1. Introduction
This manual provides essential information for the assembly, installation, operation, and maintenance of the ECGSOLAX ECG-HVM6.5KP-48V Solar Hybrid Inverter. Please read this manual carefully before installation and operation to ensure safe and efficient use.
1.1 Product Overview
The ECG-HVM6.5KP-48V is a multifunctional solar inverter, integrating an MPPT solar charge controller, a high-frequency pure sine wave inverter, and a UPS function module. It is designed for off-grid backup power and self-consumption applications and can operate with or without batteries. The inverter features a built-in WiFi module for remote monitoring via mobile app or website.

Figure 1: Front and Rear Panel Overview of the ECGSOLAX Inverter. Shows AC input/output, PV input, battery connections, communication ports, and power switch.
1.2 Key Features
- Rated power: 6.5kW/6.5kVA, power factor 1
- MPPT range: 60V~450V, 500Voc
- High frequency design for small size and light weight
- Pure sine wave AC output
- Simultaneous solar and grid power loads
- CAN/RS485 for BMS communication
- Ability to work without battery
- WIFI remote monitoring (optional)
- Dual AC output
- Feed-in to grid capability
- Supports up to 9 inverters in parallel
1.3 Safety Instructions
This inverter should be connected to a permanent grounded wiring system. All electrical installations must comply with local electrical safety standards. Qualified personnel should perform all operations and connections. Always disconnect all wirings before attempting maintenance or cleaning.
- WARNING! Do not disconnect under load.
- DANGER: High Voltage! Electrical Hazard!
- Allow at least 5 minutes after disconnecting from all external power supplies before maintaining the inverter.
- Read instructions carefully before any operation.
- The system must be firmly grounded for operator safety.
- Charge only deep-cycle lead-acid or lithium batteries. Other battery types may burst.
- Do not disassemble the unit; refer to a qualified service center for repairs.
- Never charge a frozen battery.
- Ensure correct cable sizing for optimum operation.
- Be cautious with metal tools around batteries to prevent short circuits or explosions.
- Do not short circuit AC output and DC input. Do not connect to mains when DC input is short-circuited.
2. Setup and Installation
2.1 Unpacking and Inspection
Upon receiving the product, inspect the packaging for any damage. Open the box and check if the inverter or internal equipment is damaged. If any damage is found, contact your local distributor immediately. Verify all items against the packing list:
| No. | Item | Quantity | Description | Remarks |
|---|---|---|---|---|
| 1 | Inverter | 1 | ||
| 2 | User manual | 1 | English | |
| 3 | Tubular terminal | 10 | E6010 | For AC input, AC output, PV input. |
| 4 | OT terminal | 1 | For PE | |
| 5 | Ethernet cable | 1 | For parallel communication |
2.2 Mounting Unit
Mount the inverter on a solid, non-combustible surface. Ensure sufficient clearance (at least 30cm on all sides) for heat dissipation and wiring access. Install the inverter at eye level for easy LCD display reading. The ambient temperature should be between -10°C and 60°C for optimal operation.

Figure 2: Recommended mounting clearances for proper ventilation and access.
Installation Steps:
- Drill two Φ8 holes 160mm apart on the mounting surface. Insert M6 expansion screw tubes.
- Align the inverter's top screw holes with the installed expansion screw tubes and fix the inverter to the wall.
- Before wiring, remove the bottom cover by unscrewing the four retaining screws.
2.3 AC Input / Output Connection
Install a separate 40A AC breaker between the inverter and the AC input power source. Ensure correct polarity (L and N wires) to prevent short circuits in parallel operation. The N lines of input and output must not be connected together.
Recommended Cable Size for AC Input/Output:
- AC Input: 10 AWG (5.26 mm²)
- AC Output: 12 AWG (4 mm²)
Connection Steps:
- Ensure AC power is disconnected and the AC circuit breaker is open.
- Remove 12mm insulation from cable ends, shorten conductor to 10mm, insert into tubular terminal, and crimp tightly.
- Insert AC input cables according to polarities (PE: yellow-green, L: brown/black, N: blue) and tighten terminal screws. Connect the PE protective cable first.
2.4 PV Connection
Install a separate DC circuit breaker between the inverter and PV modules. Do not ground positive or negative PV module terminals. Cover PV modules with opaque materials during daytime installation to avoid high terminal voltage.
Recommended Cable Size for PV Connection:
- PV Module Connection: 10 AWG (5.26 mm²)
PV Module Selection Parameters:
- Max. PV Array Open Circuit Voltage: 500Vdc
- Start-up Voltage: 80Vdc
- PV Array MPPT Voltage Range: 60Vdc~450Vdc
Connection Steps:
- Ensure DC circuit breaker is open.
- Prepare PV cables with tubular terminals as described for AC connections.
- Use a multi-meter to check polarities (+ to red, - to black).
- Insert PV cables into terminal block according to polarities and tighten screws.
2.5 Battery Connection
Install a separate DC over-current protector or disconnect device (recommended 150A) between the battery and inverter. Ensure AC power is disconnected before connecting batteries.
Recommended Battery Cable Size:
- Battery Connection: 2 AWG (25 mm²)
Lead-acid Battery Connection:
- Prepare 2 DT terminals for AWG2 cables.
- Prepare battery cables (positive and negative) with DT terminals.
- Pass battery cables through the bottom shell and tighten terminal screws, ensuring correct polarity.
- Connect all battery packs as required. A minimum 200Ah capacity battery is suggested.
Lithium Battery Connection:
- Follow the power cable connection steps for lead-acid batteries.
- Connect the RJ45 terminal of the battery communication cable to the BMS communication port of the inverter. The communication protocol should be RS485 or CAN.
- Insert the other end of the RJ45 cable to the lithium battery's communication port.
2.6 Parallel Installation Guide
The inverter supports parallel operation in single phase (up to 9 units) or three-phase (up to 9 units, with up to 7 units per phase). Ensure proper clearance between inverters and use recommended breaker/disconnector sizes.

Figure 3: Example of 4 inverters connected in parallel, showing battery, grid, and device connections.
Important Considerations for Parallel Systems:
- Grid and output cables for parallel inverters in the same phase must have consistent material, cross-sectional area, and length.
- All inverters must be connected to the same batteries. It is recommended to connect battery interfaces to a common copper bar.
- Do not connect the same PV string to multiple inverters; each inverter must have its own PV connection.
- The leakage current specification of the AC input breaker should be 300mA.
- Parallel communication cables should be arranged separately from power lines with at least 5cm spacing to avoid interference.
Smart Communication Stick Connection (Optional):
The smart communication stick (WiFi) connects the inverter to the cloud platform for monitoring. Insert the stick directly into the COM port. For parallel systems, you can either install one WiFi stick on any inverter (the entire system uploads data through it) or install WiFi sticks on each inverter (each uploads its own data).
3. Operation
3.1 Power ON/OFF
Once the inverter is properly installed and batteries are connected, press the ON/OFF switch (located on the bottom of the case) to turn on the unit.
3.2 Operation and Display Panel
The front panel features an LCD display, four indicators (AC, Invert, Charging, Fault), and four function keys (ESC, UP, DOWN, ENTER) to show operating status and input/output power information.
LED Indicators:
| Indicator | State | Message |
|---|---|---|
| AC (Green) | Solid On | Mains power is normal and in operation. |
| Flashing | Mains power is normal but not yet in operation. | |
| Off | Mains power is abnormal. | |
| Invert (Yellow) | Solid On | Output powered by battery or PV in battery mode. |
| Off | Other states. | |
| Charging (Yellow) | Solid On | Battery is in float charging. |
| Flashing | Battery is in constant voltage charging. | |
| Off | Other states. | |
| Fault (Red) | Solid On | Fault occurs in the inverter. |
| Flashing | Warning condition occurs in the inverter. | |
| Off | Inverter is working properly. |
Function Buttons:
- ESC: To exit setting mode.
- UP: To go to previous selection.
- DOWN: To go to next selection.
- ENTER: To confirm selection or enter setting mode.
3.3 LCD Setting Programs (Key Settings)
Press and hold ENTER for 2 seconds to enter setting mode. Use UP/DOWN to select programs and ENTER to confirm. ESC to exit.
- Program 01: Output Voltage (Default: 230V, Adjustable: 208V, 220V, 230V, 240V)
- Program 02: Output Frequency (Default: 50Hz, Adjustable: 50Hz, 60Hz)
- Program 03: Output Source Priority (Grid first, Solar first, SBU priority)
- Program 04: Input Mode (Appliance, UPS, GEN)
- Program 05: Charger Source Priority (Only PV, PV first, PV and Grid)
- Program 06: Grid Charging Current (Default: 60A, Adjustable: 2A-120A)
- Program 07: Maximum Charging Current (Default: 100A, Adjustable: 2A-120A)
- Program 17: Battery Type (AGM, Flooded, Lithium (Ternary), FEL (Lithium iron), User-Defined)
- Program 27: Parallel Operation Mode (SIG: Single mode, PAR: Single-phase parallel, 3P1/3P2/3P3: Three-phase)
- Program 28: Parallel Identity Code (ATO: Auto, 1-9: Unique ID)
- Program 38: Battery Dual Output Low Voltage Shutdown Point (Default: 48V, Adjustable: 44V-60V)
- Program 44: BMS Communication Function (CVT, PYL, GRO, VOL, IRF, PAC protocols)
4. Maintenance
4.1 Battery Equalization
The equalization function helps reverse the buildup of negative chemical effects like stratification and removes sulfate crystals from battery plates, extending battery life. This function is primarily for lead-acid batteries; do not activate it when using lithium batteries.
How to Apply Equalization:
Enable the battery equalization function in LCD setting Program 32 by setting a time, or choose immediate equalization on Program 35. You can configure:
- Equalization voltage point (Program 31)
- Equalization charging time (Program 32)
- Equalization delay time (Program 33)
- Equalization interval time (Program 34)
- Immediate equalization mode activation (Program 35)
The controller will enter the Equalize stage when the set equalization interval is reached or if immediate equalization is activated.
5. Troubleshooting
This section provides guidance on common faults and alarms. For detailed information, refer to the full user manual PDF available at User Manual (PDF).
5.1 Fault Reference Codes
If a fault occurs, the fault indicator will be solid red, and the buzzer will sound briefly. The system will attempt to restart automatically. If the fault persists after six restarts, the inverter will remain in fault status.
| Fault Code | Meaning | Trigger Conditions | What to Do |
|---|---|---|---|
| 1 | Bus boost fail | Grid soft start process starts but bus voltage does not reach set value. | Restore after reaching the set voltage for 15 seconds. |
| 2 | Bus over voltage | Bus voltage is higher than set value. | Restore after reaching the set voltage for 15 seconds. |
| 3 | Bus below voltage | Bus voltage is lower than set value. | Cannot restore. |
| 5 | System over temperature | PFC temperature is higher than set value or fan is not connected. | Restore after temperature lower than set value and fan connected for 15 minutes. |
| 14 | Over load | The load current is higher than the set value. | Restore after reaching the set value for 15 seconds. |
| 24 | Parallel Configuration Differ | In three-phase parallel mode, different machine parallel mode settings may have phase loss. | Restore after set to single machine operation and disconnect parallel communication, or parallel operation condition recover. |
| 26 | BMS Fault | Error code in BMS message. | Restore after BMS fault resolved. |
5.2 Alarm Reference Codes
When an alarm occurs, the LED red light will flash, and the LCD will display the alarm code. The inverter does not enter fault mode during an alarm.
| Alarm Code | Meaning | Trigger Conditions | What to Do |
|---|---|---|---|
| 50 | Battery open | Battery disconnected for < 10 minutes. | Restore after battery connected and charging for 2 minutes. |
| 51 | Battery under voltage | Battery voltage is lower than BAU set value. | Restore after battery voltage exceeding BAU set value by 2V. |
| 56 | BMS loss | Communication failure after BMS communication function is enabled. | Restore after communication function disabled or communication success. |
| 58 | Fan error | No fan speed signal detected. | Restore after fan speed signal detected. |
| 60 | Overload | Mains current/battery discharge current/load power is higher than rated value. | Restore after mains current/battery discharge current/load power is less than rated value. |
| 62 | PV energy weak | When battery is not connected, bus voltage is lower than set value. | Restore after battery connected or grid connected, or 10 minutes later. |
6. Specifications
Detailed technical specifications for the ECG-HVM6.5KP-48V Solar Hybrid Inverter.
| Category | Specification | |
|---|---|---|
| AC Input | Rated Input Voltage (VAC) | 208/220/230/240; L+N+PE |
| Voltage Range (VAC) | 90~280 (APP/GEN mode); 170~264 (UPS mode) | |
| Frequency (Hz) | 50/60 (Auto Adaptive) | |
| AC Output | Rated Capacity (kVA/kW) | 6.5 (Output Power rating reduced to 90% at 208V, 95% in parallel mode) |
| Surge Power (kVA) | 12 | |
| Voltage (VAC) | 208/220/230/240 | |
| Power Factor (PF) | 1 | |
| Frequency (Hz) | 50/60±0.1% | |
| Switch Time (ms) | 10 (APP/UPS mode) / 20 (GEN mode) | |
| WaveForm | Pure SineWave | |
| Performance | Overload Capacity | 1min@ 102%-120% load; 10s@ 120%-200% load |
| Max. Efficiency (Battery Mode) | 94%@48V | |
| Charger (PV/AC) | Solar Charger Type | MPPT |
| Max PV Input Current (A)/Power (W) | 27/9000 | |
| MPPT Range@Operating Voltage (VDC) | 60-450 | |
| PV Start-up Voltage (VDC) | 80 | |
| Max PV Open Circuit Voltage (VDC) | 500 | |
| Max PV Charge Current (A) | 120 | |
| Battery | Normal Voltage (VDC) | 48 |
| Battery Type | Lithium/Lead-acid | |
| General Data | HMI | LCD |
| Interface | RS485/CAN/RS232, Parallel ports | |
| Monitoring | WiFi(Optional) | |
| Ingress Protection | IP21 | |
| Operating Temperature (°C) | -10~60 | |
| Relative Humidity | 5%~95% (Non-condensing) | |
| Max. Operating Altitude (m) | 4000 (Derating above 2000) | |
7. User Tips
- For optimal performance, ensure all cable connections are secure and correctly sized according to the manual. Loose connections can lead to efficiency loss or safety hazards.
- Regularly check the LCD display for any fault or alarm codes. Addressing these promptly can prevent minor issues from escalating.
- If using lithium batteries, always ensure the BMS communication cable is properly connected and the correct battery type is selected in the LCD settings (Program 17).
- When setting up a parallel system, double-check the parallel identity codes (Program 28) to ensure each inverter has a unique ID.
- Keep the inverter's ventilation clear and ensure adequate clearance around the unit to prevent overheating, especially in warmer climates.
8. Frequently Asked Questions (FAQ)
- Q: Can this inverter work without batteries?
- A: Yes, the ECGSOLAX ECG-HVM6.5KP-48V inverter has the ability to work without batteries, making it suitable for direct solar power applications.
- Q: How many inverters can be connected in parallel?
- A: This inverter supports up to 9 units in parallel for single-phase operation, and up to 9 units for three-phase operation (with a maximum of 7 units per phase).
- Q: What should I do if I see a fault code on the LCD?
- A: Refer to the 'Fault Reference Code' section in this manual (or the full PDF manual) to identify the code and follow the recommended actions. Often, the system will attempt to restart automatically.
- Q: Is WiFi monitoring built-in or optional?
- A: The WiFi module is built-in or can be a plug-and-play monitoring device. It allows users to monitor the PV system status via a mobile app or website.
- Q: What type of batteries are compatible with this inverter?
- A: The inverter is compatible with both Lithium and Lead-acid (AGM, Flooded) battery types. Ensure the correct battery type is selected in the LCD settings (Program 17) for proper operation.