1. Important Safety Instructions
Please read and follow all instructions and cautions carefully before installation and operation. Save these instructions for future reference.
- Installation and wiring must comply with Local and National Electric Codes (NEC) and be performed by a certified technician.
- Do NOT disassemble or attempt to repair the inverter. There are no user-serviceable parts inside.
- Do NOT parallel this device with other AC input sources to avoid damage.
- Avoid touching the unit during operation as it can become very hot. Do not open the terminal cover while the unit is in operation.
- Ensure all connections to and from the inverter are tight. Sparks may occur during connections; keep flammable materials and gases away from the installation area.
- External breakers or fuses are recommended.
- After installation, verify all line connections are tight and secured.
- Do NOT allow positive (+) and negative (-) battery terminals to touch each other. Use Lithium, deep cycle Sealed Lead Acid, Flooded, Gel, or AGM batteries.
- Explosive battery gases may be present during charging. Ensure adequate ventilation.
- When working with lead-acid batteries, wear eye protection and have fresh water available for contact with battery acid.
- Over-charging or excessive gas precipitation can damage battery plates. Review specific battery requirements.
2. Setup and Installation
2.1 Product Overview and Features
The PowMr POW-SunSmart series is an all-in-one solar charge inverter designed for solar energy storage, utility charging, and AC sine wave output. It features DSP control for high response speed, reliability, and industrial standard performance.
- Supports lead-acid and Li-ion battery connections.
- Dual activation function for dormant Li-ion batteries (mains/PV power supply).
- Supports split-phase and single-phase pure sine wave output.
- Adjustable output voltage levels: 100Vac, 105Vac, 110Vac, 115Vac, 120Vac, 127Vac per phase.
- Two solar inputs with simultaneous tracking of two maximum power points (MPPT).
- Dual MPPT with 99.9% efficiency, max 22A current per circuit.
- Charging modes: solar only, mixed mains/PV charging.
- Time-slot charging/discharging function.
- Energy saving mode.
- Two output modes: utility bypass and inverter output with uninterrupted power supply.
- Large LCD screen with dynamic flow diagram.
- 360° protection: short circuit, over current, over/under voltage, overload, backfill.
- Communication: CAN, USB, RS485.

Image: Key features of the 10KW Split-Phase Hybrid Solar Inverter, including Pure Sine Wave, Dual MPPT, 11KW Max PV Array Power, 500V VOC, 22A, 120V/220V AC output, compatibility with Lead-acid, Lithium, and Batteryless systems, and support for Solar, Utility, or Generator power.
2.2 Mounting the Inverter
The POW-SunSmart series is designed for INDOOR USE ONLY (IP20).
- Choose a solid wall for installation.
- Mount the inverter at eye level.
- Ensure adequate heat dissipation space around the unit.
- Operating ambient temperature: -10~55°C (14~131°F).
DANGER:
- Do not install near highly flammable materials or in potential explosive areas.
- Do not install with lead-acid batteries in a confined space.
CAUTION:
- Do not install in direct sunlight or in a humid environment.
To mount, drill 4 holes according to the dimensions (500mm height, 230mm width for top holes, 295mm width for bottom holes). Insert 2 expansion screws at the top and fix the inverter with 2 M5 screws at the bottom.
2.3 System Connection Diagram
A complete system typically includes PV modules, utility grid/generator, battery, home loads, and the inverter.

Image: Diagram showing the overall system connection. PV panels connect to the inverter, which connects to external battery packs. The inverter also connects to the utility grid/generator input and supplies power to various home appliances (loads).
2.4 Wiring Connections
Before making any connections, ensure the terminal cover and insect screen are removed. Clean the insect screen regularly to prevent overheating.
2.4.1 AC Input & Output Connection
Connect live, neutral, and ground wires as per the diagram. Ensure circuit breakers are open before connecting. Use sufficiently thick cables to avoid safety hazards.
DANGER: Risk of electric shock. Do not operate with electricity.
2.4.2 Battery Connection
Connect positive and negative battery cables. Ensure correct polarity. Use sufficiently thick cables.
DANGER: Risk of electric shock. Do not operate with electricity. Incorrect polarity can damage the inverter.
The inverter is compatible with 48V lead-acid and lithium batteries, and can run batteryless. Battery charging current setting range: 0~200A.

Image: Inverter compatibility with various 48V battery types: AGM, GEL, FLD (Flooded), LI (Lithium), SLD (Sealed Lead-Acid), and USER defined. It also highlights batteryless support, where the inverter can power loads from PV array or AC grid without a battery.
2.4.3 PV Connection
Connect positive and negative wires of PV strings. Ensure circuit breakers are open. The maximum open circuit voltage of PV modules in series must NOT exceed 500Vdc to prevent inverter damage.
DANGER: Risk of electric shock. Do not operate with electricity. Over-voltage can damage the inverter.

Image: Diagram illustrating dual MPPT connections. PV1 and PV2 can be connected to solar panels of different orientations and specifications. Shows an example of 4500W and 3000W PV inputs to the inverter, charging a 48V 200Ah battery pack. Benefits of Dual MPPT include improved efficiency, reduced impact of shading, and enhanced system reliability.
2.4.4 Dry Contact Connection
Used for battery temperature sampling and remote generator start/stop. Refer to the manual for specific pin configurations.
2.4.5 Grounding Connection
Connect the grounding terminal to the grounding busbar. The grounding cable should have a diameter of at least 4 mm2 and be as close as possible to the grounding point.
2.5 Inverter Start-up Procedure
- Restore the terminal cover.
- Close the battery circuit breaker.
- Press the rocker switch at the bottom of the inverter; the screen and indicator will light up.
- Close circuit breakers for PV input, AC input, and AC output sequentially.
- Start loads one by one, from smallest to largest power.
2.6 Parallel Connection (Optional)
The inverter supports parallel operation for up to six units. This requires specific communication cable connections and wiring configurations for PV, battery, and AC input/output.
For detailed parallel connection diagrams and instructions, refer to Appendix 10 of the full user manual (PDF). It covers single-phase, two-phase, and three-phase parallel connections.

Image: Complex wiring diagram showing how to connect up to six inverters in parallel for increased capacity. The diagram illustrates connections for battery, utility grid, and loads across multiple inverters (P1, P2, P3 groups).
3. Operating Instructions
3.1 Operation and Display Panel
The inverter features an LCD screen, 3 LED indicators, and 4 touchable keys for operation and monitoring.
Video: Demonstration of the inverter's touch screen display, showing real-time voltage, current, daily kWh, temperature, and rated values for PV side, AC IN side, Battery side, and Load side.
3.1.1 Touchable Keys
- Gear Icon: Enter/exit the setting menu.
- Up Arrow: Go to the next selection.
- Down Arrow: Go to the previous selection.
- Check Mark: Confirm/Enter the selection in the setting menu.
3.1.2 LED Indicators
- AC/INV (Yellow): Steady on for utility grid bypass output; Flashing for inverter output.
- CHARGE (Green): Steady on for charging complete; Flashing for charging.
- FAULT (Red): Steady on for level-1 fault; Flashing for level-2 fault; Off for level-3 or level-4 fault.
3.2 Viewing Real-time Data
From the main screen, use the UP/DOWN keys to cycle through real-time data such as PV input voltage/current/power, battery voltage/current, AC input voltage/current/power, load voltage/current/power, temperatures, frequencies, and software version.
3.3 System Settings
The inverter offers extensive configurable settings accessible via the setting menu. Key settings include:
- AC Output Source Priority: UTI (Utility priority), SBU (Inverter first), SOL (Solar priority), SUB (Solar/Utility Hybrid).
- AC Output Frequency: 50.0Hz or 60.0Hz.
- AC Input Voltage Range: UPS (90~140V) or APL (85~140V).
- Battery to Mains Voltage Threshold: Configures the switch-over point.
- Battery Charging Mode: SNU (Solar/Utility Hybrid), OSO (Solar Only).
- Max. Charging Current (Grid+PV): Configurable up to 180A (8KW) or 200A (10KW).
- Battery Type: USER, SLD (Sealed Lead-Acid), FLD (Flooded), GEL, L14/L15/L16 (Lithium), N13/N14 (Ternary Li-ion), NOb (No battery mode).
- Battery Voltages: Boost, Float, Over-discharge, Under-voltage alarm, Discharge limit.
- Battery Equalization: Enable/disable, voltage, duration, delay, interval.
- Power Saving Mode: Enable/disable.
- Overload/Over-temperature Restart: Enable/disable auto restart.
- Buzzer Alarm: Enable/disable.
- Parallel Mode: SIG (Single), PAL (Parallel), 2P0/2P1/2P2 (Two-phase), 3P1/3P2/3P3 (Three-phase).
- SOC Settings: For discharge alarming, discharge cutoff, charge cutoff, switching to mains/inverter.
3.4 Communication
The inverter supports USB-B, WIFI, RS485/CAN, and Dry Contact ports for communication and monitoring.
- USB-B Port: Connects to a computer for reading/modifying parameters via software.
- WIFI Port: Connects to a Wi-Fi/GPRS data acquisition module (purchased separately) for mobile app monitoring.
- RS485/CAN Port: Connects to the BMS of Li-ion batteries.

Image: Screenshot of the SmartESS app interface for monitoring and controlling the inverter. Shows options to download on the App Store and Get it on Google Play. Also depicts optional WiFi/GPRS modules, noting they need to be purchased separately.
4. Maintenance
To ensure optimum and long-lasting performance, perform the following checks twice a year:
- Ensure clear airflow around the inverter; remove dirt/debris from the radiator.
- Check exposed conductors for damage (sunlight, friction, dry rot, insects, rodents); repair/replace as needed.
- Verify display consistency; note and correct any faults.
- Check all terminals for corrosion, insulation damage, overheating; tighten screws.
- Clean the insect screen and check for dirt/nesting insects/corrosion.
- Replace failed lightning arresters promptly.
DANGER: Before maintenance, disconnect all power sources and ensure capacitors are fully discharged to avoid electric shock.
5. Troubleshooting
Refer to the table below for common fault codes and their remedies. If issues persist, contact support.
| Fault Code | Meaning | Remedy |
|---|---|---|
| No screen display | No power input or device switch is off. | Check battery/PV air-switches, ensure switch is ON, press any button to exit sleep mode. |
| 01 (BatVoltLow) | Battery under-voltage. | Charge battery until voltage exceeds set parameter. |
| 03 (BatOpen) | Battery disconnected. | Check battery connections, breaker, and BMS communication. |
| 04 (BatLowEod) | Battery over-discharge. | Charge battery until voltage exceeds set parameter. Manual reset (power off/on). |
| 06 (BatOverVolt) | Battery over-voltage. | Discharge battery until voltage is below recovery point. |
| 13 (Overload Bypass) | Bypass overload. | Reduce load power and restart. |
| 14 (OverloadInverter) | Inverter overload. | Reduce load power and restart. |
| 19 (OverTemperMppt) | MPPT heat sink over-temperature. | Allow unit to cool down. |
| 20 (OverTemperInv) | Inverter heat sink over-temperature. | Allow unit to cool down. |
| 21 (FanFail) | Fan failure. | Toggle fan, check for obstructions. If persistent, contact service. |
If you encounter product faults not listed or unresolved, contact the after-sales service department. Do not disassemble the device yourself.
6. Specifications
| Category | Parameter | Value (POW-SunSmart 10KP) |
|---|---|---|
| Inverter Output | Rated Output Power | 10,000W |
| Max. Peak Power | 20,000W | |
| Rated Output Voltage | 120/240Vac (split phase/single phase) | |
| Rated AC Frequency | 50/60Hz | |
| Waveform | Pure Sine Wave | |
| Battery | Battery Type | Li-ion / Lead-Acid / User Defined |
| Rated Battery Voltage | 48Vdc | |
| Voltage Range | 40-60Vdc | |
| Max. MPPT Charging Current | 200A | |
| PV Input | Max. Input Current | 22/22A |
| Max. Voltage of Open Circuit | 500Vdc/500Vdc | |
| MPPT Voltage Range | 125-425Vdc | |
| General | Dimensions (L*W*H) | 620 × 445 × 130mm |
| Weight | 27kg (59.5lb) | |
| Operating Temperature Range | -10~55℃ (14~131°F) |
7. Warranty and Support
This PowMr Hybrid Inverter comes with an 18-month warranty.
For technical support, warranty claims, or further inquiries, please contact:
SHENZHEN HEHEJIN INDUSTRIAL CO.,LTD
- Tel/Fax: +86 755-28219903
- Email: support@powmr.com
- Web: www.powmr.com
- Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China
Our company is not responsible for damages due to improper use, exceeding voltage/temperature limits, unauthorized disassembly, or force majeure.