1. Introduction
1.1 Purpose & Scope
This manual describes the assembly, installation, operation, and troubleshooting of the ECGSOLAX 4200W 24V Hybrid Solar Inverter. Please read this manual carefully before installation and operation. Keep this manual for future reference. This manual provides safety and installation guidelines as well as information on tools and wiring.
1.2 Product Overview
The ECGSOLAX Hybrid Solar Inverter is a multi-function inverter/charger, combining the capabilities of an inverter, solar charger, and battery charger to provide uninterruptible power support in a portable size. Its comprehensive LCD display allows for user-configurable and easy-accessible button operation for settings such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications. The solar charging module utilizes optimized MPPT technology to quickly track the maximum power point of the PV array, ensuring maximum energy harvest from solar panels and converting DC into pure sine wave AC output.
1.3 Key Features
- Pure sine wave solar inverter
- WIFI & GPRS available for iOS and Android monitoring
- Inverter operation without a battery
- One-key restoration to factory settings
- Built-in lithium battery automatic activation
- MPPT: Max 6200W (for 4.2KW model), Max 6500W (for 6.2KW model)
- High PV input voltage range (90~450VDC)
- Built-in anti-dust kit for harsh environments
- Smart battery charge design to optimize battery life
- Dual output
- Configurable input voltage range for home appliances and personal computers via LCD setting
- Configurable battery charging current based on applications via LCD setting
- Configurable AC/Solar Charger priority via LCD setting
- Compatible with mains voltage or generator power
- Auto restart while AC is recovering
- Overload/Over temperature/Short circuit protection
- Cold start function
1.4 Basic System Architecture
The inverter/charger can be integrated into a complete running system with a generator or utility power source and PV modules. Consult with your system integrator for other possible system architectures depending on your specific requirements. This inverter is capable of powering various appliances in home or office environments, including motor-type appliances such as tube lights, fans, refrigerators, and air conditioners.

2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION -- To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION - Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for details.
- One piece of 150A fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
3. Setup (Installation)
3.1 Unpacking and Inspection
Before installation, inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items:
- The unit x 1
- User manual x 1
- DC Fuse x 1
- Ring terminal x 1
3.2 Preparation
Before connecting all wirings, remove the bottom cover by unscrewing two screws.
3.3 Mounting the Unit
Consider the following points before selecting where to install:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level in order to allow the LCD display to be read at all times.
- For proper air circulation to dissipate heat, allow a clearance of approximately 20 cm to the side and approximately 50 cm above and below the unit.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Be sure to keep other objects and surfaces as shown in the diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing two M4 or M5 screws.

3.4 Battery Connection
CAUTION: For safety and regulation compliance, it's recommended to install a separate DC over-current protector or disconnect device between the battery and inverter. A 150A fuse is provided for over-current protection.
WARNING: All wiring must be performed by qualified personnel. Use appropriate cables for battery connection to reduce risk of injury.
Recommended Battery Cable Size:
| Model | Wire Size | Cable (mm²) | Torque value (max) |
|---|---|---|---|
| 3.6KW/4.2KW/6.2KW | 1 x 2AWG | 25 | 2 Nm |
Battery Connection Steps:
- Remove insulation sleeve 18 mm for positive and negative conductors.
- Suggest putting bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Connect all battery packs as shown in the diagram below.
- Insert the battery wires flatly into the inverter's battery connectors and ensure the bolts are tightened with a torque of 2 Nm in a clockwise direction. Ensure correct polarity at both the battery and the inverter/charger, and that conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.

WARNING: Shock Hazard! Installation must be performed with care due to high battery voltage in series.
CAUTION!! Before making the final DC connection or closing the DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).
3.5 AC Input/Output Connection
CAUTION!! Before connecting to an AC input power source, install a separate AC breaker between the inverter and the AC input power source. This ensures the inverter can be securely disconnected during maintenance and fully protected from overcurrent. Recommended AC breaker: 32A for 3.6KW/4.2KW and 50A for 6.2KW. Do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by qualified personnel. Use appropriate cables for AC input connection.
Suggested Cable Requirement for AC Wires:
| Model | Gauge | Cable (mm²) | Torque Value |
|---|---|---|---|
| 3.6KW/4.2KW | 12 AWG | 4 | 1.2 Nm |
| 6.2KW | 10 AWG | 6 | 1.2 Nm |
AC Input/Output Connection Steps:
- Before making AC input/output connection, open the DC protector or disconnector first.
- Remove insulation sleeve 10mm for six conductors. Shorten phase L and neutral conductor N by 3 mm.
- Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect PE protective conductor (Ground - yellow-green), L (LINE - brown or black), and N (Neutral - blue).
- Then, insert AC output wires according to polarities indicated on the terminal block and tighten the terminal screws (L - LINE (brown or black), N - Neutral (blue)).
- Make sure the wires are securely connected.
WARNING: Be sure that the AC power source is disconnected before attempting to hardwire it to the unit.
3.6 PV Connection
CAUTION: Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.
WARNING! It's very important for system safety and efficient operation to use appropriate cables for PV module connection.
Suggested Cable Requirement for PV Wires:
| Model | Wire Size | Cable (mm²) | Torque value (max) |
|---|---|---|---|
| 3.6KW/4.2KW/6.2KW | 1 x 12AWG | 4 | 1.2 Nm |
PV Module Selection:
When selecting proper PV modules, consider the following parameters:
- Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.
| INVERTER MODEL | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Max. PV Array Open Circuit Voltage | 500Vdc | ||
| PV Array MPPT Voltage Range | 90Vdc~450Vdc | ||
CAUTION: Exceeding the maximum input voltage can destroy the unit! Check the system before wire connection.
PV Module Wire Connection Steps:
- Check the input voltage of PV array modules. The acceptable input voltage of the inverter is 120VDC - 500VDC. Ensure the maximum current load of each PV input connector is 10A.
- Disconnect the DC circuit breaker.
- Assemble provided PV connectors with PV modules. Strip 8mm of insulation from the cable ends, crimp terminals, and insert into connector housings.
- Check correct polarity of connection cable from PV modules and PV input connectors. Connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.
3.7 Final Assembly
After connecting all wirings, replace the bottom cover by screwing the two screws back in.
3.8 Communication Connection
The inverter supports Wi-Fi and GPRS cloud communication for monitoring. Use the supplied communication cable to connect to the inverter and the respective module (Wi-Fi or GPRS). Download the APP and follow the 'Wi-Fi Plug Quick Installation Guideline' or 'GPRS RTU Quick Installation Guideline' to set up the network and register. The inverter status will be shown via the mobile phone APP or computer webpage.

4. Operation
4.1 Power ON/OFF
Once the unit has been properly installed and the batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.
4.2 Operation and Display Panel
The operation and display panel is located on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.
RGB Light Indicators:
- Battery Mode: Red Light
- Utility Mode: Blue Light
- PV Mode: Purple Light
LED Indicator Messages:
| Indicator | LED State | Message |
|---|---|---|
| INV/AC | Green Solid On | Output is powered by utility in Line mode. |
| Green Flashing | Output is powered by battery or PV in battery mode. | |
| CHG | Green Solid On | Battery is fully charged. |
| Green Flashing | Battery is charging. | |
| FAULT | Red Solid On | Fault occurs in the inverter. |
| Red Flashing | Warning condition occurs in the inverter. |
Function Keys:
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
4.3 LCD Display Icons
The LCD display provides various icons to indicate input source, output information, battery status, load status, mode of operation, and mute status. These icons help in understanding the current state and performance of the inverter.
Input Source Information:
- Indicates the AC input.
- Indicates the PV input.
- Displays input voltage, input frequency, PV voltage, charger current (if PV is charging for 3.6KW models), charger power, battery voltage.
Output Information:
- Displays output voltage, output frequency, load percent, load in VA, load in Watt, and discharging current.
Battery Information:
- Indicates battery status.
Load Information:
- Indicates overload.
Mode Operation Information:
- Indicates unit connects to the mains.
- Indicates unit connects to the PV panel.
- Indicates load is supplied by utility power (AC BYPASS).
- Indicates the utility charger circuit is working.
- Indicates the DC/AC inverter circuit is working.
Mute Operation:
- Indicates unit alarm is disabled.
4.4 LCD Setting
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Use the "UP" or "DOWN" buttons to select setting programs, then press "ENTER" to confirm or "ESC" to exit. The manual provides detailed tables for various settings including output source priority, maximum charging current, AC input voltage range, battery type, auto restart options, output frequency, output voltage, GRID-tie current, and LED pattern light. Refer to pages 14-20 of the PDF manual for full details on these settings.
4.5 Display Setting
The LCD display information can be switched by pressing the "UP" or "DOWN" key. The selectable information includes input voltage, input frequency, PV voltage, charging current, charging power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, DC discharging current, and main CPU Version. Refer to pages 21-24 of the PDF manual for examples of display screens in charged and discharged states, with power less than or greater than 1kW.
4.6 Operating Mode Description
The inverter operates in various modes including Standby, Line mode, and Grid-Tie Operation. Each mode has specific conditions for input voltage, PV voltage, battery voltage, output voltage, load, and charging status. Refer to page 25 of the PDF manual for a detailed table describing each operating mode.
4.7 Battery Equalization Description
The equalization function is integrated into the charge controller to reverse the buildup of negative chemical effects like stratification and to remove sulfate crystals. This process helps maintain the overall capacity and lifespan of the battery. It is recommended to equalize the battery periodically.
How to Apply Equalization Function:
Enable the battery equalization function in LCD setting program 30. Then, apply this function by either:
- Setting the equalization interval in program 35.
- Activating equalization immediately in program 36.
When to Equalize:
In the float stage, when the set equalization interval is reached, or equalization is actively initiated, the controller will enter the Equalize stage.
Equalize Charging Time and Timeout:
During the Equalize stage, the controller supplies power to charge the battery until it reaches the battery equalization voltage. Constant-voltage regulation then maintains this voltage. The battery remains in this stage until the set equalized time is reached. If the battery voltage does not reach the equalization voltage by the end of the set time, the controller extends the equalized time. If the battery voltage is still low after the extended timeout, the controller stops equalization and returns to the float stage.
5. Maintenance
5.1 Clearance and Maintenance for Anti-Dust Kit
Every inverter comes with an anti-dust kit installed from the factory. The inverter automatically detects this kit and activates an internal thermal sensor to adjust the internal temperature. This kit prevents dust from entering the inverter, increasing product reliability in harsh environments.
Maintenance Steps:
- Loosen the screw in a counterclockwise direction on the top of the inverter.
- Remove the dustproof case and take out the air filter foam.
- Clean the air filter foam and dustproof case. After cleaning, re-assemble the dust-kit back to the inverter.
NOTICE: The anti-dust kit should be cleaned every one month.
6. Troubleshooting
6.1 Fault Reference Code
The inverter displays specific fault codes to indicate issues. Refer to the table below for common fault codes and their meanings.
| Fault Code | Fault Event | Icon on |
|---|---|---|
| 01 | Fan is locked when inverter is off. | 01 ERROR |
| 02 | Over temperature | 02 ERROR |
| 03 | Battery voltage is too high | 03 ERROR |
| 04 | Battery voltage is too low | 04 ERROR |
| 05 | Output short circuited or over temperature is detected by internal converter components. | 05 ERROR |
| 06 | Output voltage is too high. | 06 ERROR |
| 07 | Overload time out | 07 ERROR |
| 08 | Bus voltage is too high | 08 ERROR |
| 09 | Bus soft start failed | 09 ERROR |
| 51 | Over current or surge | 51 ERROR |
| 52 | Bus voltage is too low | 52 ERROR |
| 53 | Inverter soft start failed | 53 ERROR |
| 55 | Over DC voltage in AC output | 55 ERROR |
| 57 | Current sensor failed | 57 ERROR |
| 58 | Output voltage is too low | 58 ERROR |
| 59 | PV voltage is over limitation | 59 ERROR |
6.2 Warning Indicator
The inverter provides warning indicators for various conditions. Refer to the table below for warning codes, events, audible alarms, and icon flashes.
| Warning Code | Warning Event | Audible Alarm | Icon flashing |
|---|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep three times every second | 01 |
| 03 | Battery is over-charged | Beep once every second | 03 |
| 04 | Low battery | Beep once every second | 04 |
| 07 | Overload | Beep once every 0.5 second | 07 |
| 10 | Output power derating | Beep twice every 3 seconds | 10 |
| 15 | PV energy is low. | Beep twice every 3 seconds | 15 |
| E9 | Battery equalization | None | E9 |
| bP | Battery is not connected | None | bP |
6.3 General Troubleshooting
If you encounter issues with your inverter, refer to the comprehensive troubleshooting table below. This table lists common problems, their LCD/LED/Buzzer indications, possible causes, and recommended solutions.
| Problem | LCD/LED/Buzzer | Explanation / Possible cause | What to do |
|---|---|---|---|
| Unit shuts down automatically during startup process. | LCD/LEDs and buzzer will be active for 3 seconds and then complete off. | The battery voltage is too low (<1.91V/Cell) | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | No indication. | 1. The battery voltage is far too low. (<1.4V/Cell) 2. Internal fuse tripped. | 1. Contact repair center for replacing the fuse. 2. Re-charge battery. 3. Replace battery. |
| Input voltage is displayed as 0 on the LCD and green LED is flashing. | Input protector is tripped | Check if AC breaker is tripped and AC wiring is connected well. | |
| Mains exist but the unit works in battery mode. | Green LED is flashing. | Insufficient quality of AC power. (Shore or Generator) | 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS/Appliance) |
| Green LED is flashing. | Set "Solar First" as the priority of output source. | Change output source priority to Utility first. | |
| When the unit is turned on, internal relay is switched on and off repeatedly. | LCD display and LEDs are flashing | Battery is disconnected. | Check if battery wires are connected well. |
| Fault code 07 | Overload error. The inverter is overload 110% and time is up. | Reduce the connected load by switching off some equipment. | |
| Fault code 05 | Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
| Fault code 02 | Temperature of internal converter component is over 120°C. Internal temperature of inverter component is over 100°C. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
| Buzzer beeps continuously and red LED is on. | Fault code 03 | Battery is over-charged. The battery voltage is too high. | Return to repair center. Check if spec and quantity of batteries are meet requirements. |
| Fault code 01 | Fan fault | Replace the fan. | |
| Fault code 06/58 | Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) | 1. Reduce the connected load. 2. Return to repair center | |
| Fault code 08/09/53/57 | Internal components failed. | Return to repair center. | |
| Fault code 51 | Over current or surge. | Restart the unit, if the error happens again, please return to repair center. | |
| Fault code 52 | Bus voltage is too low. | ||
| Fault code 55 | Output voltage is unbalanced. |
7. Specifications
7.1 Product Properties
| Attribute | Value |
|---|---|
| Model Number | ECO II 4.2KW-PLUS |
| Output Current | 120A |
| Size | 110*334*423mm |
| Output Type | SINGLE |
| Weight | 9kg |
| Output Frequency | 50Hz-60Hz |
| Is Smart Device | Yes |
| Origin | Mainland China |
| Certification | CE |
| Battery voltage | 4.2KW 24V |
| Output Voltage | 220VAC-240VAC |
| Output Waveform | Pure sine Wave |
| Solar inverter Type | Hybrid Solar inverter |
| Communication Interface | RS232/WIFI/GPRS |
7.2 Line Mode Specifications
| INVERTER MODEL | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) | ||
| Nominal Input Voltage | 230Vac | ||
| Low Loss Voltage | 170Vac±7V (UPS); 90Vac±7V (Appliances) | ||
| Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) | ||
| High Loss Voltage | 280Vac±7V | ||
| High Loss Return Voltage | 270Vac±7V | ||
| Max AC Input Voltage | 300Vac | ||
| Nominal Input Frequency | 50Hz / 60Hz (Auto detection) | ||
| Low Loss Frequency | 40±1Hz | ||
| Low Loss Return Frequency | 42±1Hz | ||
| High Loss Frequency | 65±1Hz | ||
| High Loss Return Frequency | 63±1Hz | ||
| Output Short Circuit Protection | Circuit Breaker | ||
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) | ||
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) | ||
7.3 Inverter Mode Specifications
| INVERTER MODEL | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Rated Output Power | 3.6KW | 4.2KW | 6.2KW |
| Output Voltage Waveform | Pure Sine Wave | ||
| Output Voltage Regulation | 230Vac±5% | ||
| Output Frequency | 50Hz | ||
| Peak Efficiency | 93% | ||
| Overload Protection | 3s@≥150% load; 5s@101%~150% load | ||
| Surge Capacity | 2* rated power for 5 seconds | ||
| Nominal DC Input Voltage | 24Vdc | 48Vdc | |
| Cold Start Voltage | 23.0Vdc | 46.0Vdc | |
| Low DC Warning Voltage @ load < 50% | 22.0Vdc | 44.0Vdc | |
| Low DC Warning Voltage @ load ≥ 50% | 21.0Vdc | 42.0Vdc | |
| Low DC Warning Return Voltage @ load < 50% | 22.5Vdc | 45.0Vdc | |
| Low DC Warning Return Voltage @ load ≥ 50% | 22.0Vdc | 44.0Vdc | |
| Low DC Cut-off Voltage @ load < 50% | 20.5Vdc | 41.0Vdc | |
| Low DC Cut-off Voltage @ load ≥ 50% | 20.0Vdc | 40.0Vdc | |
| High DC Recovery Voltage | 32Vdc | 62Vdc | |
| High DC Cut-off Voltage | 33Vdc | 63Vdc | |
| No Load Power Consumption | 35W | 42W | 62W |
7.4 Charge Mode Specifications
| INVERTER MODEL | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Utility Charging Mode | |||
| Charging Algorithm | 3-Step | ||
| AC Charging Current (Max) | 100Amp (@VI/P=230Vac) | 100Amp (@VI/P=230Vac) | |
| Bulk Charging Flooded Battery Voltage | 29.2 | 58.4 | |
| Bulk Charging AGM / Gel Battery Voltage | 28.2 | 56.4 | |
| Floating Charging Voltage | 27Vdc | 54Vdc | |
| MPPT Solar Charging Mode | |||
| Max. PV Array Power | 6200W | 6200W | 6500W |
| Nominal PV Voltage | 240Vdc | 360Vdc | |
| PV Array MPPT Voltage Range | 90Vdc-450Vdc | ||
| Max. PV Array Open Circuit Voltage | 500Vdc | ||
| Max Charging Current (AC charger plus solar charger) | 120Amp | 140Amp | 120Amp |
7.5 Grid-Tie Operation Specifications
| INVERTER MODEL | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Nominal Output Voltage | 220/230/240 VAC | ||
| Feed-in Grid Voltage Range | 195~253VAC | ||
| Feed-in Grid Frequency Range | 49~51±1Hz/59~61±1Hz | ||
| Nominal Output Current | 15.7A | 18.2A | 26.9A |
| Power Factor Range | >0.99 | ||
| Maximum Conversion Efficiency (DC/AC) | 97% | ||
7.6 General Specifications
| INVERTER MODEL | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Safety Certification | CE | ||
| Operating Temperature Range | -10°C to 50°C | ||
| Storage temperature | -15°C~60°C | ||
| Humidity | 5% to 95% Relative Humidity (Non-condensing) | ||
| Dimension (D*W*H), mm | 100 x 300 x 444 | ||
| Net Weight, kg | 10 | 10.5 | 11 |
7.7 Approximate Back-up Time Table
The backup time depends on the quality, age, and type of the battery. Specifications of batteries may vary depending on different manufacturers.
| Model | Load (W) | Backup Time @ 24Vdc 100Ah (min) | Backup Time @ 24Vdc 200Ah (min) |
|---|---|---|---|
| 3.6KW / 4.2KW | 300 | 449 | 1100 |
| 600 | 222 | 525 | |
| 900 | 124 | 303 | |
| 1200 | 95 | 227 | |
| 1500 | 68 | 164 | |
| 1800 | 56 | 126 | |
| 2100 | 48 | 108 | |
| 2400 | 35 | 94 | |
| 2700 | 31 | 74 | |
| 3200 | 28 | 67 | |
| 3600 | 25 | 60 | |
| 4200 | 22 | 53 | |
| 6.2KW | 500 | 613 | 1288 |
| 1000 | 268 | 613 | |
| 1500 | 158 | 402 | |
| 2000 | 111 | 271 | |
| 2500 | 90 | 215 | |
| 3200 | 76 | 182 | |
| 3500 | 65 | 141 | |
| 4000 | 50 | 112 | |
| 4500 | 44 | 100 | |
| 5000 | 40 | 90 | |
| 6200 | 36 | 80 |
8. User Tips
- Always double-check all wiring connections (battery, AC input/output, PV) for correct polarity and secure fastening before powering on the inverter to prevent damage and ensure safe operation.
- Familiarize yourself with the LCD display icons and setting options. Understanding these will help you configure the inverter for optimal performance based on your specific application and battery type.
- Regularly clean the anti-dust kit (monthly) to ensure proper airflow and prevent overheating, especially in harsh environments.
- If you encounter any fault codes or warning indicators, refer to the troubleshooting tables in this manual immediately. Many issues can be resolved by checking connections or adjusting settings.
- For detailed information on specific settings or advanced configurations, refer to the full user manual PDF available at: ECGSOLAX Inverter User Manual (PDF).