1. Introduction
The GEYA GYM9H-Z Miniature Circuit Breaker is designed for both AC and DC circuits, offering reliable overload and short-circuit protection. Its non-polarized design simplifies installation by eliminating the need to distinguish between positive and negative poles, making it suitable for various applications including photovoltaic (PV) systems, battery main disconnects, industrial, commercial, high-rise buildings, and residential installations.
This manual provides essential information for the safe and effective use of your GYM9H-Z circuit breaker. Please read it thoroughly before installation and operation.
2. Safety Information
WARNING: Electrical shock hazard. Installation and maintenance should only be performed by qualified personnel.
- Always disconnect power before installing or servicing the circuit breaker.
- Ensure proper wiring according to local electrical codes and the provided diagrams.
- Do not operate the circuit breaker if it appears damaged.
- Verify that the rated current and voltage of the circuit breaker match your application requirements.
- The device is designed for indoor use in environments free from excessive dust, moisture, and corrosive gases.
3. Product Features
- Non-Polarized Design: No need to distinguish between positive and negative poles, simplifying wiring and allowing for polarity reversal.
- Dual AC/DC Compatibility: Suitable for both alternating current (AC) and direct current (DC) applications.
- Overload and Short-Circuit Protection: Provides essential safety for electrical circuits.
- Transparent Identification Function: Clear labeling for easy identification.
- Contact Position Indication: Green indication window for closed state, red for open state, offering clear status at a glance.
- Double Sink Flow Bar Wiring: Facilitates secure and efficient wiring connections.
- RoHS 2.0 Compliant: Environmentally friendly manufacturing.



4. Technical Specifications
| Attribute | Value |
|---|---|
| Model Number | GYM9H-Z Non-polar DC MCB |
| Type | Mini Circuit breaker |
| Rated Current (In) | 6A-63A (1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63A) |
| Rated Voltage (Ue) | AC: 230/400V (50/60Hz); DC: 1P:150V, 2P:300V, 3P:450V, 4P:600V |
| Poles | 1P, 2P, 3P, 4P |
| Tripping Curves | B: (6±20%)In, C: (8.5±20%)In, D: (12±20%)In |
| Breaking Capacity | 6KA |
| Mechanical Life | 20000 times |
| Electrical Life | 10000 times |
| Rated insulation voltage (Ui) | 500V |
| Rated impulse withstand voltage (Uimp) | 4KV |
| Tightening Torque | 2.0N.m |
| Class of protection | IP20 |
| EU LVD Voltage | Low voltage: Below 50Vac or 75Vdc |
| High-concerned chemical | None |
| Is Smart Device | No |
| Certification | CE |
Temperature Compensation
When the ambient temperature is not the baseline temperature of 30°C, the reference correction coefficient is as follows:
| Ambient Temperature | -20°C | -10°C | 0°C | 10°C | 20°C | 30°C | 40°C | 50°C | 60°C |
|---|---|---|---|---|---|---|---|---|---|
| Current Correction Factor | 1.25 | 1.2 | 1.15 | 1.10 | 1.05 | 1.00 | 0.95 | 0.90 | 0.85 |
Outline Overall And Installing Dimensions

5. Setup and Installation
The GEYA GYM9H-Z MCB is designed for easy installation on a standard DIN rail. Its non-polarized nature simplifies wiring for both AC and DC applications.
5.1 Wiring Instructions
The GYM9H-Z circuit breaker does not require distinguishing between positive and negative poles, offering flexibility in wiring. It supports both "Top in / Bottom out" and "Bottom in / Top out" configurations.

5.2 Typical Application: PV System Wiring
For photovoltaic systems, the GYM9H-Z can be integrated as a solar disconnect switch or for AC output protection. Below is a typical wiring example:

- Connect the DC input from your solar panels to the designated terminals of the GYM9H-Z circuit breaker, acting as a solar disconnect switch.
- Connect the output of the solar disconnect switch to the DC input of your inverter.
- Connect the AC output of the inverter to the AC load, ensuring another GYM9H-Z circuit breaker is installed for AC protection.
- Ensure all connections are tight (Tightening Torque: 2.0N.m) and secure.
6. Operation
Operating the GEYA GYM9H-Z circuit breaker is straightforward:
- To Turn ON: Push the toggle switch upwards. The indication window will show GREEN, indicating the circuit is closed and power is flowing.
- To Turn OFF: Push the toggle switch downwards. The indication window will show RED, indicating the circuit is open and power is disconnected.
- Automatic Tripping: In case of an overload or short-circuit, the circuit breaker will automatically trip to the OFF position (red indication window) to protect the circuit. Before resetting, identify and resolve the fault.
- Resetting: After resolving the fault, push the toggle switch fully downwards to reset the internal mechanism, then push it upwards to turn the circuit breaker ON.
7. Maintenance
Regular maintenance ensures the longevity and reliable operation of your GEYA GYM9H-Z circuit breaker:
- Visual Inspection: Periodically inspect the circuit breaker for any signs of physical damage, discoloration, or loose connections.
- Cleaning: Keep the circuit breaker clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquid cleaners.
- Connection Check: Ensure all terminal connections remain tight. Re-tighten if necessary, adhering to the specified tightening torque (2.0N.m).
- Functionality Test: Occasionally test the tripping mechanism by simulating a fault (only if safely possible and by qualified personnel) or by manually switching it OFF and ON to ensure smooth operation.
- Environmental Conditions: Ensure the operating environment remains within the specified temperature and humidity ranges to prevent premature wear or malfunction.
8. Troubleshooting
| Problem | Possible Cause | Solution |
|---|---|---|
| Circuit breaker trips frequently. | Overload, short-circuit, or ground fault in the circuit. | Identify and remove the cause of the overload or fault. Reduce the load or repair the short-circuit/ground fault. If the problem persists, consult a qualified electrician. |
| Circuit breaker does not reset. | Persistent fault in the circuit, or internal damage to the breaker. | Ensure the fault has been cleared. Try pushing the switch fully down before pushing it up. If it still doesn't reset, the breaker might be damaged and needs replacement. |
| No power to the circuit, but breaker is ON. | Loose wiring connection, fault elsewhere in the circuit, or upstream power issue. | Check all wiring connections for tightness. Verify power supply from the source. Inspect other components in the circuit. |
| Breaker feels hot to the touch. | Overload, loose connection, or undersized breaker for the load. | Immediately disconnect power. Check for overloads or loose connections. Ensure the breaker's rated current is appropriate for the circuit's load. Consult a qualified electrician. |
9. User Tips
- For solar PV systems, the non-polarized design of the GYM9H-Z simplifies installation, especially in setups where polarity might be reversed or needs flexibility.
- Always ensure the circuit breaker is easily accessible for manual operation and visual inspection.
- Consider the ambient temperature when selecting the appropriate current rating, as higher temperatures may require derating (refer to the Temperature Compensation table in Specifications).
- When installing multiple circuit breakers, ensure adequate ventilation to prevent overheating.
10. Warranty and Support
GEYA products are manufactured to high-quality standards and are certified to required industry standards, including CCC, CE, CB, SAA, SEMKO, TUV, and Rosh. For detailed warranty information or technical support, please refer to the official GEYA website or contact your local distributor.
A user manual in PDF format is available for download: GEYA GYM9H-Z User Manual (PDF).