Important Safety Instructions
Please save these instructions for future use!
This manual contains all safety, installation and operating instructions for the POW-LVM5K Series all-in-one solar charge inverter.
General Safety Precautions
- Non-safety voltage exists inside the all-in-one solar charge inverter. To avoid personal injury, users shall not disassemble the all-in-one solar charge inverter themselves. Contact our professional maintenance personnel if there is a need for repair.
- Do not place the all-in-one solar charge inverter within the reach of children.
- Do not install the all-in-one solar charge inverter in harsh environments such as moist, oily, flammable or explosive, or heavily dusty areas.
- The mains input and AC output are high voltage, so please do not touch the wiring terminals.
- The housing of the all-in-one solar charge inverter is hot when it is working. Do not touch it.
- Do not open the terminal protective cover when the all-in-one solar charge inverter is working.
- It is recommended to attach proper fuse or circuit breaker to the outside of the all-in-one solar charge inverter.
- Always disconnect the fuse or circuit breaker near the terminals of PV array, mains and battery before installing and adjusting the wiring of the all-in-one solar charge inverter.
- After installation, check that all wire connections are tight to avoid heat accumulation due to poor connection, which is dangerous.
- The all-in-one solar charge inverter is off-grid. It is necessary to confirm that it is the only input device for load, and it is forbidden to use it in parallel with other input AC power to avoid damage.
Product Overview
The PowMr 5KW-48V-N series is a new type of mixed solar energy storage inverter, integrating solar energy storage, municipal power charge storage, and AC sine wave output. It features DSP control and advanced control algorithms for high response speed, reliability, and industrial standards. It offers four charge modes (solar only, mains priority, solar priority, mixed charge) and two output modes (inverting and mains power bypass) to suit various application needs.
The solar charge module utilizes optimized MPPT tracking technology for real-time maximum power point tracking of the photovoltaic array. The AC-DC charge module ensures stable and reliable battery charging with wide AC voltage input and comprehensive protection. The DC-AC inverter module, based on full digital intelligent design, uses advanced SPWM technology to output pure sine wave, suitable for various AC loads.




Basic System Introduction
A complete system includes the following parts:
- Photovoltaic module: Converts light energy into direct current (DC) to charge the battery via the inverter, or directly inverts DC to alternating current (AC) to supply power to the load.
- Mains or generator: Connected at the AC input, it can supply power to the load and charge the battery. If no mains power or generator is connected, the system can still operate normally, with load power supplied by the battery and photovoltaic modules.
- Battery: Ensures normal power consumption of the system load when solar energy or mains supply is insufficient.
- Household load: Can be connected to various household and office AC loads (refrigerators, lamps, televisions, fans, air conditioners, etc.).
- Inverting and control all-in-one inverter: The energy conversion device of the whole system.
The specific system wiring mode is determined by the actual application scenario.

Production Overview Diagram

Dimension Drawing

Setup and Installation
Installation Notice
- Take care while installing the battery. When installing lead-acid liquid batteries, wear goggles. Wash any body part contacting battery acid with clear water immediately.
- Do not place any metal object beside the battery to prevent short circuits.
- Acid gas may be generated during battery charge. Ensure good ventilation around the environment.
- During cabinet installation, reserve sufficient space around the inverter for heat dissipation. Do not install the inverter and lead-acid liquid battery in the same cabinet to avoid corrosion from acid gas.
- Only batteries consistent with the inverter type can be charged.
- Loose connections and corroded wires can cause excessive heat, melting insulation, burning materials, or fire. Ensure all connectors are tightened and wires are fixed with ties.
- Conductors should be selected based on a current density no greater than 5A/mm².
- Outdoor installations must be protected from direct sunlight and rain.
- After the power switch is turned off, high voltage may still be present inside the inverter. Do not open or touch internal components until capacitors are fully discharged.
- Do not install the inverter in humid, greasy, flammable, explosive, dusty, or other severe environments.
- The polarity of the battery input must not be reversed, as this can damage the device or cause unpredictable dangers.
- AC supply input and AC output are high voltage; do not touch the wires.
- Do not touch the fan when it is working to prevent injury.
- Confirm that the inverter is the sole power supply for the load device. Do not use it in parallel with other AC power sources to avoid damage.
Select the Mount Location
Confirm the installation position and heat dissipation space. The inverter should be mounted on a wall surface.
Ensure sufficient airflow through the cooling fins. Reserve at least 200mm space at the left and right air outlets to guarantee heat loss through natural convection.

WARNING
Danger of explosion! Never install the all-in-one inverter and lead-acid liquid battery into the same sealed space or in a sealed place with probable accumulation of battery gas.
Mount the Inverter
Install the unit by screwing two screws. It's recommended to use M6 screws.
Preparation for Wiring
Before connecting all wirings, please take off the bottom cover by removing two screws.

Wiring Specification and Breaker Type
For wiring and installation, observe national and local electrical specifications.
PV Input Wiring
The minimum wire diameter for the photovoltaic array is calculated based on its short circuit current. Refer to the short circuit current value in the PV array specification. The short circuit current of the array cannot exceed the maximum input current of PV.
| Model | Wire Diameter | Max. PV input current | Circuit breaker Spec |
|---|---|---|---|
| POW-LVM5K-48V-N | 6mm²/10AWG | 22A | 2P-25A |
Note: The voltage in series shall not exceed maximum PV input open-circuit voltage.
AC Input Wiring
| Model | Wire Diameter | Max. bypass input current | Circuit breaker Spec |
|---|---|---|---|
| POW-LVM5K-48V-N | 10mm²/7AWG | 63A | 2P-63A |
Note: There is already a corresponding breaker at the input connection point of mains supply. Therefore, it is not necessary to add one more.
Battery Wiring
| Model | Wire Diameter | Rated Battery Discharge Current | Max. Charge Current | Circuit Breaker Spec |
|---|---|---|---|---|
| POW-LVM5K-48V-N | 30mm²/7AWG | 125A | 80A | 2P-200A |
AC Output Wiring
| Model | Wire Diameter | Rated Inverter AC Output current | Max. bypass output current | Circuit Breaker Spec |
|---|---|---|---|---|
| POW-LVM5K-48V-N | 10mm²/7AWG | 42A | 63A | 2P-63A |
Note: The wire diameter is only for reference. In case of long distance between photovoltaic array and all-in-one inverter or between all-in-one inverter and battery, use thicker wire to reduce voltage drop and improve system performance.
NOTICE
Above wire diameter and breaker are only for reference. Please select appropriate wire diameter and breaker based on practical condition.
AC Input/Output Wiring
- Before AC input/output wiring, disconnect the external breaker and confirm the cable thickness.
- Connect AC input wire: Connect ground lead first, then live wire (L), and neutral wire (N).
- Connect AC output wire: Connect ground lead first, then live wire (L), and neutral wire (N). The ground wire connects to the grounding screw hold through a shaped terminal.

NOTICE
Use thick ground cable as far as possible (with cable section not less than 4mm²), place the ground point to be close to the all-in-one inverter as far as possible and choose shorter ground wire to the greatest extent.
PV Input Wiring
- Before wiring, disconnect the external breaker and confirm the cable thickness.
- Correctly connect PV input wire: PV+ (positive input pole) and PV- (negative input pole).

Battery Wiring
- Before wiring, disconnect the external breaker and confirm the cable thickness. BAT wire should be connected with the machine via O-shaped terminal (recommended 6mm inside diameter). Compress the O-shaped terminal firmly to prevent excessive heating.
- Correctly connect BAT wire: BAT+ (positive battery pole) and BAT- (negative battery pole).

WARNING
- Input from mains supply, AC output, and photovoltaic array may generate high voltage. Before wiring, ensure the breaker or fuse is open.
- During wiring, pay attention to safety. Do not close the breaker or fuse. Ensure '+' and '-' poles are correctly connected. A breaker must be installed at the battery end. Before wiring, open the breaker to prevent strong electric sparks. Avoid battery short circuits.
- If the inverter is in an area with frequent thunder, install an external arrester at the PV input terminal.
Final Assembly and Startup
- After wiring, inspect all connections for correctness and tightness. Verify positive and negative input poles for battery and PV, and ensure AC input is not incorrectly connected to AC output.
- Once wiring is reliable and correct, install the terminal protection cover.
- Startup: First, close the breaker at the battery end. Press the rocker switch on the lower left side to 'ON'. The 'AC/INV' indicator light will flash, indicating normal inverter operation.
- Next, close the breakers for the photovoltaic array and mains supply.
- Finally, after AC output is normal, turn on AC loads one by one, starting with high impact current loads, to avoid protection actions from simultaneous load activation. The inverter will operate according to the set mode.
NOTICE
- If power is supplied to different AC loads, turn on loads with great impact current first, then loads with little impact current after the first load stabilizes.
- In case of abnormal operation or display, refer to the 'Troubleshooting' section.
Operating Mode
Charge Mode
- Photovoltaic priority: Mains charge starts only when PV is out of work. Maximizes solar energy use. Suitable for areas with stable power grids and expensive electricity.
- Mains supply priority: Mains supply charges the battery preferentially. PV charge starts only when mains supply is valid.
- Mixed charge: Prioritizes PV MPPT charge. Mains supply supplements if PV energy is insufficient. Stops mains charge if PV energy is sufficient. Fastest charging, suitable for unstable grids.
- Only solar: Only PV charge is used, no mains supply. Maximizes energy saving. Suitable for areas with good light conditions.
Output Mode
- Photovoltaic priority mode: PV and battery supply power to the load. Switches to mains supply when PV is invalid. Maximizes solar energy use and maintains battery charge. Suitable for stable power grids.
- Mains supply priority mode: Switches to inverter for power supply only when mains supply is invalid (backup UPS). Applicable to areas with unstable power grids.
- Inverter priority mode: Switches to mains supply only in case of battery undervoltage. Maximizes DC energy use. Applied to stable power grids.
- Mixed functions mode: When the battery is unavailable or fully charged, the load is provided by PV and commercial power, with maximum PV output.
Operation and Display Panel
The inverter features an LCD screen and 3 LED indicator lights to dynamically display system data and operation states.
Touchable Keys
| Function Key | Description |
|---|---|
| SET | Enter/exit setting menu |
| UP | Last option |
| DOWN | Next option |
| ENT | Confirm/enter option under setting menu |
LED Indicators
| Indicator light | Color | Description |
|---|---|---|
| AC/INV | Yellow | Constant on: mains supply output Flashing: inverter output |
| CHARGE | Green | Flashing: battery in charge Constant on: charge completed |
| FAULT | Red | Constant on: fault state |
Introduction to LCD Screen

LCD Icons and Functions
| Icon | Function |
|---|---|
| ⚡ | Indicating that AC input end has been connected to power grid |
| ☀ | Indicating that PV input end has been connected to solar battery panel |
| 🔋 | Indicating machine has been connected to battery (with charge level) |
| ⚡ | Indicating that inverter circuit is working. |
| BYPASS | Indicating that the machine is in mains supply bypass work mode |
| OVER LOAD | Indicating that AC output is in overload state |
| 100% / 25% | Indicating percentage of AC output load |
| Li / SLA | Indicating battery type (Lithium / Lead-acid) |
| 🔇 | Indicating that buzzer is not enabled |
| ⚠ | Indicating alarm of machine |
| ERROR | Indicating that the machine is in fault state. |
| ⚙ | Indicating that the machine is in setting mode. |
Real-time Data View Method
In the LCD main screen, press the "UP" and "DOWN" keys to view different real-time data:
| Page | Left Parameter of Screen | Middle Parameter of Screen | Right Parameter of Screen |
|---|---|---|---|
| 1 | Battery input voltage | Fault code | Output voltage |
| 2 | PV temperature | PV output KW | |
| 3 | PV input voltage | PV output current | |
| 4 | Input battery current | Output battery current | |
| 5 | Input battery KW | Output battery KW | |
| 6 | AC input frequency | AC output load frequency | |
| 7 | AC input voltage | AC output load current | |
| 8 | Input voltage | Output load KVA | |
| 9 | INV temperature | INV output load KW | |
| 10 | APP software version | Bootloader software version | |
| 11 | Model Battery Voltage Rating | Model Output Power Rating | |
| 12 | Model PV Voltage Rating | Model PV Current Rating |
Setting Parameters
To enter/exit the setting menu, press the "SET" key. Use "UP" and "DOWN" to select the parameter item code, then "ENT" to edit. Adjust values with "UP" and "DOWN", then "ENT" to confirm.
Battery Type Parameters (Lead-acid Battery)
| Parameters | Sealed lead acid battery (SLD) | Colloidal lead acid battery (GEL) | Vented lead acid battery (FLD) | User-defined (USE) |
|---|---|---|---|---|
| Overvoltage disconnection voltage | 60V | 60V | 60V | 60V |
| Equalizing charge voltage | 58.4V | 56.8V | 59.2V | 40~60V (Adjustable) |
| Boost charge voltage | 57.6V | 56.8V | 58.4V | 40~60V (Adjustable) |
| Floating charge voltage | 55.2V | 55.2V | 55.2V | 40~60V (Adjustable) |
| Undervoltage alarm voltage | 44V | 44V | 44V | 40~60V (Adjustable) |
| Low voltage disconnection voltage | 42V | 42V | 42V | 40~60V (Adjustable) |
| Discharge limit voltage | 40V | 40V | 40V | 40~60V (Adjustable) |
| Over-discharge delay time | 5s | 5s | 5s | 1~30s (Adjustable) |
| Equalizing charge duration | 120 mins | - | 120 mins | 0~600 mins (Adjustable) |
| Equalizing charge interval | 30 days | - | 30 days | 0~250 days (Adjustable) |
| Boost charge duration | 120 mins | 120 mins | 120 mins | 10~600 mins (Adjustable) |
Battery Type Parameters (Lithium Battery)
| Parameters | Ternary lithium battery (N13) | Ternary lithium battery (N14) | Lithium iron phosphate battery (L16) | Lithium iron phosphate battery (L15) | Lithium iron phosphate battery (L14) | User-defined (USE) |
|---|---|---|---|---|---|---|
| Overvoltage disconnection voltage | 60V | 60V | 60V | 60V | 60V | 60V |
| Equalizing charge voltage | - | - | - | - | - | 40~60V (Adjustable) |
| Boost charge voltage | 53.2V (Adjustable) | 57.6V (Adjustable) | 56.8V (Adjustable) | 53.2V (Adjustable) | 49.2V (Adjustable) | 40~60V (Adjustable) |
| Floating charge voltage | 53.2V (Adjustable) | 57.6V (Adjustable) | 56.8V (Adjustable) | 53.2V (Adjustable) | 49.2V (Adjustable) | 40~60V (Adjustable) |
| Undervoltage alarm voltage | 43.6V (Adjustable) | 46.8V (Adjustable) | 49.6V (Adjustable) | 46.4V (Adjustable) | 43.2V (Adjustable) | 40~60V (Adjustable) |
| Low voltage disconnection voltage | 38.8V (Adjustable) | 42V (Adjustable) | 48.8V (Adjustable) | 45.6V (Adjustable) | 42V (Adjustable) | 40~60V (Adjustable) |
| Discharge limit voltage | 36.4V | 39.2V | 46.4V | 43.6V | 40.8V | 40~60V (Adjustable) |
| Over-discharge delay time | 30s (Adjustable) | 30s (Adjustable) | 30s (Adjustable) | 30s (Adjustable) | 30s (Adjustable) | 1~30s (Adjustable) |
| Equalizing charge duration | - | - | - | - | - | 0~600mins (Adjustable) |
| Equalizing charge interval | - | - | - | - | - | 0~250days (Adjustable) |
| Boost charge duration | 120mins (Adjustable) | 120mins (Adjustable) | 120mins (Adjustable) | 120min (Adjustable) | 120mins (Adjustable) | 10~600 mins (Adjustable) |
Other Functions
Dry Node Function
This dry node can control the switch of a diesel generator to charge the battery.

RS485 Communication Function
The inverter has two RS485 communication ports (RS485-1 and RS485-2) with two functions:
- RS485 communication with lithium battery BMS (RS485-2, customizable).
- RS485-1 connects to a WiFi/GPRS communication module (developed by PowMr) for remote monitoring and control via mobile app.

USB Communication Function
This port is for USB communication with the upper computer software. Install the corresponding "USB to serial port chip CH340T driver" on your computer.

Protection Functions
| No. | Protection Function | Note |
|---|---|---|
| 1 | Current limiting protection | When the charge current of the configured PV array exceeds the rated current of PV, it will be charged at the rated current. |
| 2 | Anti-reverse charge protection at night | At night, because the battery voltage is greater than that of the PV module, the battery shall be protected against discharge through the PV module. |
| 3 | AC input over-voltage protection | When the AC voltage exceeds 140V (120V model), the AC charge will be stopped and converted to inverter for output. |
| 4 | AC input under-voltage protection | When the AC voltage is lower than 90V (120V model), the AC charge will be stopped and converted to inverter for output. |
| 5 | Battery overvoltage protection | When the battery voltage reaches the overvoltage breaking voltage point, charge from PV and AC power to the battery shall be automatically stopped to prevent the battery from being damaged due to overcharge. |
| 6 | Battery low-voltage protection | When the battery voltage reaches the low-voltage breaking voltage point, the discharge to the battery will automatically stopped to prevent the battery from damage owing to over discharge. |
| 7 | Load output short circuit protection | In case of short-circuit fault at the load output end, the output of AC voltage can be turned off immediately and then restored 1 minute later. After trying for 3 times, the output load end is still in short circuit state, it is required to eliminate the short circuit fault of the load at first, and then turn on the machine again to restore normal output. |
| 8 | Radiator overtemperature protection | In case of excessive internal temperature, the all-in-one inverter shall stop charge and discharge; after the temperature returns to normal state, the all-in-one inverter shall restore charge and discharge. |
| 9 | Overload protection | There is output within 3 minutes after overload protection. The output is turned off in case of 5 times of continuous overload until the machine is turned on again. Specific overload grade and duration are shown in the technical parameter able after the manual. |
| 10 | AC reverse flowing protection | Prevent AC power inverted from battery inverting against reverse flowing into bypass AC input. |
| 11 | Bypass overcurrent protection | Built-in AC input overcurrent protection breaker. |
Troubleshooting
| Fault | Solving Measures |
|---|---|
| No display on screen | Check whether the battery air switch or PV air switch is closed; whether the switch is in "on" state; press any key on the screen to exit from the screen sleep mode. |
| Charge battery overvoltage protection | Measure whether the battery voltage exceeds 60V, and disconnect the photovoltaic array air switch and the AC air switch. |
| Battery undervoltage protection | After the battery charge restores to be above low-voltage disconnection recovery voltage. |
| Fan fault | Check if the fan doesn't work or if it's blocked by something else. |
| Radiator overtemperature protection | When the device cools below the overtemperature recovery temperature, it shall restore to normal charge and discharge control. |
| Bypass overload protection, inverting overload protection | Decrease consumer; Restart all-in-one inverter and the load output is restored. |
| Inverting short-circuit protection | Carefully check load connection condition, clear short-circuit fault point; After power on again, the load output is restored. |
| PV overvoltage | Check whether PV input voltage exceeds maximum allowable input voltage with a multimeter. |
| No connection alarm of battery | Check whether the battery is not disconnected or whether the breaker at the battery side is not closed. |
Meaning of Fault Code
| Fault Code | Fault Name | Affecting output or not | Note |
|---|---|---|---|
| 【01】 | BatVoltLow | Yes | Battery undervoltage alarm |
| 【02】 | BatOverCurrSw | Yes | Average overcurrent software protection for battery discharge |
| 【03】 | BatOpen | Yes | No connection alarm of battery |
| 【04】 | BatLowEod | Yes | Stop discharge alarm for battery undervoltage |
| 【05】 | BatOverCurrHw | Yes | Battery overcurrent hardware protection |
| 【06】 | BatOverVolt | Yes | Charge overvoltage protection |
| 【07】 | BusOverVoltHw | Yes | Bus overvoltage hardware protection |
| 【08】 | BusOverVoltSw | Yes | Bus overvoltage software protection |
| 【09】 | PV VoltHigh | No | PV overvoltage protection |
| 【10】 | PV OCSw | No | PV overcurrent software protection |
| 【11】 | PV OCHw | No | PV overcurrent hardware protection |
| 【12】 | bLineLoss | No | AC power failure |
| 【13】 | OverloadBypass | Yes | Bypass overload protection |
| 【14】 | OverloadInverter | Yes | Inverter overload protection |
| 【15】 | AcOverCurrHw | Yes | Inverter overcurrent hardware protection |
| 【17】 | InvShort | Yes | Inverter short-circuit protection |
| 【19】 | OverTemperMppt | No | PV radiator overtemperature protection |
| 【20】 | OverTemperInv | Yes | Overtemperature protection of inverter radiator |
| 【21】 | FanFail | Yes | Fan fault |
| 【22】 | EEPROM | Yes | Memory fault |
| 【23】 | ModelNumErr | Yes | Inaccurate model setting |
| 【26】 | RlyShort | Yes | Inverted AC Output Backfills to Bypass AC |
| 【29】 | BusVoltLow | Yes | Bus undervoltage protection |
| 【32】 | BatCapacityLowStop | Yes | Inverter stops when battery capacity is low (setting BMS to enable validity) |
| 【34】 | CanCommFault | Yes | CAN communication fault in parallel operation |
| 【58】 | BMS communication error | No | Check whether the communication line is connected correctly and whether [33] is set to the corresponding lithium battery communication protocol |
| 【59】 | BMS alarm | No | Check the BMS fault type and troubleshoot battery problems |
| 【60】 | BMS battery low temperature alarm | No | BMS alarm battery low temperature |
| 【61】 | BMS battery over temperature alarm | No | BMS alarm battery over temperature |
| 【62】 | BMS battery over current alarm | No | BMS alarm battery over current. |
| 【63】 | BMS battery undervoltage alarm | No | BMS alarm low battery. |
| 【64】 | BMS battery over voltage alarm | No | BMS alarm battery over voltage |
System Maintenance
To maintain optimum and permanent operation performance, check the following items semiannually:
- Confirm that the air flow around the inverter is not blocked. Remove any dirt or debris from the radiator.
- Check whether the insulation of all exposed wires is damaged due to sun exposure, friction, dry rot, insect or rat damage. Repair or replace wires if necessary.
- Verify that the indication and display are consistent with device operation. Pay attention to any fault or error display and take corrective measures.
- Check all terminals for corrosion, insulation damage, high temperature or burning/discoloration signs, and tighten terminal screws.
- Check for dirt, nesting insects, and corrosion. Clean as required.
- If the arrester has failed, replace it to protect the inverter and other devices against lightning damage.
WARNING
Danger of electric shock! To perform operations, ensure all power supplies to the inverter are disconnected and all capacitors are discharged. Then, inspection or operation can be performed.
Damages Not Covered
The manufacturer is not responsible for the following damages:
- Damage caused by improper use or use in inappropriate places.
- Open-circuit voltage of photovoltaic module exceeds maximum allowable voltage.
- Damage caused by operation ambient temperature beyond the limited range.
- Personally taking apart and maintaining the inverter.
- Damage caused by force majeure (e.g., transportation or handling).
Technical Specifications
AC Mode
| Parameter | Value |
|---|---|
| Rated input voltage | 110/120Vac |
| Input voltage range | (90Vac-140Vac) |
| Frequency | 50Hz/60Hz (auto-sensing) |
| Frequency range | 47±0.3Hz ~ 55±0.3Hz (50Hz); 57±0.3Hz ~ 65±0.3Hz (60Hz) |
| Overload/short-circuit protection | Breaker |
| Efficiency | >95% |
| Conversion time (Bypass and inverting) | 10ms (Typical value) |
| AC reverse flowing protection | Yes |
| Maximum bypass overload current | 63A |
Inverting Mode
| Parameter | Value |
|---|---|
| Output voltage waveform | Pure sine wave |
| Rated output power (VA) | 5000 |
| Rated output power (W) | 5000 |
| Power factor | 1 |
| Rated output voltage (Vac) | 120Vac |
| Output voltage error | ± 5% |
| Output frequency range (Hz) | 50Hz ± 0.3Hz; 60Hz ± 0.3Hz |
| Efficiency | >90% |
| Overload protection | (102%<load<110%) ±10%: reporting error and turn off the output after 5 minutes; (110%<load<125%) ±10%: reporting error and turn off the output after 10 seconds; Load>125% ±10%: reporting error and turn off the output after 5 seconds; |
AC Charge
| Parameter | Value |
|---|---|
| Battery type | Lead acid or lithium battery |
| Maximum charge current | 40A |
| Charge current error | ± 5Adc |
| Charge voltage range | 40-60Vdc |
| Short-circuit protection | Breaker and blown fuse |
| Breaker specification | 63A |
| Overcharge protection | Turn off charge after 1min alarm |
Solar Charge
| Parameter | Value |
|---|---|
| Maximum PV open-circuit voltage | 500Vdc |
| PV operation voltage range | 120-500Vdc |
| MPPT voltage range | 120-450Vdc |
| Battery voltage range | 40-60Vdc |
| Maximum input power | 5500W |
| Charge current range of solar energy (settable) | 0-80A |
| Charge short-circuit protection | Blown fuse |
| Wiring protection | Inverse wiring protection |
General Specifications
| Parameter | Value |
|---|---|
| Peak power | 10000VA |
| Loaded motor capacity | 4HP |
| Output short-circuit protection | Breaker |
| Specification of bypass breaker | 63A |
| Rated battery input voltage | 48V (minimum start voltage 44V) |
| Battery voltage range | 40.0Vdc~60Vdc ± 0.6Vdc (settable LCD screen) |
| Power saving mode | Load ≤50W |
| Operation temperature range | -10°C ~ 55°C |
| Storage temperature range | -25°C ~ 60°C |
| Humidity range | 5% to 95% (three-proof paint protection) |
| Noise | ≤60dB |
| Thermal dissipation | Forced cooling with adjustable air speed |
| Communication interface | USB/RS485 (WiFi/GPRS)/dry node control |
| Dimension (L*W*D) | 426mm*322mm*126mm |
| Weight (kg) | 11.5 |
Authentication Specification
| Parameter | Value |
|---|---|
| Specification authentication | CE(IEC62109)/CETL(UL 1741 C22.2 NO.107.1)/FCC/SAA |
| EMC authentication grade | EN61000 |
User Tips
- Battery-less Operation: This model can work without batteries in 'Mixed functions mode' where the load is provided by PV and commercial power.
- Output Voltage: The inverter provides 110/120Vac output. It does not support 220V output.
- Weight: The unit weighs approximately 11.5 kg.
Warranty and Support
Warranty
The PowMr 5KW 48V Hybrid Solar Inverter comes with an 18-month warranty.
Contact Information