or CAN.
  3. Insert the other end of the RJ45 cable to the battery communication port of the lithium battery.
  4. Set the battery type to "Lib" in LCD Setting Program 17.

3.8 Smart Communication Stick Connection (Optional)

The smart communication stick (WIFI) is used for cloud platform connectivity. Insert the stick directly into the COM port on the inverter.

Wi-Fi Monitoring Setup and Port Diagram
Figure 8: Diagram showing the Wi-Fi Mode Interface connection to the inverter's COM port for monitoring via mobile app.

3.9 Final Assembly

After connecting all wiring, reinstall the bottom cover by screwing in the four retaining screws.

Video 1: A step-by-step guide on connecting the inverter to a lithium battery and commissioning the system, including wiring, communication setup, and initial settings.

4. Operation

4.1 Power ON/OFF

Once the unit is properly installed and batteries are connected, simply press the ON/OFF switch (located on the bottom right corner of the inverter) to turn on the unit.

4.2 Operation and Display Panel

The front panel of the inverter features a display screen, four indicators, and four function keys for operation and monitoring.

4.2.1 LCD Display Icons

The LCD displays various icons indicating the system status, input/output, and battery information.

Display AreaIconDescription
Battery InformationBattery iconIndicates battery status.
Battery type (AGM, FLD, USER, Li-ion)Shows the selected battery type.
CC, CV, FLOATIndicates charging stages: Constant Current, Constant Voltage, Float.
Battery voltageDisplays current battery voltage.
AC Input InformationUPS APPUPS or APP input mode. Displays as APP when set to GEN input.
PV Input InformationPV input iconIndicates PV power, voltage, current.
Output InformationOutput voltage, apparent power, active powerAlternates display every five seconds.
Load CapacityLoad capacity iconIndicates current load level.
Other InformationMute, Wifi connected, PV+Grid, PV firstIndicates system status and connectivity.

4.2.2 LCD Setting

Press and hold the ENTER button for 2 seconds to enter the Settings interface. Use UP/DOWN to navigate and ENTER to confirm. ESC to exit.

ProgramDescriptionSetting Option
01Output voltage230V (default), adjustable: 208V, 220V, 230V, 240V
02Output frequency50Hz (default), adjustable: 50Hz, 60Hz
03Output source prioritySolar first, Grid first (default), PBG priority, MKS
04Input modeAPP: Appliance (default), UPS, GEN
05Charger source priorityPNG: PV and Grid (default), OPV: Only PV, PVF: PV first
06Grid charging current60A (default), adjustable: 2-120A
07Maximum charging current100A (default), adjustable: 2-120A
14Silent mode settingOFF (default) / ON (disables buzzer sound for alarms/faults)
17Battery typeAGM (default), Flooded, Lithium (Ternary), FEL (Lithium iron), User-Defined
26Reset factory settingOFF (default) / ON (restores all settings to factory defaults)
44BMS Communication FunctionOFF (default) / Specific protocols (CVT, PYL, GRO, VOL, IRO, PAR)

4.2.3 Display Information

The LCD display information can be cycled using the "UP" or "DOWN" keys. If idle, the daily PV power generation is displayed.

LCD DisplayInformation
P1Daily power generation from solar.
P2Total power generation from solar.
P3Lithium battery voltage and current (if BMS communication is active).
P4Lithium battery temperature and SOC (if BMS communication is active).
P5Lithium battery rated capacity and remaining capacity (if BMS communication is active).
P6Lithium battery maximum charging voltage and minimum discharging voltage (if BMS communication is active).
P7Lithium battery maximum charging current and maximum discharging current (if BMS communication is active).
P8Lithium battery alarm and fault information (if BMS communication is active).
P9Inverter firmware version.

5. Maintenance

Regular maintenance ensures the longevity and optimal performance of your inverter. Always prioritize safety during maintenance procedures.

5.1 General Maintenance Guidelines

  • Before any maintenance, disconnect the inverter from all external power supplies (AC, PV, and Battery). Wait at least 5 minutes for internal capacitors to discharge.
  • Do not attempt to disassemble the unit. Refer all servicing and repairs to qualified service personnel.
  • Keep the inverter's ventilation openings clear of dust and debris to ensure proper airflow and prevent overheating.
  • Periodically check all wiring connections for tightness and signs of wear or damage.
  • Ensure the inverter is installed in a clean, dry environment, free from excessive dust, moisture, and corrosive substances.

5.2 Battery Equalization (Lead-acid Batteries Only)

The equalization function helps reverse the buildup of negative chemical effects (stratification and sulfation) in lead-acid batteries, which can reduce battery capacity. This function should NOT be activated when using lithium batteries.

To apply equalization:

  1. Enable the battery equalization function in LCD setting Program 29.
  2. Set balance mode on Program 29.
  3. Set balance voltage point on Program 30.
  4. Set balance charging time on Program 31.
  5. Set balance delay time on Program 32.
  6. Set balance interval time on Program 33.
  7. Set immediate balance mode activation on Program 34.

The controller will enter the Equalize stage when the set equalization interval is reached or when immediate activation is selected during the float stage.

6. Troubleshooting

This section provides guidance on identifying and resolving common issues indicated by fault codes or operational problems.

6.1 Fault Reference Code

If a fault occurs, the fault indicator will be constantly on, and the buzzer will sound for 10 seconds. The LCD will display a fault code. The system will attempt to restart automatically. If it fails after six attempts, it will remain in fault status. Power off the unit completely or wait 30 minutes to restart.

Fault CodeMeaningTrigger ConditionsWhat to do / Resume Conditions
1Grid soft start failedGrid soft start process starts but bus voltage does not reach set value.Restore after reaching the set voltage for 15 seconds.
2Bus over voltageBus voltage is higher than set value.Restore after reaching the set voltage for 15 seconds.
3Bus below voltageBus voltage is lower than set value.Cannot restore.
4Battery over currentBattery current is higher than set value.Cannot restore.
5System over temperaturePFC temperature is higher than set value or fan is not connected.Restore after temperature lowers and fan is connected for 15 minutes.
12Inverter short circuitInverter voltage is less than set value and current is higher than set value.Restore after reaching the set value for 15 seconds.
18PV reverse connectionPV reverse connection.Restore after connecting correctly for 15 seconds.
26BMS faultError code in BMS message.Restore after BMS fault resolved.

6.2 Alarm Reference Code

In alarm mode, the inverter does not enter fault mode; the LED red light flashes, and the LCD displays the alarm code.

Alarm CodeMeaningTrigger ConditionsResume Conditions
50Battery openBattery disconnected for more than 10 minutes.Restore after battery connected and charging for 2 minutes.
51Battery under voltageBattery voltage is lower than BAU set value.Restore after battery voltage exceeding BAU set value by 2V.
56BMS lossCommunication failure after BMS communication function is enabled.Restore after communication function disabled or communication success.
58Fan errorNo fan speed signal detected.Restore after fan speed signal detected.
60OverloadOutput load is higher than 6.5KW or battery current is higher than MDC value.Restore after load is lower than 6.5KW and battery current is lower than MDC.

6.3 Common Issues

Unable to start:

  • Check if the battery voltage sampling is functioning properly and if the battery voltage has been calibrated.
  • Use a multimeter to measure the voltage at the battery terminals. Ensure it reaches the minimum voltage of 11.5V per cell for startup.
  • Configure the battery voltage according to the machine model. Connecting the wrong battery voltage can cause capacitor explosion.

PV not charging:

  • Check if the PV input voltage is too close to the critical threshold.
  • For low voltage versions, check if the software version numbers of the main control are compatible.
  • Connecting the wrong battery voltage can damage the auxiliary power supply on the PV side, leading to a loss of power and inability to communicate with the main control.

7. Specifications

Detailed technical specifications for the Anern FGI-S6500/FGI-S5000 Hybrid Solar Inverter.

7.1 AC Input

ItemValue
Rated Input Voltage (VAC)208/220/230/240; L+N+PE
Voltage Range (VAC)90~280 (APP mode); 170~280 (UPS mode)
Frequency (Hz)50/60 (Auto Adaptive)

7.2 AC Output

ItemValue
Rated Capacity (kW)6.5 (Output Power rating will be reduced to 90% when setting the Output Voltage to 208V)
Surge Power (kVA)12
Voltage (VAC)208/220/230/240
Power Factor (PF)1
Frequency (Hz)50/60±0.1%
Switch Time (ms)10 (APP/UPS mode) / 20 (GEN mode)
WaveFormPure Sine Wave
Overload Capacity (Battery Mode)1min@ 102%~110% load; 10s@ >110% load
Max. Efficiency (Battery Mode)94%@48V

7.3 Charger (PV/AC)

ItemValue
Solar Charger TypeMPPT
Max PV Input Current/Power27A/9000W
MPPT Range@Operating Voltage (VDC)60~450
PV Start-up Voltage80Vdc
Max PV Open Circuit Voltage (VDC)500
Max PV Charge Current (A)120
Max AC Charge Current (A)120
Max. Charge Current (PV+AC) (A)120

7.4 Battery

ItemValue
Normal Voltage (VDC)48
Battery TypeLithium and Lead-acid

7.5 General Data

ItemValue
HMILCD
InterfaceRS485/CAN/RS232
MonitoringWiFi (Optional)
Ingress ProtectionIP21
Operating Temperature-10°C~60°C
Relative Humidity5%~95% (Non-condensing)
Storage Temperature-15°C~60°C
Max. Operating Altitude4000m (Derating above 1000m)

8. User Tips

Based on user feedback and common questions, here are some helpful tips:

  • Quiet Operation: Many users report that this inverter operates quietly, making it suitable for various installation environments.
  • Versatile Settings: The inverter offers a wide range of settings to adapt to different situations and system configurations. Take time to explore the LCD settings to optimize performance for your specific needs.
  • WiFi Module Recommended: For remote monitoring and enhanced control, it is highly recommended to acquire the optional WiFi module. This allows you to monitor your PV system's status from your mobile phone or a website.
  • Voltage Compatibility: This device is designed for 220V-240V (AC) output. It does not support 110V voltage. Ensure your load requirements match this specification.
  • Professional Installation: Given the complexity and high voltage involved, professional installation is strongly advised to ensure safety and proper functioning.

9. Warranty and Support

9.1 Warranty Information

This product typically comes with a two-year warranty. Please retain your purchase receipt for warranty claims. For specific warranty terms and conditions, refer to your purchase agreement or contact the seller directly.

9.2 Further Assistance

For additional support, troubleshooting, or to view the complete user manual, you can access the PDF document:

View User Manual (PDF)