1. Introduction
1.1 Purpose
This manual describes the assembly, installation, operation, and troubleshooting of the Daxtromn AGH-8.2KW Hybrid Solar Inverter. Please read this manual carefully before installation and operation. Keep this manual for future reference.
1.2 Scope
This manual provides safety and installation guidelines as well as information on tools and wiring. This multi-function inverter/charger combines the functions of an inverter, solar charger, and battery charger to offer uninterruptible power support. Its comprehensive LCD display offers user-configurable and easy-accessible button operation for settings such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.
2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION: To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION: Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for details.
- One piece of 150A fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
3. Product Overview
3.1 Features
- Pure sine wave inverter
- Configurable input voltage range for home appliances and personal computers via LCD setting
- Configurable battery charging current based on applications via LCD setting
- Configurable AC/Solar Charger priority via LCD setting
- Compatible with mains voltage or generator power
- Auto restart while AC is recovering
- Overload/Over temperature/short circuit protection
- Smart battery charger design for optimized battery performance
- Cold start function
3.2 Basic System Architecture
The following illustration shows the basic application for this inverter/charger. It includes the following devices for a complete running system: Generator or Utility, and PV modules. Consult with your system integrator for other possible system architectures depending on your requirements. This inverter can power all kinds of appliances in home or office environments, including motor-type appliances such as tube lights, fans, refrigerators, and air conditioners.
3.3 Product Components
The Daxtromn AGH-8.2KW Hybrid Solar Inverter features a robust design with clear indicators and accessible ports. Key specifications include 8200W Rated Power, 160A Max Charge Current, 5400W*2 Max PV Array Power, and 90-500V Max PV Input.
The inverter charger specifications detail the model name AGH-8.2KW, operating temperature range of -10 to 50°C, PV input characteristics (e.g., max PV voltage 500Vdc, MPPT range 90-450Vdc, max PV input power 5400W*2), Grid/AC output (nominal output voltage 220/230/240Vac), two load output power (full load 8200W, maximum main load 8200W), AC input (nominal operating frequency 50/60Hz), and battery specifications (battery voltage range 48Vdc, maximum battery current 190A).
The product overview diagram below identifies the various components and ports of the inverter.
- LCD display
- Status indicator
- Charging indicator
- Fault indicator
- Touch Function buttons
- Power on/off switch
- AC input
- Main output
- Second output
- PV1 and PV2 input
- WIFI communication/RS-232 port
- Battery communication/RS-485 port
- Battery input
- Anti dust kit
The inverter's physical design is shown in the product display images, and its dimensions are 500x390x136mm with a net weight of 14.5kg.
4. Installation
4.1 Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items:
- The unit x 1
- User manual x 1
- Ring terminal x 1
- Mc4 terminal head x 2
4.2 Preparation
Before connecting all lines, remove the screws under the machine and remove the bottom cover plate.
4.3 Mounting the Unit
Consider the following points before selecting where to install:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level in order to allow the LCD display to be read at all times.
- For proper air circulation to dissipate heat, allow a clearance of approximately 20 cm to the side and approximately 50 cm above and below the unit.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Make sure that other objects and surfaces are left with enough space from the machine to ensure adequate heat dissipation and that there is enough room to remove the wires.
CAUTION: SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing two screws. It's recommended to use M4 or M5 screws.
4.4 Battery Connection
CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to typical amperage in below table as required fuse or breaker size.
WARNING! All wiring must be performed by qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable as below.
Recommended battery cable size:
| Model | Wire Size | Cable (mm²) | Torque value (max) |
|---|---|---|---|
| 8.2KW/10.2KW | 1 x 2AWG | 25 | 2 Nm |
Please follow below steps to implement battery connection:
- Remove insulation sleeve 18 mm for positive and negative conductors.
- Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Connect all battery packs as shown in the connection diagram (Figure 1).
- Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charger is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.
WARNING: Shock Hazard Installation must be performed with care due to high battery voltage in series.
CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
4.5 AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 63A for 8.2KW/10.2KW.
CAUTION!! There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires:
| Model | Gauge | Cable (mm²) | Torque Value |
|---|---|---|---|
| 8.2KW/10.2KW | 10 AWG | 6 | 1.2 Nm |
Please follow below steps to implement AC input/output connection:
- Before making AC input/output connection, be sure to open DC protector or disconnector first.
- Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
- Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure to connect PE protective conductor (➔Ground (yellow-green)), L (➔LINE (brown or black)), N (➔Neutral (blue)) first.
WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
- Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws. L (➔LINE (brown or black)), N (➔Neutral (blue)).
- Make sure the wires are securely connected.
4.6 PV Connection
CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check manufacturer of air conditioner if it's equipped with time-delay function during installation. Otherwise, this inverter/charger will trigger overload fault and cut off output to protect your appliance but sometimes it still causes internal damage to the air conditioner.
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for PV wires:
| Model | Wire Size | Cable (mm²) | Torque value (max) |
|---|---|---|---|
| 8.2KW/10.2KW | 1 x 10AWG | 6 | 1.2 Nm |
PV Module Selection: When selecting proper PV modules, please be sure to consider below parameters:
- Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
| INVERTER MODEL | 8.2KW/10.2KW |
|---|---|
| Max. PV Array Open Circuit Voltage | 500Vdc |
| PV Array MPPT Voltage Range | 90Vdc~450Vdc |
Take 250Wp PV module as an example. After considering above two parameters, the recommended module configurations are listed as below table.
| Solar Panel Spec. (reference) | SOLAR INPUT (Min in serial: 6 pcs, max. in serial: 13 pcs) | Q'ty of panels | Total input power |
|---|---|---|---|
| 250Wp, Vmp: 30.1Vdc, Imp: 8.3A, Voc: 37.7Vdc, Isc: 8.4A, Cells: 60 | 6 pcs in serial | 6 pcs | 1500W |
| 8 pcs in serial | 8 pcs | 2000W | |
| 12 pcs in serial | 12 pcs | 3000W | |
| 13 pcs in serial | 13 pcs | 3250W | |
| 12 pieces in serial and 3 sets in parallel | 36 pcs | 8200W | |
| 10 pieces in serial and 4 sets in parallel | 40 pcs | 10200W |
PV Module Wire Connection:
Step 1: Check the input voltage of PV array modules. The acceptable input voltage of the inverter is 120VDC - 500VDC. Please make sure that the maximum current load of each PV input connector is 10A.
CAUTION: Exceeding the maximum input voltage can destroy the unit!! Check the system before wire connection.
Step 2: Disconnect the DC circuit breaker.
Step 3: Assemble provided PV connectors with PV modules by following the steps below. Components for PV connectors and Tools:
| Component | Image |
|---|---|
| Female connector housing | ![]() |
| Female terminal | ![]() |
| Male connector housing | ![]() |
| Male terminal | ![]() |
| Crimping tool and spanner | ![]() |
Cable preparation and connector assembly process: Strip one cable 8 mm on both end sides and be careful NOT to nick conductors.
Step 4: Check correct polarity of connection cable from PV modules and PV input connectors. Then, connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.
4.7 Final Assembly
After connecting all wirings, please put the bottom cover back by screwing two screws.
4.8 Communication Connection
1. Wi-Fi cloud communication (option): Please use the supplied communication cable to connect to the inverter and Wi-Fi module. Download the APP and install it from the APP store, and refer to the "Wi-Fi Plug Quick Installation Guideline" to set up the network and register. The inverter status would be shown by mobile phone APP or webpage of a computer.
2. GPRS cloud communication (option): Please use the supplied communication cable to connect to the inverter and GPRS module, and then apply external power to the GPRS module. Download the APP and install it from the APP store, and refer to the "GPRS RTU Quick Installation Guideline" to set up the network and register. The inverter status would be shown by mobile phone APP or webpage of a computer.
3. Battery communication: The communication between the battery and the inverter can be realized through the battery communication interface, so that the inverter and the lithium battery can exchange information (Baud rate: 9600).
4. Lithium battery and inverter connection: Use power cables and communication cables for lithium batteries and inverters to connect. Note: For lithium battery and inverter positive and negative positions, check the correct installation. The RJ45 connector of the communication cable connects to the BMS port of the inverter, and the other RJ45 connector connects to the RS485 port of the lithium battery. Before connecting, make sure that the lithium battery and inverter are turned off. (It is recommended to install a circuit breaker for the power cables of the lithium battery and the inverter battery interface. Otherwise, a spark may occur.)
The lithium battery communication cable interface and connection diagram are shown below:
In order to communicate with the lithium battery BMS, you should press the "ENTER" button for a long time, and set the battery type as "LIB-485" in program 05. Then select the matching battery protocol in Program 43.
5. Operation
5.1 Power ON/OFF
Once the unit has been properly installed and the batteries are connected well, simply press the On/Off switch (located on the button of the case) to turn on the unit.
5.2 Operation and Display Panel
The operation and display panel, shown below, is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.
LED Indicator:
| Indicator | LED Indicator | Messages |
|---|---|---|
| INV/AC | Green Solid On | Output is powered by utility in Line mode. |
| Green Flashing | Output is powered by battery or PV in battery mode. | |
| CHG | Green Solid On | Battery is fully charged. |
| Green Flashing | Battery is charging. | |
| FAULT | Red Solid On | Fault occurs in the inverter. |
| Red Flashing | Warning condition occurs in the inverter. |
Function Keys:
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
LCD Display Icons: The LCD display provides various icons to indicate input source information, configuration program and fault information, output information, and battery information. These icons help in understanding the current status and operation of the inverter.
Load Information: The 'OVER LOAD' icon indicates an overload condition.
Mode Operation Information: Icons indicate connection to mains, PV panel, load supplied by utility power, utility charger circuit working, DC/AC inverter circuit working, and mute operation (unit alarm disabled).
5.3 LCD Setting
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Press "UP" or "DOWN" button to select setting programs. And then, press "ENTER" button to confirm the selection or ESC button to exit. The manual provides detailed tables for various settings including:
- Program 00: Exit setting mode (Escape, One-button restore setting options)
- Program 01: Output source priority (Utility first, Solar first, SBU priority, MKS priority)
- Program 02: Maximum charging current (Configurable from 10A to 160A)
- Program 03: AC input voltage range (Appliances, UPS)
- Program 05: Battery type (AGM, Flooded, User-Defined, LIB-485)
- Program 06: Auto restart when overload occurs
- Program 07: Auto restart when over temperature occurs
- Program 09: Output frequency (50Hz, 60Hz)
- Program 10: Output voltage (220V, 230V, 240V)
- Program 11: Maximum utility charging current
- Program 12: Setting voltage point back to utility source when selecting "SBU priority" or "Solar first"
- Program 13: Setting voltage point back to battery mode when selecting "SBU priority" or "Solar first"
- Program 16: Charger source priority (Solar first, Solar and Utility, Only Solar)
- Program 18: Alarm control
- Program 19: Auto return to default display screen
- Program 20: Backlight control
- Program 22: Beeps while primary source is interrupted
- Program 23: Overload bypass
- Program 25: Record Fault code
- Program 26: Bulk charging voltage (C.V voltage)
- Program 27: Floating charging voltage
- Program 29: Low DC cut-off voltage
- Program 30: Battery equalization
- Program 31: Battery equalization voltage
- Program 33: Battery equalized time
- Program 34: Battery equalized timeout
- Program 35: Equalization interval
- Program 36: Equalization activated immediately
- Program 37: GRID-tie operation
- Program 38: GRID-tie current
- Program 39: Led pattern light
- Program 41: Dual output
- Program 42: Enter the dual output functional voltage point
- Program 43: Lithium battery protocol (PYLON, PACE)
- Program 44: Delayed grid access
- Program 45: Maximum Second Load
5.4 Display Setting
The LCD display information will be switched in turns by pressing "UP" or "DOWN" key. The selectable information is switched as below order: input voltage, input frequency, PV voltage, charging current, charging power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, load in Watt, DC discharging current, main CPU Version. Examples of charged and discharged states, and power levels are provided in the manual.
5.5 Operating Mode Description
The inverter supports various operating modes, including Standby mode, Line mode, and Grid-Tie Operation. The LCD display will show different information depending on the active mode and power conditions (e.g., input voltage, PV voltage, battery voltage, output voltage, load in Watt/KVA, charging status).
5.6 Battery Equalization Description
The equalization function is added to the charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize the battery periodically.
How to Apply Equalization Function: You must enable the battery equalization function in monitoring LCD setting program 30 first. Then, you may apply this function in the device by either one of the following methods: 1. Setting equalization interval in program 35. 2. Active equalization immediately in program 36.
When to Equalize: In the float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter the Equalize stage.
Equalize charging time and timeout: In the Equalize stage, the controller will supply power to charge the battery as much as possible until the battery voltage raises to the battery equalization voltage. Then, constant-voltage regulation is applied to maintain the battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until the setting battery equalized time is arrived.
However, in the Equalize stage, when the battery equalized time is expired and the battery voltage doesn't rise to the battery equalization voltage point, the charge controller will extend the battery equalized time until the battery voltage achieves the battery equalization voltage. If the battery voltage is still lower than the battery equalization voltage when the battery equalized timeout setting is over, the charge controller will stop equalization and return to the float stage.
5.7 Mains and Lithium Battery Activation Function
- After 90s of mains power connection to the inverter, the machine is connected to the mains and starts to work.
- The inverter is in lithium battery mode (item 05 is LIP or LIL). After the mains is connected, if the battery is not connected, the mains activation function is automatically enabled.
6. Troubleshooting
This section provides guidance for common issues. If problems persist, contact service personnel.
6.1 Fault Reference Code
| Fault Code | Fault Event | Icon on |
|---|---|---|
| 01 | Fan is locked when inverter is off. | 01 ERROR |
| 02 | Over temperature | 02 ERROR |
| 03 | Battery voltage is too high | 03 ERROR |
| 04 | Battery voltage is too low | 04 ERROR |
| 05 | Output short circuited or over temperature is detected by internal converter components. | 05 ERROR |
| 06 | Output voltage is too high. | 06 ERROR |
| 07 | Overload time out | 07 ERROR |
| 08 | Bus voltage is too high | 08 ERROR |
| 09 | Bus soft start failed | 09 ERROR |
| 51 | Over current or surge | 51 ERROR |
| 52 | Bus voltage is too low | 52 ERROR |
| 53 | Inverter soft start failed | 53 ERROR |
| 55 | Over DC voltage in AC output | 55 ERROR |
| 57 | Current sensor failed | 57 ERROR |
| 58 | Output voltage is too low | 58 ERROR |
| 59 | PV voltage is over limitation | 59 ERROR |
The battery fault code is added in lithium battery mode:
| Fault code | Fault event | Fault condition |
|---|---|---|
| 02 | The battery temperature is too high Procedure | Lithium battery charging battery temperature ≥65°C. The discharge temperature of the lithium battery is higher than 70°C. |
| 03 | The battery voltage is too high Procedure | Lithium battery maximum single cell voltage >3.65V. Total voltage of lithium battery >54.6V (48V lithium battery). |
| 04 | The battery voltage is too low Procedure | Minimum voltage of a lithium battery cell<2.71V; Lithium battery total voltage <40.4V (48V lithium battery). |
6.2 Warning Indicator
| Warning Code | Warning Event | Audible Alarm | Icon flashing |
|---|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep three times every second | 01◯ |
| 03 | Battery is over-charged | Beep once every second | ☒ 03 |
| 04 | Low battery | Beep once every second | 04◯ |
| 07 | Overload | Beep once every 0.5 second | 07◯ |
| 10 | Output power derating | Beep twice every 3 seconds | 10◯ |
| 15 | PV energy is low. | Beep twice every 3 seconds | ☒ 15 |
| E9 | Battery equalization | None | ☒ E9 |
| bP | Battery is not connected | None | bP◯ |
Added a battery warning code in lithium battery mode:
| Warning code | Warning event | Warning condition |
|---|---|---|
| 04 | The battery voltage is too low | Minimum voltage of a lithium battery cell<2.85V; Lithium battery total voltage<42V (48V lithium battery). |
| 05 | The battery voltage is too high | Lithium battery maximum single cell voltage >3.55V; Total voltage of lithium battery >54V (48V lithium battery). |
| 06 | The battery is low warning | Remaining battery capacity ≤10% |
7. Maintenance
7.1 Clearance and Maintenance for Anti-Dust Kit
Every inverter is already installed with an anti-dust kit from the factory. The inverter will automatically detect this kit and activate an internal thermal sensor to adjust the internal temperature. This kit also keeps dust from your inverter and increases product reliability in harsh environments.
Step 1: Please loosen the screw in the counterclockwise direction on the top of the inverter.
Step 2: Then, the dustproof case can be removed, and the air filter foam taken out as shown in the chart.
Step 3: Clean the air filter foam and dustproof case. After clearance, re-assemble the dust-kit back to the inverter.
NOTICE: The anti-dust kit should be cleaned from dust every one month.
8. Specifications
8.1 Table 1 Line Mode Specifications
| INVERTER MODEL | 8.2KW | 10.2KW |
|---|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) | |
| Nominal Input Voltage | 230Vac | |
| Low Loss Voltage | 170Vac±7V (UPS); 90Vac±7V (Appliances) | |
| Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) | |
| High Loss Voltage | 280Vac±7V | |
| High Loss Return Voltage | 270Vac±7V | |
| Max AC Input Voltage | 300Vac | |
| Nominal Input Frequency | 50Hz / 60Hz (Auto detection) | |
| Low Loss Frequency | 40±1Hz | |
| Low Loss Return Frequency | 42±1Hz | |
| High Loss Frequency | 65±1Hz | |
| High Loss Return Frequency | 63±1Hz | |
| Output Short Circuit Protection | Circuit Breaker | |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) | |
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) | |
Output power derating: When AC input voltage drops to 170V, the output power will be derated.
8.2 Table 2 Inverter Mode Specifications
| INVERTER MODEL | 8.2KW | 10.2KW |
|---|---|---|
| Rated Output Power | 8.2KW | 10.2KW |
| Output Voltage Waveform | Pure Sine Wave | |
| Output Voltage Regulation | 230Vac±5% | |
| Output Frequency | 50Hz | |
| Peak Efficiency | 93% | |
| Overload Protection | 3s@≥150% load; 5s@101%~150% load | |
| Surge Capacity | 2* rated power for 5 seconds | |
| Nominal DC Input Voltage | 48Vdc | |
| Cold Start Voltage | 46.0Vdc | |
| Low DC Warning Voltage @ load < 50% | 44.0Vdc | |
| Low DC Warning Voltage @ load ≥ 50% | 42.0Vdc | |
| Low DC Warning Return Voltage @ load < 50% | 45.0Vdc | |
| Low DC Warning Return Voltage @ load ≥ 50% | 44.0Vdc | |
| Low DC Cut-off Voltage @ load < 50% | 41.0Vdc | |
| Low DC Cut-off Voltage @ load ≥ 50% | 40.0Vdc | |
| High DC Recovery Voltage | 62Vdc | |
| High DC Cut-off Voltage | 63Vdc | |
| No Load Power Consumption | 70W | 75W |
8.3 Table 3 Two Load Output Power
| INVERTER MODEL | 8.2KW | 10.2KW |
|---|---|---|
| Full Load | 8200W | 10200W |
| Maximum Main Load | 8200W | 10200W |
| Second Load Range | 1640W~5740W | 2040W~7140W |
| Main Load Cut Off Voltage | 52VDC | |
| Main Load Return Voltage | 54VDC | |
8.4 Table 4 Charge Mode Specifications
| INVERTER MODEL | 8.2KW | 10.2KW |
|---|---|---|
| Utility Charging Mode | ||
| Charging Algorithm | 3-Step | |
| AC Charging Current (Max) | 140Amp | 140Amp |
| Bulk Charging Flooded Battery Voltage | 58.4 | |
| AGM / Gel Battery Voltage | 56.4 | |
| Floating Charging Voltage | 54Vdc | |
| MPPT Solar Charging Mode | ||
| Max. PV Array Power PV1 Channel | 5400W | 5400W |
| Max. PV Array Power PV2 Channel | 5400W | 5400W |
| IMax.PV PV1 Channel | 18A | |
| IMax.PV PV2 Channel | 18A | |
| Nominal PV Voltage | 360Vdc | |
| PV Array MPPT Voltage Range | 90Vdc-450Vdc | |
| Max. PV Array Open Circuit Voltage | 500Vdc | |
| Max Charging Current (AC charger plus solar charger) | 160Amp | |
8.5 Table 5 Grid-Tie Operation
| INVERTER MODEL | 8.2KW | 10.2KW |
|---|---|---|
| Nominal Output Voltage | 220/230/240 VAC | |
| Feed-in Grid Voltage Range | 195~253VAC | |
| Feed-in Grid Frequency Range | 50±1Hz/60±1Hz | |
| Nominal Output Current | 35.6A | 44.3A |
| Power Factor Range | >0.99 | |
| Maximum Conversion Efficiency (DC/AC) | 98% | |
8.6 Table 6 General Specifications
| INVERTER MODEL | 8.2KW | 10.2KW |
|---|---|---|
| Safety Certification | CE | |
| Operating Temperature Range | -10°C to 50°C | |
| Storage temperature | -15°C~60°C | |
| Humidity | 5% to 95% Relative Humidity (Non-condensing) | |
| Dimension (D*W*H), mm | 500*390*136mm | |
| Net Weight, kg | 14.5 | 14.7 |
9. User Tips
- This inverter supports grid-tie operation, allowing it to feed electricity back into the grid. Refer to Program 37 in the LCD settings for configuration.
- The inverter is CE certified, ensuring it meets European safety, health, and environmental protection requirements.
10. Warranty and Support
For detailed warranty information and technical support, please refer to the official user manual PDF provided by Daxtromn. This document contains comprehensive information regarding product guarantees, service procedures, and contact details for support.
The user manual PDF can be referenced at: Daxtromn AGH-8.2KW Hybrid Solar Inverter User Manual (PDF)
11. Appendix: Approximate Back-up Time Table
| Model | Load (W) | Backup Time @ 48Vdc 100Ah (min) | Backup Time @ 48Vdc 200Ah (min) |
|---|---|---|---|
| 8.2KW/10.2KW | 500 | 613 | 1288 |
| 1000 | 268 | 613 | |
| 1500 | 158 | 402 | |
| 2000 | 111 | 271 | |
| 2500 | 90 | 215 | |
| 3200 | 76 | 182 | |
| 3500 | 65 | 141 | |
| 4000 | 50 | 112 | |
| 4500 | 44 | 100 | |
| 5000 | 40 | 90 | |
| 6200 | 36 | 80 | |
| 7200 | 32 | 70 | |
| 8200 | 28 | 60 | |
| 9200 | 24 | 50 | |
| 10200 | 20 | 40 |
Note:
- Backup time depends on the quality of the battery, age of battery, and type of battery. Specifications of batteries may vary depending on different manufacturers.
- The final interpretation right of this product belongs to the company.