1. Introduction
The CJtest CJ6000 three-phase digital volt ampere phase test meter is designed for measuring three-phase electrical parameters. It achieves high-precision measurement of three-phase voltage, current, phase angle, frequency, power, power factor, and other electrical parameters.
The instrument features a high-speed Cortex M3 processor and a 24-bit high-speed ADC for electrical parameter measurement and calculation. It boasts a fully graphical interface with a true color display resolution of 800x480, touch screen operation, and a user-friendly human-machine interface, making it easy to carry and operate.
Key capabilities include:
- Simultaneous measurement of three-phase voltage and four-circuit current (including zero line current).
- Simultaneous measurement of three-phase AC voltage phase angle, current phase angle, and power angle to determine grid frequency and phase sequence.
- Hexagonal chart display and color phase sequence analysis.
- Automatic identification of transformer winding, capacitance, and inductive loads.
- Measurement of active power, reactive power, apparent power, three-phase power, and power factor.
2. Safety Instructions
Please read and adhere to the following safety instructions to ensure safe operation and prevent damage to the instrument or injury to personnel:
- Safety should always be the primary consideration when using this instrument.
- Before use, confirm that the instrument and all accessories are in good condition, free from damage, exposure, or disconnection.
- Do not use the instrument to test voltages above 600V.
- Ensure that all connecting plugs are tightly inserted into their respective interfaces.
- Do not use the instrument in damp conditions.
- Prohibit testing in flammable and hazardous areas.
- The test line must be removed from the tested wire before being disconnected from the instrument. Do not touch the input socket by hand to avoid electric shock.
- Avoid using the instrument in strong electromagnetic environments, as this may affect its normal operation.
- Do not place or store the instrument in areas with high temperature, high humidity, condensation, or under direct sunlight for extended periods.
- The instrument and current clamps must be regularly maintained and kept clean. Do not wipe with corrosive agents or rough objects.
- Avoid impact on the current clamp, especially on the joint surface of the clamp.
- If the instrument is not used for a long time, charge its battery to at least two-thirds capacity before storage.
- Any use, disassembly, calibration, or maintenance of this instrument must be carried out by authorized and qualified personnel.
- If continued use of the instrument poses a danger, it should be immediately stopped and sealed for disposal by an authorized and qualified organization.
- It is strictly prohibited to use sharp or hard objects to scratch the touch screen to prevent damage.
- The touch screen is strictly prohibited from being hit or subjected to pressure.
3. Setup
3.1 Instrument Components
Host Diagram:
Figure 1: Host Diagram, illustrating the main unit with its display, navigation buttons, and power controls.
Current Clamp Sensor:
Figure 2: Current Clamp Sensor, showing four high-precision clamp sensors used for current measurement.
Voltage Test Wire:
Figure 3: Voltage Test Wire, illustrating the cables used for voltage measurement.
3.2 Measurement Wiring
3.2.1 Unidirectional Measurement Wiring Method
Connect the live wire to the UA phase of the instrument and the neutral wire to the UN. Clamp the current clamp sensor onto the live wire and connect it to the IA socket.
Figure 8: Single phase electrical wiring method.
3.2.2 Three Phase Three Wire Wiring Method
Connection of voltage lines: Use dedicated voltage test lines (yellow, red, and black), with one end sequentially inserted into the UA, UC, and UN phase sockets of this instrument, and the other end connected to the A phase, C phase, and B phase of the tested circuit. Attention: The yellow wire is connected to the UA jack, the black wire is connected to the UN jack, and the red wire is connected to the UC jack.
Connection of current line: Insert the IA and IC clamps into the IA and IC sockets of this instrument, and then clip the other end into the measured current circuit.
Figure 9: Schematic diagram of three-phase three-wire wiring.
3.2.3 Three Phase Four Wire Connection Method
Connection of voltage lines: Use dedicated voltage test lines (yellow, green, red, and black), with one end sequentially inserted into the UA, UB, UC, and UN phase sockets of this instrument, and the other end connected to the A phase, B phase, C phase, and zero line of the tested line.
Connection of current lines: Insert the IA, IB, and IC clamp meters into the IA, IB, and IC sockets of this instrument, and then clip the other end into the measured current circuit.
Figure 10: Schematic diagram of three-phase four-wire wiring.
4. Operating Instructions
4.1 Power On/Off
To power on the instrument, continuously press the power button (
). The instrument will display a welcome screen:
Figure 4: Startup screen.
Continue pressing the button for 3 seconds until the instrument fully powers on and makes a beep sound. Release the button once the instrument is on.
4.2 Measurement Interface Description
Upon startup, the instrument automatically enters the measurement interface, displaying real-time electrical parameters:
Figure 5: Voltage Ampere Phase Measurement Interface.
The interface shows various parameters including Voltage (Vol), Current (Curr), Phase Angle (P.Angle), Displacement Power Factor (DPF), Active Power (P(W)), Apparent Power (S(var)), Reactive Power (Q(VA)), Frequency (Freq), and Load characteristics.
4.3 Unbalance Measurement
By default, the instrument tests the volt ampere phase upon startup. To test three-phase imbalance, select the [volt ampere phase] option and press the [down] button. The unbalance test interface will be displayed:
Figure 6: Unbalance measurement interface.
If the measurement method is three-phase three-wire, press the [Right] or [Left] button to select the appropriate wiring method. If you need to switch to three-phase four-wire, select 'Three-phase four wire' and press the corresponding button.
4.4 Navigation and Data Saving
Press the [ESC] button on any testing interface to exit the test and return to the main page. Use the [Right] or [Left] buttons to select icons on the main page, then press [OK] to enter the function interface.
Figure 7: Home page interface.
The instrument has data retention and saving functions. During testing, press the [SAVE] button to open a data saving dialog box. Data is automatically saved and stored in a loop, with newer data overwriting the oldest. Saved data can be viewed using the viewing function. A purple icon with a red number indicates the serial number of the saved data. Use the [Down] button to scroll through the data.
4.5 System Settings
To access system settings, navigate to the 'Sys setup' icon on the home page and press [OK]. The system settings dialogue window will appear:
Figure 8: System Settings Dialogue Window.
Use the [Loop/TAB] button to cycle the cursor position. Use the [Down] button to adjust numerical values (e.g., for time settings). For language settings, you can choose between Simplified Chinese and English. When adjusting a specific digit of time, use the [Right] or [Left] button to select the digit. After making adjustments, press [Loop/TAB] to move the cursor to [Save], then press [OK] to save and exit.
4.6 Load Characteristics Analysis
During the testing process, the instrument analyzes load characteristics:
- If the load power angle is less than 5 degrees, the instrument determines it as a resistive load.
- If the power angle is greater than 5 degrees, the instrument determines whether it is a capacitive load or a resistive load based on the positive or negative power angle.
5. Maintenance
- Regularly clean the instrument and current clamps. Do not use corrosive agents or rough objects for cleaning.
- Avoid physical impact on the current clamps, especially on their joint surfaces.
- If the instrument is to be stored for an extended period, ensure the built-in lithium battery is charged to at least two-thirds of its capacity.
- All maintenance, calibration, and repairs must be performed by authorized and qualified personnel.
- Store the instrument in a dry environment, away from extreme temperatures, humidity, condensation, and direct sunlight.
6. Troubleshooting
If you encounter any issues with the CJtest CJ6000 that cannot be resolved by following the operating instructions, please consider the following general steps:
- Check Connections: Ensure all test leads and clamp sensors are securely connected to the instrument and the circuit being tested.
- Battery Level: Verify that the instrument's battery is sufficiently charged.
- Environmental Conditions: Confirm that the operating environment is within the specified temperature and humidity ranges, and free from strong electromagnetic interference.
- Restart: Try powering off the instrument completely and then restarting it.
For persistent problems or complex technical issues, please contact authorized service personnel for assistance. Do not attempt to disassemble or repair the instrument yourself, as this may void the warranty and cause further damage.
7. Specifications
| Parameter | Value |
|---|---|
| Model | CJ6000 |
| Working Power Supply | Built-in 8.4V/2.6AH lithium battery |
| Voltage Range | 1~500V (0.5% accuracy) |
| Current Range | 0.001~10A (0.2% accuracy) |
| Active Power | 0.001~5000W (0.5% accuracy) |
| Reactive Power | 0.001~500VAR (0.5% accuracy) |
| Apparent Power | 0.001~500VA (0.5% accuracy) |
| Frequency | 45~65Hz (0.1% accuracy) |
| Phase | 0~360° (±2° accuracy) |
| Display | Large screen color LCD |
| Dimensions | 380mm*260mm*180mm |
| Operating Temperature | 0-40°C |
| Accuracy Class | 1% |
| DIY Supplies | Electrical |
| Certification | CE |
8. Accessories
The CJtest CJ6000 package includes the following accessories:
| Name | Quantity (Full Functional Configuration) | Quantity (Standard Configuration) |
|---|---|---|
| Main Meter | 1pcs | 1pcs |
| Current Clamp | 4pcs | 3pcs |
| 12V1A Adapter | 1pcs | 1pcs |
| Alligator Clip | 4pcs | 4pcs |
| Wire | 4pcs | 4pcs |
| User Manual/Certificate of conformity | 1pcs | 1pcs |
| Suitcase | 1pcs | 1pcs |
9. User Tips
- Upon receiving your CJ6000, carefully unbox and verify that all listed accessories, including the alligator clips and protective suitcase, are present and in good condition.
- Always ensure the battery is adequately charged before starting any critical measurements to avoid interruptions.
10. Warranty and Support
Product Replacement: Within one month from the date of sale, if the product exhibits any quality issues not caused by user misuse, the company is responsible for replacing it with a new one. Disassembly of the instrument by the user will void this replacement service.
Free Repair: If problems occur within one year from the date of sale, and are not caused by improper use by the user, the company will provide free repair services.
Paid Repair: If damage is caused by improper use by the customer, a reasonable repair fee will be charged.
For any service inquiries or support, please contact your vendor or authorized service center.