1. About This Manual
1.1 Purpose
This manual describes the assembly, installation, operation, and troubleshooting of your Daxtromn Hybrid Solar Inverter. Please read this manual carefully before installations and operations, and keep it for future reference.
1.2 Scope
This manual provides safety and installation guidelines, as well as information on tools and wiring required for the inverter.
2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION: To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION: Only qualified personnel can install this device with a battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow the required specifications to select the appropriate cable size. It is very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short-circuit batteries or other electrical parts, which could cause an explosion.
- Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Refer to the INSTALLATION section of this manual for details.
- One piece of 150A fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input to be short-circuited. Do NOT connect to the mains when DC input short circuits.
- Warning: Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to a local dealer or service center for maintenance.
3. Product Overview
The Daxtromn Hybrid Solar Inverter is a multi-function inverter/charger, combining the functions of an inverter, solar charger, and battery charger to offer uninterruptible power support in a compact size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation for settings such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.
3.1 Features
- Pure sine wave output.
- Configurable input voltage range for home appliances and personal computers via LCD setting.
- Configurable battery charging current based on applications via LCD setting.
- Configurable AC/Solar Charger priority via LCD setting.
- Compatible with mains voltage or generator power.
- Auto restart while AC is recovering.
- Overload/Over temperature/short circuit protection.
- Smart battery charger design for optimized battery performance.
- Cold start function.
- Lithium battery activation function by PV or Utility (EGH models).
- Compatible with LiFePO4 battery via RS485.
- Capable to work without battery.
- Detachable dust cover for harsh environments.
- Built-in Wi-Fi remote monitoring (optional).
- Smart Timer Charge/Discharge (JGH-6.2KW).
- Dual MPPT (EGH-11KW).
3.2 Basic System Architecture
The inverter can power all kinds of appliances in home or environment, including motor-type appliances such as tube lights, fans, refrigerators, and air conditioners.

3.3 Product Components and Display Panel

Front Panel & LCD Display:
- LCD Display
- Status Indicator
- Charging Indicator
- Fault Indicator
- ESC Button
- Up Button
- Down Button
- Enter Button
Back Panel (EGH-11KW/4.2KW):
- Power ON/OFF Switch
- Battery negative/positive outlet hole
- RS232 Communication Port (RJ45)
- RS485 Communication Port (RJ45)
- Dry Contact Port
- PV1 input
- PV2 input
- AC input
- AC output
- Grounding Point

Back Panel (JGH-6.2KW):
- RS232 Communication Port
- BMS/RS485 Communication Port
- CT Signal Port
- Power ON/OFF Switch
- Output Ground Wire
- AC Input
- AC Output
- Battery Terminal Positive
- Battery Terminal Negative
- PV Input
4. Installation & Setup
4.1 Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items:
- Inverter unit x 1
- User manual x 1
4.2 Preparation
Before connecting any cables, remove the bottom cover by removing two screws.
4.3 Mounting the Unit
Consider the following points before selecting where to install:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level to allow the LCD display to be read at all times.
- For proper air circulation to dissipate heat, allow a clearance of approximately 20 cm to the sides and 50 cm above and below the unit.
- The ambient temperature should be between -10°C and 50°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Be sure to keep other objects and surfaces clear to guarantee sufficient heat dissipation and to have enough space for removing wires.
CAUTION: Suitable for mounting on concrete or other non-combustible surfaces only.
Install the unit by screwing three M6*80mm expansion bolts into the wall.
4.4 Battery Connection
CAUTION: For safety operation and regulation compliance, it is requested to install a separate DC over-current protector or disconnect device between the battery and inverter. It may not be required to have a disconnect device in some applications, however, it is still requested to have over-current protection installed. Please refer to the typical amperage in the table below for the required fuse or breaker size.
WARNING: All wiring must be performed by qualified personnel. It is very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce the risk of injury, please use the proper recommended cable and terminal size.
Recommended Battery Cable and Terminal Size:
| Rated Capacity | Typical Amperage | Battery Capacity | Wire Size | Cable (mm²) | Ring Terminal D (mm) | Ring Terminal L (mm) | Torque Value |
|---|---|---|---|---|---|---|---|
| 3.6KVA | 165A | 200AH | 2*4AWG | 25 | 8.4 | 33.2 | 5Nm |
| 6.2KVA | 124A | 200AH | 1*2AWG / 2*4AWG | 38 / 25 | 8.4 | 39.2 / 33.2 | 5Nm |
| 11KVA | 228A | 250AH | 1*3/0AWG | 85 | 8.4 | 54 | 5Nm |
Battery Connection Steps:
- Assemble battery ring terminals based on the recommended battery cable and terminal size.
- Insert the battery wires flatly into the battery connectors of the inverter and make sure the bolts are tightened with a torque of 2 Nm in a clockwise direction. Ensure polarity at both the battery and the inverter/charger is correctly connected, and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.
4.5 AC Input/Output Connection
CAUTION: Before connecting to an AC input power source, please install a separate AC breaker between the inverter and AC input power source. This will ensure the inverter can be disconnected during maintenance and fully protected from overcurrent of AC input. The recommended spec of breaker is 32A for 24V system and 63A for 48V system.
CAUTION: There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.
WARNING: All wiring must be performed by qualified personnel. It is very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce the risk of injury, please use the proper recommended cable size.
Suggested Cable Requirement for AC Wires:
| Rated Capacity | Gauge | Torque Value |
|---|---|---|
| 3.6KVA | 12AWG | 1.2~1.6Nm |
| 6.2KVA | 10AWG | 1.4~1.6Nm |
| 11KVA | 8AWG | 1.4~1.6Nm |
AC Input/Output Connection Steps:
- Before making AC input/output connection, be sure to open the DC protector or disconnector first.
- Remove insulation sleeve 10mm for six conductors. Shorten phase L and neutral conductor N by 3mm.
- Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor (yellow-green) first.
- Ensure all wires are securely connected.
4.6 PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between the inverter and PV modules.
WARNING: All wiring must be performed by qualified personnel. It is very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce the risk of injury, please use the proper recommended cable size.
Recommended PV Cable Size:
| Typical Amperage | Gauge | Torque Value |
|---|---|---|
| 30A | 12AWG | 1.4~1.6Nm |
PV Module Selection: When choosing the right PV module, be sure to first consider the following requirements:
- The open circuit voltage (Voc) of the PV modules does not exceed the maximum PV array open circuit voltage of the inverter.
- The maximum supply voltage of the PV modules should be close to the optimal PV access voltage range of the inverter for best performance.
- If one PV module cannot meet this requirement, it is necessary to connect multiple PV modules in series.
PV Module Wire Connection Steps:
- Remove insulation sleeve 10 mm for positive and negative conductors.
- Suggest putting bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Fix wire cover to the inverter with supplied screws.
- Check the correct polarity of wires from PV modules and PV input connectors. Connect the positive pole (+) of the connection wire to the positive pole (+) of the PV input connector. Connect the negative pole (-) of the connection wire to the negative pole (-) of the PV input connector. Screw two wires tightly in a clockwise direction. Recommended tool: 4mm blade screwdriver.
4.7 Final Assembly
After connecting all wirings, please put the bottom cover back by screwing the two screws.
5. Operation
5.1 Power ON/OFF
Once the unit has been properly installed and the batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.
Steps to Start Up:
- Connect the battery that meets the requirements (battery voltage needs to be beyond 23V) or AC (AC needs to confirm the suitable input range depending on the output mode), then you can start up the inverter.
- Mains Power On: Connect to normal AC power, press the switch, the system will automatically turn on. If you set AC output power priority, after waiting for a period of time, the panel will display AC mode, indicating successful turn-on, and then enter AC mode.
- Battery Boot: Connect to battery, press the power-on button to establish a working power source. The system will automatically turn on, after waiting for a period of time, the panel will display battery mode, indicating successful turn-on, and then enter battery mode.
Shutdown Steps: When the system is in battery mode or AC mode output, press the switch again, then the system will be turned off.
5.2 Operation and Display Panel
The operation and display panel, shown in the product overview, is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.
LED Indicator Status:
| Indicator | Color | Status | Message |
|---|---|---|---|
| AC/INV | Green | Solid On | Output is powered by utility in Line mode. |
| Flashing | Output is powered by battery or PV in battery mode. | ||
| CHG | Yellow | Solid On | Battery is fully charged. |
| Flashing | Battery is charging. | ||
| FAULT | Red | Solid On | Fault occurs in the inverter. |
| Flashing | Warning condition occurs in the inverter. |
Function Keys:
| Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
5.3 LCD Setting
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Press the "UP" or "DOWN" button to select setting programs. Then, press "ENTER" to confirm the selection or the ESC button to exit.
Key settings include:
- Output Source Priority: Configure how the inverter prioritizes power sources (Solar, Utility, Battery). Options include Solar First, SBU (Solar-Battery-Utility), SUB (Solar-Utility-Battery), SUF (Solar-Utility-Feed to Grid), PEC (Power Export Control).
- Max Charging Current: Set the total charging current for solar and utility chargers.
- AC Input Voltage Range: Select between Appliances (wide range) or UPS (narrower range for sensitive loads).
- Battery Type: Select the type of battery connected (Flooded, AGM, User-Defined, Lithium protocols).
- Reset Factory Setting: Restore all settings to default.
- Low DC Cut-off Voltage: Set the voltage at which the inverter shuts down due to low battery.
- Battery Equalization: Enable or disable battery equalization.
- Battery Equalization Voltage: Set the voltage for battery equalization.
- Battery Equalized Time/Timeout: Set the duration for equalization.
- Equalization Interval: Set the frequency of equalization cycles.
- BMS Function Switch: Enable or disable BMS communication.
- Output Frequency: Set to 50Hz or 60Hz.
- Output Voltage: Set to 220V, 230V, or 240V.
- ECO Function: Enable or disable ECO mode for power saving.
- Scheduled Time for AC Output On/Off: Set specific times for AC output operation.
5.4 Battery Equalization Description
Equalization function is added into the charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it is recommended to equalize the battery periodically.
6. Maintenance
To ensure optimal performance and longevity of your Daxtromn Hybrid Solar Inverter, regular maintenance is recommended:
- Keep Clean: Ensure the inverter's ventilation openings are free from dust and debris to allow for proper heat dissipation. Use a soft, dry cloth to clean the exterior.
- Check Connections: Periodically inspect all electrical connections (battery, AC input/output, PV input) to ensure they are tight and free from corrosion. Loose connections can lead to poor performance or safety hazards.
- Monitor Performance: Regularly check the LCD display for any fault codes or unusual operating parameters. Address any warnings or faults promptly.
- Battery Health: If using lead-acid batteries, ensure they are properly maintained (e.g., checking electrolyte levels if applicable) and that the equalization function is used as recommended.
7. Troubleshooting
7.1 Fault and Alarm Descriptions
The inverter enters fault mode when a critical error occurs. The red LED light will be solid on, and the LCD will display a fault code. Alarms indicate a warning condition; the red LED flashes, and the LCD displays an alarm code, but the inverter does not enter failure mode.
Common Fault Codes:
| Fault Code | Fault Event |
|---|---|
| F01 | Fan is locked when inverter is off. |
| F02 | Over temperature or NTC is not connected well. |
| F03 | Battery voltage is too high. |
| F04 | Battery voltage is too low. |
| F05 | Output short circuited or over temperature is detected by internal converter components. |
| F06 | Output voltage is too high. |
| F07 | Overload time out. |
| F08 | Bus voltage is too high. |
| F09 | Bus soft start failed. |
| F51 | Over currents or surge. |
| F52 | Bus voltage is too low. |
| F53 | Inverter soft start failed. |
| F55 | Over DC voltage in AC output. |
| F57 | Current sensor failed. |
| F58 | Output voltage is too low. |
| F59 | PV voltage is over limitation. |
Common Alarm Codes:
| Alarm Code | Alarm Event | Audible Alarm |
|---|---|---|
| A01 | Fan is locked when inverter is on. | Beep three times every second |
| A02 | Over temperature | None |
| A03 | Battery is over-charged | Beep once every second |
| A04 | Low battery | Beep once every second |
| A07 | Overload | Beep once every 0.5 second |
| A10 | Output power derating | Beep twice every 3 seconds |
| A15 | PV energy is low. | Beep twice every 3 seconds |
| A16 | High AC input (>280VAC) during BUS soft start | None |
| A27 | Max battery discharge current setting | None |
| E9 | Battery equalization | None |
| bP | Battery is not connected | None |
7.2 Troubleshooting Guide
| Problem | Explanation/Possible Cause | What to do |
|---|---|---|
| Unit shuts down automatically during startup. | Battery voltage is too low (<1.91V/Cell). | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | 1. Battery voltage is far too low (<1.4V/Cell). 2. Internal fuse tripped. 3. Input protector is tripped. | 1. Contact repair center for fuse replacement. 2. Re-charge battery. 3. Replace battery. Check AC breaker and wiring. |
| Mains exist but unit works in battery mode. | 1. Insufficient quality of AC power. 2. Output source priority set to other than Utility. | 1. Check AC wires/generator. 2. Change output source priority to Utility first. |
| Internal relay switches on/off repeatedly. | Battery is disconnected. | Check if battery wires are connected well. |
| Buzzer beeps continuously, red LED on. | Overload, PV input voltage too high, output short circuit, over temperature, battery over-charged, fan fault, output abnormal, internal components failed, over current, bus voltage too low, output voltage unbalanced, PV input voltage beyond spec. | Reduce load, reduce PV modules, check wiring, check airflow, return to repair center, replace fan, restart unit. |
8. Specifications
Detailed specifications for each model are provided below. Please refer to the specific model you have.
8.1 EGH-11KW Specifications

8.2 JGH-6.2KW Specifications

8.3 EGH-4.2KW Specifications

9. Warranty and Support
Daxtromn provides a one-year official warranty for this product. For product quality issues (non-human-caused damage), support for free replacement parts or repair technical guidance is available. Please note that due to the large size and weight of the inverter, international return shipping can be expensive and time-consuming. If you encounter any problems, please contact your seller immediately and provide a video/photo of the malfunction. Engineers can provide remote troubleshooting assistance, as many issues are often resolved by correcting wiring or parameter settings.
For detailed support or warranty claims, please contact your point of purchase or Daxtromn customer service.