1. Important Safety Information
Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
DANGER: Electrical Hazard
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. The addition of the electrical hazard symbol indicates an electrical hazard exists which will result in personal injury if the instructions are not followed.
WARNING: Personal Injury Hazard
Indicates a potentially hazardous situation which, if not avoided, can result in death or serious injury. This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, can result in minor or moderate injury.
NOTICE
Used to address practices not related to physical injury. The safety alert symbol shall not be used with this signal word.
Please Note:
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.
2. Product Overview
The TAIYEDQ TAC4321CT is a three-phase DIN rail mountable multifunction energy meter. It supports wireless communication via WiFi and integrates with the Tuya platform for remote access via a mobile APP. This meter measures and analyzes various power parameters including voltage, current, four-quadrant power, power factor, and harmonic content. It also provides measurements for multiple electric energy parameters such as two-way active energy, reactive energy, and monthly/daily electricity consumption statistics. It is suitable for power monitoring in photovoltaic inverters, new energy electricity consumption analysis, and real-time power monitoring in various environments. The device features high stability, long life, RS485 communication (Modbus RTU), a large LCD screen, and touch-sensitive keys for local operation. Password protection ensures data security.
2.1. Product Features
- Supports external current transformers (5A/1A output) with reverse connection correction.
- Supports external voltage transformer access (minimum 30V input).
- DIN Rail mounting, standard 4 modulus width.
- Touch button design for improved operability.
- Measures voltage, current, active power, reactive power, apparent power, power factor, phase angle.
- Provides analytical data for total harmonic content of voltages and currents.
- Statistical data and local storage: two-way power, demand, monthly (12 months) and daily (31 days) electricity consumption.
- Dual-timing function for meter startup and load running time.
- RS485 communication (up to 38400bps, Modbus RTU).
- WiFi wireless communication.
- One optocoupler pulse output interface with configurable parameters.
- LCD refresh time of 1 second, with manual or automatic scroll display.
2.2. Product Views




3. Setup and Installation
3.1. Installation Dimensions
The TAC4321CT meter is designed for DIN Rail mounting. Ensure adequate space for installation and wiring.

Width: 72mm, Height: 100mm, Depth: 66mm (including DIN rail clip).
3.2. Wiring Diagrams
Proper wiring is critical for the safe and accurate operation of the meter. Refer to the detailed wiring diagrams below for various configurations. Ensure all connections are secure and follow local electrical codes.

This diagram illustrates various wiring configurations including 3-phase 4-wire (3CT/3PT+3CT), 3-phase 3-wire (2CT/2PT+2CT), 2-phase 3-wire (L+L+N, 2CT), 1-phase 2-wire (L+N, 1CT/3CT), auxiliary power (AC/DC), RS485 communication, and pulse output. Terminal specifications for wire size and torque are provided.
3.3. Network Configuration (WiFi Setup)
To utilize the smart features of your energy meter, you need to connect it to your WiFi network using the Tuya Smart APP.
- Power On: After completing the physical wiring, power on the meter.
- Connect Phone to WiFi: Ensure your smartphone is connected to a 2.4GHz WiFi network. The meter does not support 5GHz WiFi.
- Open Tuya Smart APP: Launch the Tuya Smart APP on your smartphone.
- Add Device: Click the 'Add Device' button (usually a '+' icon) and select 'Smart Meter (WiFi)' from the 'Energy' category.
- Confirm WiFi Details: Verify that the WiFi hotspot name and password displayed in the app match your 2.4GHz network.
- Proceed: Follow the on-screen prompts in the Tuya Smart APP to complete the network distribution process.
Tip: During network configuration, it is advisable to enable Bluetooth on your mobile phone to improve the smoothness of the connection process.
This video demonstrates the process of adding the energy meter to the Tuya Smart APP, connecting it to WiFi, and navigating the app interface to view measurement data and settings.
4. Operating Instructions
4.1. Meter Startup
After the TAC4321CT series products are properly wired and connected to the power supply, the meter will initiate a self-test process. The LCD screen will display a sequence of information:
- Full Screen Characters: All LCD segments will light up briefly.
- Software Version: Displays the software version number (e.g., 'Soft 13 21.00').
- Self-Test Result: Displays the self-test result (e.g., 'PASS').
4.2. LCD Display Area Description
The LCD provides comprehensive information about the meter's status and measurements. Key indicators include:
- Grid Type Icon: Represents the current measurement type (e.g., 3-phase 4-wire).
- Maximum Demand Icon: Indicates maximum demand readings.
- Direction Icon: Shows import and export energy flow.
- Status Indicator: General status of the meter.
- Unit Icon: Unit of measurement data (e.g., kWh, V, A).
- Battery/Lock Icon: Displays battery status and if the device is locked.
- Measured Values: Numerical readings for various parameters.
- Digital I/O Status Icon: Status of digital input/output.
- Multi-Tariff Icon: Indicates the active tariff segment (e.g., T1, T2).
- Warning Status Icon: Alerts to potential issues.
- Channel Indicator: For multiple measurement channels.
- Quadrant Indicator: Shows the quadrant of the current load.
4.3. Button Functions
The meter has four control buttons for navigation and settings:
| Button | Label | Short Press Function | Press 3 Seconds Function |
|---|---|---|---|
| 1 | U/I Esc | Page scroll for parameters (voltage, current); Exit/Return in settings. | Enter auxiliary display screen. |
| 2 | PF/HZ ▲ | View power factor, max demand; Scroll up in settings. | None |
| 3 | P ▼ | View power information; Scroll down in settings. | None |
| 4 | E ↵ | View energy data, system time; Move cursor right in settings. | Enter setting mode; Confirm in settings. |
4.4. Display Screens
The meter cycles through various display screens showing real-time data. Examples include:
- Voltage (L-N, L-L): Displays phase-to-neutral and phase-to-phase voltages.
- Current: Displays current for each phase (L1, L2, L3).
- Voltage/Current THD: Total Harmonic Distortion for voltage and current.
- Power Factor & Frequency: Total power factor and system frequency.
- Active/Reactive/Apparent Power: Per phase and total power readings.
- Energy Readings: Total active energy, import/export active energy, total reactive energy, import/export reactive energy.
- Tariff Energy: Energy consumed under different tariff segments (T1, T2, T3, T4).
- Date & Time: Current system date and time.
4.5. Multi-Tariffs Function
The meter supports a multi-tariffs function, allowing time-sharing measurement of electricity. The 24-hour day is divided into several time periods, each assigned a specific rate number. The meter accumulates electricity consumption for each period and stores it accordingly. Up to 8 starting time points and 4 tariff segments (T1, T2, T3, T4) are supported.

Example: T1 (06:10-12:00), T2 (12:00-18:00), T3 (18:00-21:00), T4 (21:00-06:10 next day).
4.6. Parameter Settings
To access and modify meter parameters, follow these general steps:
- Enter Password Input Mode: From the main display screen, press Button 4 for 3 seconds.
- Enter Password: Use Buttons 2 and 3 to change flashing digits, Button 4 to move the cursor. Press Button 4 for 3 seconds to confirm. Default password is '0000'.
- Navigate Settings Menu: Once in the settings menu, use Buttons 2 and 3 to scroll through options and Button 4 to enter a selected submenu. Button 1 exits a submenu or returns to the main display.
Key parameters that can be configured include:
- Communication Parameters: Modbus address (1-247, default 1), Baud rate (1200-38400bps, default 9600bps), Parity bit (None, Even, Odd), Stop bit (1 or 2).
- CT/PT Ratios: Primary and secondary values for Current Transformers (CT1, CT2) and Voltage Transformers (PT1, PT2).
- System Parameters: Current direction correction (forward/reverse), System type (1P2W, 2P3W, 3P3W, 3P4W), User password, Reset max demand, Historical electricity consumption log.
- Pulse Output: Pulse output type (total active, import active, etc.), Pulse output rate (0.001-100 kWh/kvarh per pulse), Pulse output width (60, 100, 200ms).
- Demand Parameters: Demand interval period (0-60 minutes), Sliding time (1-demand interval period).
- Time Parameters: Backlight time (on/off, 5-120 minutes), Automatic scroll display time (0-60 seconds), RTC Date and Time, Tariff time.
5. Maintenance
The TAIYEDQ TAC4321CT energy meter is designed for reliable operation with minimal maintenance. To ensure its longevity and accuracy:
- Keep Clean: Periodically wipe the meter's exterior with a soft, dry cloth. Do not use abrasive cleaners or solvents.
- Check Connections: Ensure all wiring connections remain tight and secure. Loose connections can lead to inaccurate readings or operational issues.
- Environmental Conditions: Operate the meter within its specified environmental conditions (temperature, humidity) to prevent damage.
- Firmware Updates: Check the Tuya Smart APP or manufacturer's website for any available firmware updates to ensure optimal performance and security.
6. Troubleshooting
If you encounter issues with your energy meter, refer to the following troubleshooting guide:
6.1. Error Codes
| LCD Display | Fault Description |
|---|---|
| Err-01 | The battery voltage is too low |
| Err-02 | The WiFi module fault |
| Err-03 | 1. The battery voltage is too low 2. The WiFi module fault |
6.2. Alarm Prompts
| LCD Display | Alarm Definition |
|---|---|
| Alarm Icon (triangle with exclamation) | Occurs over voltage, over current or power exceeds the limit |
6.3. General Troubleshooting
- No Display/No Power:
- Check the main power supply to the meter.
- Verify all auxiliary power wiring connections are secure.
- Ensure the rated voltage is within the meter's operating range.
- WiFi Connection Issues:
- Ensure your WiFi network is 2.4GHz. The meter does not support 5GHz.
- Check if the WiFi signal strength is adequate at the meter's location.
- Verify the WiFi password entered in the Tuya Smart APP is correct.
- Try resetting the meter's WiFi module (press Button 4 for 3 seconds on the WiFi status screen).
- Ensure your phone's Bluetooth is enabled during setup.
- Inaccurate Readings:
- Verify CT and PT ratios are correctly configured in the meter settings.
- Check all current and voltage wiring connections for tightness and correct polarity.
- Ensure the actual current being measured is not significantly lower than the CT's rated current (e.g., for a 100A CT, actual current should be >20A for accuracy).
- Consider potential inherent errors in current transformers.
- Meter Unresponsive:
- Try power cycling the meter (turn off power, wait 30 seconds, turn on).
- If the issue persists, contact technical support.
7. Specifications
| Category | Parameter | Value |
|---|---|---|
| Electrical Characteristics | Rate Voltage (Un) | 230 Vac (L-N) / 400 Vac (L-L) |
| Frequency | 45 to 65 Hz | |
| Measured Voltage Range | 30 to 300 Vac (L-N), 30 to 500 Vac (L-L) | |
| Max Operating Current | 5A (instrument itself), 50A/100A/150A/200A (with transformer) | |
| Power Supply | AC (80-300 Vac / 100-420 Vdc) | |
| Power Consumption | < 4VA/0.5W | |
| Measurement Accuracy | Voltage, Current, Power Factor | Class 1 (IEC 61557-12) |
| Active Energy | Class 1 (IEC 62053-21) | |
| Reactive Energy | Class 2 (IEC 62053-23) | |
| Frequency | Class 0.2 | |
| Display | Display Type | LCD |
| Communication | Interfaces | 2-wire RS485 (Modbus RTU), WiFi |
| Baud Rate | 1200 to 38400 bps (default 9600 bps) | |
| Max. Bus Loading | 64 devices | |
| Mechanical | Dimensions (W x H x D) | 72 x 100 x 66 mm |
| Mounting Position | DIN Rail mounting | |
| IP Degree of Protection | IP51 (front display), IP30 (meter body) | |
| Material | UL 94 V-0 | |
| Environmental | Operating Temperature | -25 to +55 ℃ |
| Storage Temperature | -40 to +80 ℃ | |
| Humidity | < 90%, non-condensing |
8. User Tips
- Function Display Limitations: Be aware that some functions may only be displayed on the meter's screen, the Tuya APP, or via Modbus. If a function isn't visible on the meter or app, check Modbus for its display.
- Current Transformer Accuracy: For accurate readings, ensure the actual measured current is not significantly lower than the rated current of the transformer. For example, if using a 100A CT, the actual current should ideally be above 20A to minimize errors. Current transformers inherently have some measurement errors.
- CT Aperture: The equipped current transformer has an aperture of 16mm. Consider purchasing a closed-type transformer for specific installation needs.
- User Manual PDF: A detailed user manual in PDF format is available for further reference.
9. Warranty and Support
For warranty information, technical support, or service inquiries, please contact your original seller or the manufacturer directly. Keep your purchase receipt or order details handy as proof of purchase.