1. Introduction
This manual describes the assembly, installation, operation, and troubleshooting of the Daxtromn 3.8KW 48V Hybrid Solar Inverter. Please read this manual carefully before installation and operation. Keep this manual for future reference.
This unit is a multi-function inverter/charger, combining the functions of an inverter, MPPT solar charger, and battery charger to offer uninterruptible power support in a portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation for settings such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.
1.1. Key Features
- Pure sine wave inverter output.
- Programmable supply priority for PV, battery, or Grid.
- High PV input voltage range (55~450VDC).
- Built-in Max 80A MPPT solar charge controller.
- Compatible with lithium-ion batteries.
- Supports BMS communication with lithium batteries.
- Smart battery charge design to optimize battery life.
- Overload, high temperature, and inverter output short circuit protection.
- Cold start function.
- Intelligent fan speed adjustment.
- WIFI support (optional, purchased separately).
1.2. Basic System Architecture
The inverter/charger can power various appliances in home or office environments, including motor-type appliances such as tube lights, fans, refrigerators, and air conditioners. A complete running system typically includes:
- Generator or Utility grid.
- PV modules (solar panels) (optional).
- External Battery Packs (charging voltage adjustable).
2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION: To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION: Only qualified personnel can install this device with a battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow the required specifications to select the appropriate cable size. It is very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for details.
- GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, send this inverter/charger back to your local dealer or service center for maintenance.
3. Product Overview
- LCD display
- Status indicator
- Charging indicator
- Fault indicator
- Function buttons (ESC, UP, DOWN, ENTER)
- Power on/off switch
- AC input terminals
- AC output terminals
- PV input terminals
- Battery input terminals
- RS-232/RS485 communication port
- Safety (Earth) ground terminal
4. Installation
4.1. Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items:
- Inverter Unit x 1
- User manual x 1
4.2. Preparation
Before connecting all wirings, please take off the bottom cover by removing the two screws as shown in the manual's diagrams.
4.3. Mounting the Unit
Consider the following points when selecting where to install the inverter:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level to allow the LCD display to be read at all times.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Be sure to keep other objects and surfaces clear as shown in the diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.
CAUTION: Suitable for mounting on concrete or other non-combustible surface only.
4.4. Battery Connection
CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between the battery and inverter. It is still required to have over-current protection installed.
WARNING! All wiring must be performed by qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce the risk of injury, use the proper recommended cable and terminal size.
Recommended battery cable and terminal size for 3.8KW 48V model:
- Wire Size: 1*4AWG
- Cable (mm²): 22
- Ring Terminal Dimensions: D (mm) 6.4, L (mm) 33.2
- Torque Value: 2 Nm
Steps for Battery Connection:
- Assemble battery ring terminal based on recommended battery cable and terminal size.
- Connect all battery packs as required (e.g., for a 48V system, connect four 12V batteries in series).
- Insert the ring terminal of the battery cable flatly into the battery connector of the inverter and ensure the bolts are tightened with a torque of 2-3 Nm. Make sure the polarity at both the battery and the inverter/charger is correctly connected, and ring terminals are tightly screwed to the battery terminals.
WARNING: Shock Hazard! Installation must be performed with care due to high battery voltage in series.
CAUTION: Do not place anything between the flat part of the inverter terminal and the ring terminal. Otherwise, overheating may occur.
CAUTION: Do not apply anti-oxidant substance on the terminals before terminals are connected tightly.
CAUTION: Before making the final DC connection or closing the DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
4.5. AC Input/Output Connection
CAUTION: Before connecting to an AC input power source, please install a separate AC breaker between the inverter and the AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from overcurrent of AC input. The recommended spec of AC breaker for 3.8KW is 32A.
CAUTION: There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce the risk of injury, use the proper recommended cable size.
Suggested cable requirement for AC wires for 3.8KW:
- Gauge: 12 AWG
- Torque Value: 1.2~1.6 Nm
Steps for AC Input/Output Connection:
- Before making AC input/output connection, be sure to open the DC protector or disconnector first.
- Remove insulation sleeve 10mm for six conductors. Shorten phase L and neutral conductor N by 3mm.
- Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor (⏚) first.
- Then, insert AC output wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor (⏚) first.
- Make sure the wires are securely connected.
WARNING: Be sure that the AC power source is disconnected before attempting to hardwire it to the unit.
CAUTION: Important! Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are worked in parallel operation.
CAUTION: Appliances such as air conditioners require at least 2-3 minutes to restart because it's required to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this, check the manufacturer of the air conditioner for a time-delay function before installation. Otherwise, this inverter/charger may trigger an overload fault and cut off output to protect your appliance, but internal damage to the air conditioner can still occur.
4.6. PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between the inverter and PV modules.
WARNING! All wiring must be performed by qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce the risk of injury, use the proper recommended cable size.
Suggested cable requirement for PV wires for 3.8KW/6.2KW:
- Wire Size: 1 x 12AWG
- Cable (mm²): 4
- Torque Value: 1.2 Nm
PV Module Selection:
When selecting proper PV modules, consider the following parameters:
- Open circuit Voltage (Voc) of PV modules should not exceed the max. PV array open circuit voltage of the inverter (450Vdc).
- Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.
For the SP-4200-48V model, the PV Array MPPT Voltage Range is 55-450Vdc.
Steps for PV Module Connection:
- Remove insulation sleeve 10 mm for positive and negative conductors.
- Check the correct polarity of the connection cable from PV modules and PV input connectors. Then, connect the positive pole (+) of the connection cable to the positive pole (+) of the PV input connector. Connect the negative pole (-) of the connection cable to the negative pole (-) of the PV input connector.
- Make sure the wires are securely connected.
4.7. Final Assembly
After connecting all wirings, please put the bottom cover back by screwing the two screws as shown in the manual's diagrams.
5. Operation
5.1. Power ON/OFF
Once the unit has been properly installed and the batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.
5.2. Operation and Display Panel
The operation and display panel is on the front of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.
LED Indicators:
- AC/INV (Green): Solid On (Output powered by utility in Line mode), Flashing (Output powered by battery or PV in battery mode).
- CHG (Green): Solid On (Battery is fully charged), Flashing (Battery is charging).
- FAULT (Red): Solid On (Fault occurs in the inverter), Flashing (Warning condition occurs in the inverter).
Function Keys:
- ESC: To exit setting mode.
- UP: To go to the previous selection.
- DOWN: To go to the next selection.
- ENTER: To confirm the selection in setting mode or enter setting mode.
5.3. LCD Display Icons
The LCD provides detailed information about the inverter's status. Key icons include:
- AC Icon: Indicates AC input.
- PV Icon: Indicates PV input.
- INPUT/BATT/TEMP/OUTPUT/LOAD: Displays input voltage, frequency, PV voltage, battery voltage, charger current, output voltage, output frequency, load percentage, load in VA, load in Watt, and discharging current.
- Battery Level Indicator: Shows battery level (0-24%, 25-49%, 50-74%, 75-100%) and charging status.
- OVERLOAD Icon: Indicates overload.
- BYPASS Icon: Indicates load is supplied by utility power.
- Mute Icon: Indicates unit alarm is disabled.
5.4. LCD Settings
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Use the UP or DOWN buttons to select setting programs, then press ENTER to confirm or ESC to exit.
Some key programmable settings include:
- Program 01: Output source priority (Solar first, SBU priority, Utility first).
- Program 02: Maximum charging current (10A to 110A).
- Program 03: AC input voltage range (Appliances or UPS).
- Program 04: Power saving mode enable/disable.
- Program 05: Battery type (AGM, Flooded, User-Defined).
- Program 06: Auto restart when overload occurs.
- Program 07: Auto restart when over temperature occurs.
- Program 08: Output voltage (220V, 230V, 240V).
- Program 09: Output frequency (50Hz, 60Hz).
- Program 11: Maximum utility charging current (10A to 80A).
- Program 12: Setting voltage point back to utility source when selecting "SBU priority" (various voltage options for 24V and 48V models).
- Program 13: Setting voltage point back to battery mode when selecting "SBU priority" (various voltage options for 24V and 48V models).
- Program 16: Charger source priority (Solar first, Solar and Utility, Only Solar).
- Program 18: Alarm control (on/off).
- Program 19: Auto return to default display screen.
- Program 20: Backlight control (on/off).
- Program 22: Beeps while primary source is interrupted (alarm on/off).
- Program 23: Overload bypass (enable/disable).
- Program 25: Record Fault code (enable/disable).
- Program 26: Bulk charging voltage (C.V voltage).
- Program 27: Floating charging voltage.
- Program 29: Low DC cut-off voltage.
- Program 31: Solar power balance (enable/disable).
- Program 33: Battery equalization (enable/disable).
- Program 34: Battery equalization voltage.
- Program 35: Battery equalized time.
- Program 36: Battery equalized timeout.
- Program 37: Equalization interval.
- Program 39: Equalization activated immediately.
5.5. Operating Mode Description
The inverter operates in various modes depending on input availability and settings:
- Standby Mode / Power Saving Mode: Inverter is not yet on but can charge batteries. No output is supplied, but batteries can be charged. If power saving mode is enabled, the inverter output will be off when the connected load is very low.
- Fault Mode: Errors caused by internal circuit issues or external reasons like over temperature or output short circuit.
- Line Mode: The unit provides output power from the mains (utility/generator) and also charges the battery.
- Battery Mode: The unit provides output power from the battery and/or PV power.
5.6. Battery Equalization Description
The equalization function helps reverse the buildup of negative chemical effects like stratification and removes sulfate crystals from battery plates, which can reduce battery capacity. It is recommended to equalize the battery periodically.
How to Apply Equalization Function:
- Enable battery equalization function in monitoring LCD setting program 33.
- Set the equalization interval in program 34, or activate equalization immediately in program 39.
When to Equalize:
In the float stage, when the setting equalization interval is reached, or equalization is activated immediately, the controller will enter the Equalize stage.
Equalize Charging Time and Timeout:
In the Equalize stage, the controller supplies power to charge the battery until the battery voltage reaches the equalization voltage. Constant-voltage regulation is then applied. The battery remains in this stage until the set equalized time is reached. If the battery voltage does not rise to the equalization point within the equalized time, the controller extends the time until it does. If the voltage is still low after the equalized timeout, the controller stops equalization and returns to the float stage.
6. Troubleshooting
Refer to the table below for common problems and their solutions. If errors persist, contact qualified service personnel.
| Problem | LCD/LED/Buzzer Indication | Explanation / Possible Cause | What to do |
|---|---|---|---|
| Unit shuts down automatically during startup process. | LCD/LEDs and buzzer active for 3 seconds, then off. | Battery voltage is too low (<1.91V/Cell) | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | No indication. | 1. Battery voltage is too low (<1.4V/Cell). 2. Battery polarity is connected reversed. | 1. Check if batteries and wiring are connected. 2. Re-charge battery. 3. Replace battery. |
| Input voltage displayed as 0 on LCD, green LED flashing. | Input protector is tripped. | Check if AC breaker is tripped and AC wiring is connected. | |
| Mains exist but unit works in battery mode. | Green LED is flashing. | Insufficient quality of AC power (Shore or Generator). | 1. Check if AC wires are too thin/long. 2. Check generator (if applied) or input voltage range setting. |
| Green LED is flashing. | "Solar First" set as priority of output source. | Change output source priority to Utility first. | |
| When unit is turned on, internal relay switches on and off repeatedly. | LCD display and LEDs are flashing. | Battery is disconnected. | Check if battery wires are connected. |
| Buzzer beeps continuously and red LED lights up. | Fault code 07 | Overload error. Inverter overloaded 110% and time is up. | Reduce connected load by switching off equipment. |
| Fault code 05 | Output short circuited. Temperature of internal converter component over 120°C. | Check if wiring is connected and remove abnormal load. Check air flow/ambient temperature. | |
| Fault code 02 | Internal temperature of inverter component over 100°C. | Check air flow/ambient temperature. | |
| Fault code 03 | Battery is over-charged. | Return to repair center. | |
| Fault code 01 | The battery voltage is too high. Fan fault. | Check if spec and quantity of batteries meet requirements. Replace the fan. | |
| Fault code 06/58 | Output abnormal (Inverter voltage below 190Vac or higher than 260Vac). | 1. Reduce connected load. 2. Return to repair center. | |
| Fault code 08/09/53/57 | Internal components failed. | Return to repair center. | |
| Fault code 51 | Over current or surge. | Restart unit. If error happens again, return to repair center. | |
| Fault code 52 | Bus voltage is too low. | Restart unit. If error happens again, return to repair center. | |
| Fault code 55 | Output voltage is unbalanced. | Restart unit. If error happens again, return to repair center. | |
| Fault code 56 | Battery is not connected well or fuse is burnt. | If battery is connected, return to repair center. |
6.1. Warning Indicator
The inverter provides warning indicators for various events:
- 01: Fan is locked when inverter is on (Beep three times every second).
- 03: Battery is over-charged (Beep once every second).
- 04: Low battery (Beep once every second).
- 07: Overload (Beep once every 0.5 second).
- 10: Output power derating (Beep twice every 3 seconds).
- 12: Solar charger stops due to low battery.
- 13: Solar charger stops due to high PV voltage.
- 14: Solar charger stops due to overload.
7. Specifications
Detailed technical specifications for the Daxtromn 3.8KW 48V Hybrid Solar Inverter (Model SP-4200-48V).
7.1. Line Mode Specifications (SP-3800/4200-48V)
| Parameter | Specification |
|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) |
| Nominal Input Voltage | 230Vac |
| Low Loss Voltage | 170Vac±7V (UPS); 90Vac±7V (Appliances) |
| Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) |
| High Loss Voltage | 280Vac±7V |
| High Loss Return Voltage | 270Vac±7V |
| Max AC Input Voltage | 300Vac |
| Nominal Input Frequency | 50Hz / 60Hz (Auto detection) |
| Low Loss Frequency | 40±1Hz |
| Low Loss Return Frequency | 42±1Hz |
| High Loss Frequency | 65±1Hz |
| High Loss Return Frequency | 63±1Hz |
| Output Short Circuit Protection | Line mode: Circuit Breaker; Battery mode: Electronic Circuits |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) |
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) |
7.2. Inverter Mode Specifications (SP-3800/4200-48V)
| Parameter | Specification |
|---|---|
| Rated Output Power | 4.2KVA/3.8KW |
| Output Voltage Waveform | Pure Sine Wave |
| Output Voltage Regulation | 230Vac±5% |
| Output Frequency | 60Hz or 50Hz |
| Peak Efficiency | 94% |
| Overload Protection | 5s@≥150% load; 10s@110%~150% load |
| Surge Capacity | 2* rated power for 5 seconds |
| Nominal DC Input Voltage | 48Vdc |
| Cold Start Voltage | 46.0Vdc |
| Low DC Warning Voltage (<20% load) | 44.0Vdc |
| Low DC Warning Voltage (20%≤load<50%) | 42.8Vdc |
| Low DC Warning Voltage (≥50% load) | 40.4Vdc |
| Low DC Warning Return Voltage (<20% load) | 46.0Vdc |
| Low DC Warning Return Voltage (20%≤load<50%) | 44.8Vdc |
| Low DC Warning Return Voltage (≥50% load) | 42.4Vdc |
| Low DC Cut-off Voltage (<20% load) | 42.0Vdc |
| Low DC Cut-off Voltage (20%≤load<50%) | 40.8Vdc |
| Low DC Cut-off Voltage (≥50% load) | 38.4Vdc |
| High DC Recovery Voltage | 58Vdc |
| High DC Cut-off Voltage | 62Vdc |
| No Load Power Consumption | <50W |
| Saving Mode Power Consumption | <15W |
7.3. Charge Mode Specifications (SP-3800/4200-48V)
| Parameter | Utility Charging Mode | Solar Charging Mode |
|---|---|---|
| Charging Current (UPS) @ Nominal Input Voltage | 80A | N/A |
| Bulk Charging Voltage (Flooded Battery) | 58.4V | N/A |
| Bulk Charging Voltage (AGM / Gel Battery) | 56.4V | N/A |
| Floating Charging Voltage | 54Vdc | N/A |
| Charging Algorithm | 3-Step | 3-Step |
| Rated Power | N/A | 6000W |
| PV Charge Current | N/A | 80A |
| Efficiency | N/A | 98.0% max. |
| Max. PV Array Open Circuit Voltage | N/A | 450Vdc |
| PV Array MPPT Voltage Range | N/A | 55-450Vdc |
| Standby Power Consumption | N/A | 2W |
| Battery Voltage Accuracy | N/A | ±0.3% |
| PV Voltage Accuracy | N/A | ±2V |
7.4. General Specifications (SP-3800/4200-48V)
| Parameter | Specification |
|---|---|
| Safety Certification | CE |
| Operating Temperature Range | 0°C to 55°C |
| Storage temperature | -15°C~ 60°C |
| Dimension (D*W*H), mm | 423*290*105(mm) |
| Net Weight, kg | 6.9KG |
For a comprehensive list of specifications across all models (SP-2200 to SP-7000), please refer to the detailed specifications table:
8. Maintenance
Regular maintenance ensures the longevity and optimal performance of your Daxtromn Hybrid Solar Inverter. Always ensure the unit is powered off and all AC and DC connections are disconnected before performing any maintenance or cleaning tasks.
- Cleaning: Periodically clean the exterior of the inverter to prevent dust buildup, especially around ventilation openings, to ensure proper heat dissipation.
- Connection Checks: Regularly inspect all wiring connections (battery, AC input/output, PV input) for tightness and signs of corrosion. Loose connections can lead to overheating and system malfunctions.
- Battery Health: Monitor battery voltage and perform equalization as described in Section 5.6 to maintain battery health and extend lifespan.
- Environment: Ensure the installation environment remains within the specified operating temperature and humidity ranges to prevent damage to the unit.
9. Warranty and Support
The Daxtromn 3.8KW 48V Hybrid Solar Inverter comes with a 1-year warranty from the date of purchase.
For technical support, service, or warranty claims, please contact your authorized Daxtromn dealer or the service center where you purchased the product. Ensure you have your product model number (SP-4200-48V) and serial number available when contacting support.
For further detailed information, you can refer to the official user manual PDF: View User Manual (PDF)
10. User Tips
- Battery Requirement: This inverter requires external batteries to operate. It cannot function without them. Ensure you use a 48V battery bank.
- Off-Grid Use Only: This is an off-grid inverter and is not designed for grid-tied applications. Do not attempt to connect it directly to the utility grid in a grid-tied configuration.
- No Parallel Operation: This model does not support parallel connection for increased power output.
- Optional Wi-Fi Module: For remote monitoring and control, a Wi-Fi module is available but must be purchased separately.
- Check Connections Carefully: Always double-check all wiring connections, especially polarity for batteries and PV, to prevent damage and ensure safe operation.
- Monitor Load: Be mindful of the total load connected to the inverter to avoid overloads, which can trigger fault conditions and potentially damage appliances.