1. Introduction
1.1 Product Overview
The SDM630-WIFI TY is a smart energy meter designed to measure and display various electrical characteristics of single-phase two-wire (1p2w), single-phase three-wire (1p3w), three-phase three-wire (3p3w), and three-phase four-wire (3p4w) supplies. It provides readings for voltage, frequency, current, power, active energy, reactive energy, imported energy, exported energy, and total harmonic distortion. Energy is measured in kWh and kVArh.
This meter supports a maximum 100A direct connection and features Wi-Fi communication for integration with Tuya's "Smart Life" APP. It includes two channels of pulse output, with configurable pulse constant, pulse width, and pulse type. Parameter configuration can be performed via the buttons on the panel, ensuring high functionality and security.
1.2 Product Features
- Multi-parameter measurement
- Direct connection up to 100A
- Support communication with AMR and SCADA systems
- Bidirectional energy metering (Import & Export)
- Wi-Fi function supported
- Support communication with Tuya "Smart Life" APP
- DIN rail mounting (35mm)
- LCD with white backlight, adjustable backlight time
1.3 Application Scenarios
The SDM630-WIFI TY is a versatile power meter suitable for power monitoring in various environments, including power systems, public utilities, industrial applications, and residential buildings. It is ideal for power transmission and distribution, AC charging piles, and solar photovoltaic systems. Its comprehensive communication capabilities make it highly suitable for real-time power monitoring systems.
2. Safety Information
This section provides critical information for your safety and to prevent damage to the product. Pay close attention to warnings and cautions.
2.1 Risk Information
Warning:
Failure to observe instructions can result in death, serious injury, or considerable material damage.
Caution:
Hazard of electric shock. Failure to take necessary safety precautions will result in death, serious injury, or considerable material damage.
2.2 Qualified Personnel
Operation of this equipment must only be performed by qualified personnel. Qualified personnel are authorized to commission, start up, ground, and label devices, systems, and circuits in accordance with Safety Regulatory standards.
2.3 Proper Handling
- Use only insulating tools.
- Do not connect while the circuit is live (hot).
- Place the meter only in dry surroundings.
- Do not mount the meter in an explosive area or expose it to dust, mildew, and insects.
- Ensure the wires are suitable for the maximum current of this meter.
- Ensure AC wires are connected correctly before activating current/voltage to the meter.
- Do not touch the clamps directly with metal, bare wire, or your bare hands to avoid electrical shock.
- Ensure the protection cover is placed after installation.
- Installation, maintenance, and repair should only be done by qualified personnel.
- Never break the seals or open the front cover, as this might influence the function and void the warranty.
- Do not drop or allow strong physical impact on the meter, as high-precision components inside may be damaged.
- This product is designed for mounting inside switchboards or cabinets on a DIN rail.
- This device must have a suitable sized Circuit Breaker feeding the Multi Function Energy Meter so it does not exceed the maximum rated current.
- The supply wiring of this device shall be suitable sized cable to match the installed circuit breaker.
- A Disconnection Device (Circuit Breaker) should be installed close to the Multi Function Energy Meter and clearly marked as such.
3. Technical Specifications
3.1 Electrical Characteristics
| Type of Measurement | Parameter | Accuracy |
|---|---|---|
| RMS (3P, 3P+N) | Voltage | ±0.2% |
| Current | ±0.2% | |
| Frequency | ±0.05% | |
| Power Factor | ±0.005 | |
| Measurement Accuracy | Active Power | ±0.5% (10%Ib-Imax) |
| Reactive Power | ±1% (10%Ib-Imax) | |
| Apparent Power | ±0.5% (10%Ib-Imax) | |
| Active Energy | Class 0.5 IEC62053-21 | |
| Class C EN50470-3:2022 | ||
| Reactive Energy | Class 2 IEC 62053-23 | |
| Data Update Rate | 15 | |
| Voltage AC (Un) | 3*230V(L-N)/400V(L-L) | |
| Voltage Range | 100-277 V AC (L-N) | |
| 100-480 V AC (L-L) | ||
| Frequency | 50/60Hz | |
| Current Input | 10A | |
| Maximum Current | 100A | |
| Minimum Current | 0.3A | |
| Starting Current (Ist) | 0.04A | |
| Transition Current (Itr) | 1A | |
| Over Current Withstand | 30Imax for 0.01S | |
| AC Voltage Withstand | 4KV/1min | |
| Impulse Voltage Withstand | 6kV - 1.2/50μS waveform | |
| Voltage Circuit Power Consumption | ≤2W/10VA | |
| Current Circuit Power Consumption | ≤0.05VA | |
| Display | LCD with white backlight | |
| Max. reading | 999999.99 kWh/kVArh |
Table: Electrical Characteristics of the SDM630-WIFI TY.
3.2 Mechanical Characteristics
| Characteristic | Value |
|---|---|
| Net Weight | ≈322g |
| IP Degree of Protection (IEC 60529) | IP51 Front Display, IP20 Whole Meter |
| Dimensions (DxHxW) | 100*72*66mm |
| Mounting | DIN Rail 35mm |
| Material of Meter Case | Self-extinguishing UL 94 V-0 |
Table: Mechanical Characteristics of the SDM630-WIFI TY.
3.3 Environmental Characteristics
| Characteristic | Value |
|---|---|
| Mechanical Environment | M1 |
| Operating Temperature | -40°C ~ +70°C |
| Storage Temperature | -40°C ~ +80°C |
| Operation Humidity | ≤90% Non-condensing |
| Storage Humidity | ≤95% Non-condensing |
| Pollution Degree | II |
| Altitude | ≤2000m |
| Vibration | 10Hz ~ 50Hz, IEC 60068-2-6 |
Table: Environmental Characteristics of the SDM630-WIFI TY.
3.4 Electromagnetic Compatibility
| Characteristic | Standard |
|---|---|
| Electrostatic Discharge | IEC 61000-4-2 |
| Immunity to Radiated Fields | IEC 61000-4-3 |
| Immunity to Fast Transients | IEC 61000-4-4 |
| Surge (Impulse) Immunity | IEC 61000-4-5 |
| Conducted Immunity | IEC 61000-4-6 |
| Immunity to Magnetic Fields | IEC 61000-4-8 |
| Immunity to Voltage Dips | IEC 61000-4-11 |
| Radiated Emissions | CISPR 32 |
| Conducted Emissions | CISPR 32 |
Table: Electromagnetic Compatibility of the SDM630-WIFI TY.
3.5 Safety
| Characteristic | Value |
|---|---|
| Measurement Category | Per IEC61010-1 CAT III |
| Installation Category | CAT III |
| Over-voltage Category | CAT III |
| Protective Class | II |
Table: Safety Specifications of the SDM630-WIFI TY.
3.6 Interface & Pulse Output
| Characteristic | Value |
|---|---|
| Interface | Wi-Fi 2.4G |
| RF Band | 2.412-2.484GHz |
| Max. RF Power | <17 dBm |
| Wi-Fi Protocol | 802.11 b/g/n |
| Wi-Fi Range | Up to 30m/100ft indoors and 50m/160ft outdoors (Depends on local conditions) |
| Pulse Output 1 | Configurable |
| Pulse Type (Output 1) | Import Active Energy, Total Active Energy, Export Active Energy, Import Reactive Energy, Total Reactive Energy, Export Reactive Energy (default) |
| Pulse Constant (Output 1) | 0.01, 0.1, 1, 10, 100, 400 (default) Imp/kWh |
| Pulse Width (Output 1) | 200, 100 (default), 60mS |
| Pulse Output 2 | Non-configurable |
| Pulse Type (Output 2) | Total Active Energy |
| Pulse Constant (Output 2) | 400Imp/kWh |
| Pulse Width (Output 2) | 100mS |
Table: Interface and Pulse Output Specifications.
3.7 Dimensions
The dimensions of the SDM630-WIFI TY meter are 100mm (Height) x 72mm (Width) x 66mm (Depth).
4. Installation & Setup
4.1 Mounting
The SDM630-WIFI TY is designed for 35mm DIN rail mounting.
- Select a 35mm-wide DIN rail. Pull down the back-end clip on the meter to unlock the mounting mechanism.
- Align the upper slot of the meter's DIN rail groove onto the DIN rail, ensuring full contact.
- Engage the lower slot of the DIN rail groove onto the DIN rail until audibly seated.
- Push up the back-end clip to lock the meter firmly onto the DIN rail.
4.2 Wiring Diagram
Refer to the diagram below for correct wiring configurations for different system types.
4.3 Wiring Guide
| Terminal | Measurement Connection | Specification |
|---|---|---|
| 1~8 | Strip Length | 12-13mm |
| Screw | M5 | |
| Rigid/Supple | 4-25mm² (11~4AWG) | |
| Tightening Torque | 3.5Nm | |
| Model | PH2 | |
| B, A, B2, A2 | Strip Length | 5-6mm |
| Rigid/Supple | 0.5-1.5mm² (26~14AWG) | |
| Tightening Torque | 0.4Nm | |
| Model | PH0 |
Table: Wiring Guide for SDM630-WIFI TY Terminals.
5. Operation
5.1 Installation Display
After correct wiring and powering on, the meter will enter the normal measurement state. The initial screen will light up all display segments for a display check, followed by firmware information and a self-test. The default display shows Total Active Energy in kWh.
5.2 Button Functions
The meter has four keys on the panel. Operations are categorized into two types:
- Long press: Press and hold the key for more than 3 seconds.
- Short press: Release the key within 1 second after pressing.
| Button | Short Click | Long Press (3s) |
|---|---|---|
| U/I (Up/Return) | Return to previous menu (Display mode) | Return to the previous menu (Setup mode) |
| M (Menu/Up) | Previous page or increase value | Display mode |
| P (Page/Down) | Next page or decrease value | Setup mode |
| E (Enter/Exit) | Move to right side | Enter Setup mode / Confirm setting |
Table: SDM630-WIFI TY Button Functions.
5.3 Measurements
Press the 'M' or 'P' buttons to cycle through various measurement displays:
- Voltage and Current: Phase to neutral voltage (L1, L2, L3), Phase to phase voltage (L1-L2, L2-L3, L3-L1), Current of each phase (L1, L2, L3), Phase to neutral voltage THD%, Phase current THD%.
- Frequency, Power Factor, and Demand: Total Frequency and Power Factor, Power Factor of each phase, Maximum current demand of each phase, Maximum total power demand.
- Power: Instantaneous Active Power (kW), Instantaneous Reactive Power (kVAr), Instantaneous Volt-amps (kVA), Total kW, kVAr, kVA.
- Energy, Wi-Fi: Total active energy (kWh), Total reactive energy (kVArh), Imported active energy (kWh), Exported active energy (kWh), Imported reactive energy (kVArh), Exported reactive energy (kVArh), Network Configuration State, Wi-Fi State, Upload Data State, Wi-Fi Module Firmware Version Number.
5.4 Setup Mode
The meter's settable parameters are password protected. Long pressing the 'E' button accesses the setup mode. Some menu items require a four-digit number entry, while others require selection from menu options.
5.4.1 Menu Option Selection
- Use the 'M' and 'P' buttons to scroll through options.
- Long press 'E' to confirm your selection.
- If an item flashes, it can be selected by 'M' and 'P' buttons.
- After selecting an option, long press 'E' to confirm.
- After parameter setting, press 'U/I' to return to a previous menu, then use 'M' and 'P' for more menu selection.
- After setting up, press 'U/I' repeatedly to return to the home screen.
5.4.2 Number Entry Procedure
In setting mode, some screens require number or password entry, typically from left to right.
- When the number flashes, use 'M' and 'P' buttons to select the number.
- Short press 'E' to confirm the digit setting and move to the next.
- After setting the last digit, long press 'E' to confirm the setting.
- Press 'U/I' to return to a previous menu.
5.4.3 Setting Menu Options
- Password: Default 1000.
- Pulse Type: Options include various active and reactive energy types (Import/Export kWh/kVArh). Default: EXPORT kVArh.
- Pulse Constant: Options from 0.01 to 400Imp/kWh. Default: 400Imp/kWh.
- Pulse Width: Options 200, 100, 60mS. Default: 100mS.
- Demand Interval Time: Options 0, 5, 8, 10, 15, 20, 30, 60min. Default: 60min.
- Backlight Time Setting: Options ON, 5, 10, 30, 60, 120, OFF. Default: 60.
- System Type Setting: Options 3P4W, 3P3W, 1P2W. Default: 3P4W.
- CLR Max Demand Setting: Clear maximum demand.
- Password Setting: Range 0000-9999. Default: 1000.
- NET SET Mode: Enter or Exit network setting mode.
6. Connecting to the "Smart Life" APP
6.1 Tuya Smart Life App
6.1.1 Initial State Description
The meter is not pre-configured with a Wi-Fi network. Upon first power-on, it automatically enters network configuration mode, displaying the Wi-Fi status interface (similar to Figure 1 in the manual).
6.1.2 Adding a Device
Automatic Discovery: Open the Tuya "Smart Life" APP. If a "Device to be added" pop-up appears, click "Add".
Manual Addition: If no pop-up appears, click the "+" icon on the APP's homepage, select "Add Device", and tap the corresponding meter icon to enter the manual addition process.
6.1.3 Wi-Fi Network Configuration
From the Wi-Fi list in the APP, select your network name, enter the password, and confirm. The meter will connect to the network and enter the Wi-Fi connection state.
6.1.4 Post-Connection Confirmation
After successful network connection, the meter enters data reporting mode. A checkmark icon will appear next to the device name in the APP, indicating a successful connection. Click "Finish" to access the device details page, where real-time parameters uploaded by the meter will be displayed.
6.1.5 Device Management
Viewing Devices: The list of added devices is on the APP's homepage. Click a device icon to view detailed parameters. Swipe left or right to check phase-specific information (Phase A, B, C).
Deleting Devices: On the device details page, click the "..." icon, then "Device Management", select the meter, and remove it from the APP.
6.2 EASTRON Cloud
The process for connecting to EASTRON Cloud is similar to the Tuya Smart Life App. Ensure the meter is not pre-configured with a Wi-Fi network. If previously connected to another device, unbind it first. Then, add the device via the APP, configure the Wi-Fi network, and confirm the connection.
7. Maintenance
The SDM630-WIFI TY is designed for reliable operation with minimal maintenance. Adhere to the "Proper Handling" guidelines in the Safety Information section to ensure longevity and accurate performance. Regularly check for dust accumulation in dry environments and ensure all connections remain secure. Do not attempt to open or repair the device yourself, as this will void the warranty and poses a safety risk. Any maintenance or repair should only be performed by qualified personnel.
8. Troubleshooting & FAQ
8.1 Frequently Asked Questions
- Q: What is the difference between MID and non-MID?
- A: MID (Measuring Instruments Directive) is a European Commission directive for electrical meters used for billing purposes. MID approval is required for such applications in Europe. The CT ratio can be set only once for CT meters with MID approval.
- Q: Where can I get a Datasheet?
- A: A datasheet can be downloaded from the official Eastron website: www.eastrongroup.com.
- Q: What is the warranty of your products?
- A: The product comes with an 18-month warranty.
- Q: Can you offer Modbus protocol instruction/Modbus register map?
- A: Yes, we can. Please contact us for this information.
Image: FAQ section with common questions and answers.
9. User Tips
No specific user reviews or tips were provided for this product. However, based on general usage of smart energy meters, consider the following:
- Ensure your Wi-Fi network is stable and within the meter's range for consistent data reporting to the app.
- Regularly check the app for energy consumption patterns to identify potential energy savings.
- Keep the meter's firmware updated through the app, if available, to benefit from new features and improvements.
- For accurate readings, ensure the wiring is done precisely according to the provided diagrams and specifications.
10. Warranty & Support
The Eastron SDM630-WIFI TY Smart Energy Meter comes with an 18-month warranty from the date of purchase. For any questions, technical support, or warranty claims, please contact Eastron Electronic Co., Ltd. directly.
Contact Information:
Zhejiang Eastron Electronic Co., Ltd.
No.52, DongJin Rd. Jiaxing, Zhejiang, 314001, China
Tel: 400-996-9296
Fax: +86-573-83698883
Email: sales@eastrongroup.com
Website: www.eastrongroup.com
A detailed user manual in PDF format is also available for download. You can find it on the official Eastron website or by following the link provided in the product description: User manual (PDF).