ECGSOLAX ECG-LVM12K-SP

Contents

ECGSOLAX 12KW Hybrid Solar Inverter User Manual

Model: ECG-LVM12K-SP

1. Introduction

This manual provides detailed instructions for the assembly, installation, operation, and troubleshooting of the ECGSOLAX ECG-LVM12K-SP Hybrid Solar Inverter. Please read this manual carefully before installation and operation, and keep it for future reference.

1.1 Scope

This document offers safety guidelines and installation instructions, along with information regarding necessary tools and wiring.

1.2 Target Group

This document is intended for qualified persons and end users. Tasks that do not require any particular qualification can also be performed by end users. Qualified persons must have the following skills:

  1. Knowledge of how an inverter works and was operated.
  2. Training in how to deal with the dangers and risks associated with installing and using electrical devices and installations.
  3. Training in the installation and commissioning of electrical devices and installations.
  4. Knowledge of the applicable standards and directives.
  5. Knowledge of and compliance with this document and all safety information.

1.3 Product Description

The ECGSOLAX Hybrid Solar Inverter is an energy storage device designed for photovoltaic, energy storage battery, grid, and load management. It provides stable, safe, and clean electrical energy for home, commercial, and industrial applications, meeting diverse energy needs.

1.4 Product Features

  • Supports multiple types of energy storage batteries, including lead-acid and lithium-ion batteries.
  • Provides single-phase and split-phase pure sine wave output.
  • Allows adjustment of each phase voltage within the 100~130Vac range.
  • Features two photovoltaic inputs with MPPT (Maximum Power Point Tracking) functionality, achieving up to 99.9% efficiency. Each channel supports a maximum current of 22A.
  • Offers two output modes: mains bypass and inverter output, ensuring uninterrupted power supply.
  • Includes four charging modes: PV only, Mains priority, PV priority, and mains/PV hybrid charging.
  • Supports timed battery charging and discharge.
  • Energy-saving mode to reduce no-load energy loss.
  • Equipped with various protection functions to safeguard photovoltaic panels, batteries, loads, and the controller.
  • Capacitive smart touch large screen for intuitive menu operation and convenient parameter setting.
  • Stores 256 event records and 1024 days of historical data.
  • Built-in Bluetooth and WiFi interface for native cloud platform access and automatic time synchronization.
ECGSOLAX 12KW Hybrid Solar Inverter with key features: 12000W, 48V Battery Voltage Auto, 500VDC Max PV Input, MPPT 200A Max Charging Current, Max Parallel 6 Units, Split Phase 110V/240V
Figure 1: Key Features of the ECGSOLAX 12KW Hybrid Solar Inverter.
Pure Sine Wave output illustration showing a computer, refrigerator, TV, and water heater connected to the inverter. Text states: 'Has the same voltage waveform as the grid, provide high quality Ac power with higher efficiency, stable output and high compatibility'.
Figure 2: Pure Sine Wave Output and Appliance Compatibility.

2. Setup

2.1 Product Overview

The inverter features a capacitive touchscreen and LED indicator on the front. The bottom panel includes various ports for connections.

Diagram showing the front and bottom view of the ECGSOLAX inverter with numbered components. Front: 1. Capacitive touchscreen, 2. LED indicator. Bottom: 3. Terminal protective cover, 4. ON/OFF boat type switch, 5. Photovoltaic input (1/1), 6. Battery port (positive), 7. Battery port (negative), 8. Dry contacts points, 9. CAN/RS485-2 port, 10. RS485-1 port, 11. USB-B port, 12. Grounding screws, 13. AC output port, 14. AC input port, 15. Parallel communication port.
Figure 3: Product Overview and Component Identification.

2.2 Unpacking and Inspection

Before installation, carefully inspect the unit for any damage. The package should contain:

  • The inverter unit (x1)
  • User manual (x1)
  • Ring terminals (x2)
  • Parallel cable (x1)
  • Spare screws (x4)
  • Warranty card (x1)
  • Plastic Expansion Screws (x2)
  • Stainless Steel Expansion Screws (x2)

2.3 Select the Mounting Location

This product is for indoor use only (IP20 protection level). Consider the following factors:

  • Mount on a solid wall.
  • Install at eye level.
  • Ensure adequate space must be provided for the inverter to dissipate heat.
  • The ambient temperature should be between -10°C and 55°C (14°F to 131°F) to ensure optimal operation.

DANGER:

  • The inverter should not be installed in proximity to highly flammable substances.
  • The inverter should not be installed in potential explosive areas.
  • The inverter and lead-acid batteries should not be installed in an enclosed space.

WARNING:

  • The inverter must not be installed in an area exposed to direct sunlight.
  • Do not install or utilize the inverter in a humid environment.
Diagram showing recommended clearances for inverter installation, with 200mm clearance on sides and 500mm clearance above and below for heat dissipation.
Figure 4: Recommended Mounting Clearances (200mm side, 500mm top/bottom).

2.4 Install the Inverter

NOTICE:

When operating the equipment in areas with poor air quality, dust particles may clog the air filter. Please regularly remove and clean the air filter to ensure proper internal airflow within the inverter. Failure to do so may cause the inverter to overheat, trigger overtemperature protection, disrupt power supply operation, and shorten the inverter's service life.

2.5 Wiring

All wiring should be performed by a professional electrical or mechanical engineer and must comply with local electrical safety standards.

2.5.1 System Connection Diagram

The inverter acts as an energy conversion device, connecting photovoltaic modules, mains/generator, battery, and various AC loads (refrigerators, TVs, etc.) to provide a comprehensive energy solution.

System connection diagram showing solar panels, a generator, and utility power feeding into the ECGSOLAX inverter. The inverter is connected to a battery (51.2V LiFePO4) and outputs to various home appliances like a refrigerator, laptop, washing machine, TV, and air conditioner. Labels indicate DC, AC, and LINE connections.
Figure 5: Typical System Connection Diagram.

2.5.2 Split-phase Mode (Default)

The inverter operates in split-phase mode by default, providing 120Vac (L-N) and 240Vac (L-L) output. The output voltage can be adjusted between 100V and 130V via the settings menu.

NOTICE:

  • Users can change the output voltage through the settings menu.
  • The output voltage can be set within the range of 100V to 130V.
Detailed wiring diagram for a split-phase system. It shows solar panels connected to the inverter, which is also connected to a battery bank and a utility grid. The inverter outputs to an AC load. The diagram includes labels for L1, L2, N, PE, CAN, DC breaker, and AC breaker.
Figure 6: Split-Phase Wiring Diagram.

2.5.3 Cable and Circuit Breaker Selection

Ensure appropriate cable sizes and circuit breakers are used for safe and optimal operation. Refer to the table below for specifications:

Connection TypeModelOutput ModeMax. CurrentWire DiameterCircuit Breaker
Photovoltaic InputECG-LVM12K-SPN/A22A4mm²/10 AWG2P-32A
AC InputECG-LVM12K-SPSplit Phase63A (L1/L2/N)25mm²/4AWG (L1/L2/N)3P-63A
Single Phase63A (L1/N)25mm²/4AWG (L1/N)2P-63A
BatteryECG-LVM12K-SPN/A200A120mm²/250kcmil2P-250A
AC OutputECG-LVM12K-SPSplit Phase63A (L1/L2/N)25mm²/4AWG (L1/L2/N)3P-63A
Single Phase63A (L1/N)25mm²/4AWG (L1/N)2P-63A

NOTICE:

The wire diameter is for reference only. If the distance between the PV array and the inverter or between the inverter and the battery is long, using a thicker wire will reduce the voltage drop and improve the performance of the system.

2.5.4 AC Input and Output Cables

DANGER:

  • Before connecting AC inputs and outputs, the circuit breaker must be disconnected to avoid the danger of electric shock and no live operation.
  • Check that the cable used is sufficient to meet the requirements, too thin, poor-quality cables can be a serious safety hazard.

2.5.5 Battery Wiring

DANGER:

  • Before connecting the battery, ensure the circuit breaker is turned off to eliminate the risk of electric shock. Never operate the system while it is powered.
  • Verify that the battery's positive and negative terminals are correctly connected. Reversed polarity may cause permanent damage to the inverter.
  • Confirm that the cables used meet the required specifications. Using undersized or poor-quality cables poses significant safety hazards.

2.5.6 Photovoltaic Wiring

DANGER:

  • Before connecting the PV, the circuit breaker must be disconnected to avoid the danger of electric shock, and live operation is not allowed.
  • Make sure that the open circuit voltage of the PV module in series does not exceed the maximum open circuit voltage of the inverter (500V), otherwise the inverter may be damaged.

2.5.7 Dry Contact Cable

Use a small screwdriver to push the arrow back in the direction it is pointing, then insert the communication cable (0.2 to 1.5mm²) into the dry junction port.

2.5.8 Grounding

Ensure that the ground terminal is securely connected to the ground busbar. The ground cable should be no less than 4mm² in diameter and as close to the ground point as possible.

2.6 Final Installation and Startup

After confirming that all wiring is secure and each wire is connected to the correct terminal, restore the terminal protective cover to its original position.

  1. Close the circuit breaker of the battery.
  2. Press the boat-shaped ON/OFF switch at the bottom of the inverter. The screen and indicator lights will light up, indicating that the inverter has been activated.
  3. Close the circuit breakers of photovoltaic, AC input and AC output in turn.
  4. Start the load one by one in order of increasing power.

2.7 Parallel Installation and Wiring

Up to six inverters can be connected in parallel. Ensure correct, firm, and reliable connection of the parallel communication line (packaging accessories).

Wiring Guidelines for Parallel Systems:

  • PV Wiring: When connecting multiple inverters in parallel, each inverter must be connected to a separate PV array or PV source. A single PV source must not be shared by multiple inverters, and within one inverter, PV1 and PV2 must not be connected to the same PV source.
  • Battery Cable Connection: In both split-phase and three-phase parallel configurations, all inverters must be connected to the same battery system. Connect BAT+ to BAT+ and BAT- to BAT- across all units. Before powering on the system, ensure that the wiring is correct, and that cable length and diameter are consistent, to avoid abnormal output operation in the parallel system.
  • AC OUT Connection:
    • Split-Phase Parallel Wiring: When connecting in split-phase parallel mode, connect all inverters' L1 terminals together, all L2 terminals together, N to N, and PE to PE. Ensure all connections are correct and that wiring length and conductor size are consistent before powering on, to prevent incorrect wiring that could cause abnormal operation of the parallel system.
    • Three-Phase Parallel Wiring: For three-phase parallel systems, connect all inverters' N to N and PE to PE. Inverters assigned to the same phase must have their L lines connected together. Do not connect L lines between different phases.
  • AC IN Connection: For split-phase parallel systems, connect N to N and PE to PE. L1 terminals of all inverters must be connected to the L1 phase, and L2 terminals must be connected to the L2 phase. Ensure all connections are correct and that wiring lengths and wire gauges are uniform to prevent abnormal operation of the parallel system. Do not connect multiple AC input sources simultaneously, as this may damage the inverters or other connected equipment. AC input sources must maintain consistent and unique configurations. For three-phase parallel systems, connect N to N and PE to PE. L lines of inverters in the same phase must be connected together. Do not connect L lines from different phases.
  • Parallel Communication Cable Wiring: Communication cables should be connected according to the split-phase or three-phase parallel configuration. Each inverter must follow a one-in-one-out daisy-chain connection: the male connector (OUT) of one device must be connected to the female connector (IN) of the next. Reversing this order is not allowed. All communication cables must be securely fastened with screws to prevent loosening or poor contact, which could lead to system malfunctions or equipment damage.

Attention for Parallel Systems:

  1. Before powering on and lighting up the screen, verify that all wiring is correct according to the wiring diagram above to avoid system faults.
  2. Ensure all connections are firmly secured to prevent disconnection or poor contact, which may cause abnormal system behavior.
  3. When connecting the AC output to the load, ensure correct wiring according to the electrical load requirements to avoid damage.
  4. The AC output voltage must be set consistently across all units, or configured only on the master. In parallel mode, the master unit's voltage setting will override those of the slave units to ensure consistency. This parameter can only be configured in standby mode.
  5. By default, the inverter operates in standalone mode. If parallel or three-phase mode is required, configure the AC output mode via the LCD screen. The setting procedure is as follows: Power on one unit at a time while keeping the others off. Configure the AC output mode based on the system's actual operation requirements. After setting up the unit, turn it off and proceed with the next unit in the same way. Once all units are configured, turn them on simultaneously to enter normal operation.
  6. After system startup, verify that the output voltage is correct before connecting the load.

3. Operating

3.1 LED Indication

Indicator LightColorsDescription
AC/INVGreenSteady on: Mains bypass output
Blinking: Inverter output
CHARGEGreenSteady on: Charging is complete
Blinking: Charging is underway
FAULTRedBlinking: A fault occurs

3.2 LCD Display and Operation

The inverter features a capacitive smart touch large screen for intuitive menu operation and convenient parameter setting.

3.2.1 Home Page

The home page displays the current time and status bar. Icons indicate battery BMS communication, WiFi connection, Bluetooth connection, and equipment communication status. Green indicates normal connection, gray indicates no connection. A red icon indicates equipment failure.

3.2.2 PV Data Interface

Long press the PV icon for about 1 second to enter the detailed PV data interface. This interface shows daily and total PV power generation, along with real-time PV voltage, current, and power for PV1 and PV2 (if supported).

3.2.3 Grid Data Interface

Long press the grid icon for about 1 second to enter the detailed grid data interface. For split-phase systems, it displays real-time current and voltage for L1 and L2. For single-phase, it shows grid current and voltage. The top section shows daily and total grid-connected energy.

3.2.4 Battery Data Interface

Long press the battery icon for about 1 second to enter the detailed battery data interface. This interface displays battery capacity percentage, real-time voltage, current, and charge status. "FULL" indicates a fully charged battery.

3.2.5 Load Data Interface

Long press the load icon for about 1 second to enter the detailed load data interface. For split-phase inverters, it shows current, active power, and apparent power for L1 and L2, plus overall load rate. For single-phase, it shows load current, active power, apparent power, and load rate. "OVERLOAD" icon appears during overload conditions.

3.2.6 Operating Status and Main Menu

Press and hold the inverter icon in the center of the screen to enable the manual shutdown function. Once shut down, the inverter will stop output, and "MANUAL OFF" will be displayed in the Device State section. To restore output, press and hold the inverter icon again.

3.2.7 Data Interface

The data interface provides access to real-time data, statistical data, historical data, event records, and control functions.

3.2.8 Control Function

Control functions include immediate equalization charge, time setting, clearing events, clearing status, clearing historical records, restoring factory settings, and reset. All functions, except time setting, are executed by selecting "Confirm".

3.2.9 Time-Slot Charging and Discharging Settings

In the time-based charging/discharging configuration interface, a green indicator in the "Enable Charge" or "Enable Discharge" section signifies that parameter modification is enabled. Users can configure the start and end times for each period by selecting the ">" button. If time-based charging/discharging is disabled, all configured time settings will be disregarded.

3.2.10 Battery Settings

When "Setting Parameters" or "Type Parameters" is highlighted in green, it indicates that the interface is in editable mode, and parameters can be configured via drop-down lists or input fields. Settings include battery type (USE, SLD, FLD, GEL, LiFePO4, NCM), battery system voltage (fixed at 48V), nominal battery capacity (1-9999AH), temperature compensation, switch to mains/battery SOC capacity, inverter/mains switching voltage, maximum allowed charge current, stop charge current, stop charge SOC, equalize charge timeout, and SOC low alarm.

3.2.11 System Settings

System parameters include AC output mode (Mains priority, Inverter priority), AC output voltage (100-130V), frequency (45-65Hz), parallel mode (Single, Single-phase master, Three-phase master, Two-phase 208V master, Slave), parallel phase (A, B, C Phase), battery charging mode (Hybrid), charge current limit (SET, BMS, INV), mains charging current limit (0-100A), BMS protocol (0-30), PV output priority (Charge priority), NPE ground shorting function, energy saving mode, automatic restart after overload/over-temperature, buzzer alarm, mode shift alerted, and overload bypass function.

3.3 Communication Ports

The inverter provides several communication ports for monitoring and control:

  • USB-B Port: The user can use the upper computer software through this port to read the device parameters. If you need the upper computer software installation package, you can download it from the official website or contact us to obtain the installation package. USB-B and RS485 communication ports cannot be used at the same time.
  • RS485-1 Port: Port RS485-1 is a data expansion port.
  • CAN/RS485-2 Port: The RS485-2 port is used to connect BMS to Lithium-ion batteries. If the inverter needs to communicate with a lithium-ion battery BMS, please contact us to obtain the communication protocol or upgrade the inverter firmware accordingly. If using a standard RJ45 network cable, check the pin configuration. In most cases, pins 1 and 2 must be disconnected for proper operation.
  • Dry Contact Port: The dry contact ports serve two primary functions: Switch signal output and Remote generator start/stop control. If you need to use the remote start/stop function of a generator with dry contacts, make sure that the generator has an ATS and supports remote start/stop.
  • Bluetooth: The inverter has a built-in Bluetooth module, which can be connected to the EnerWise APP (EnerWise APP can be downloaded from the website or contact us to obtain the installation package.)
  • WIFI: Connect to the EnerWise Cloud Platform after configuring the device through the mobile APP.

4. Maintenance

To maintain optimal long-term performance, it is recommended to perform the following checks twice a year:

  1. Ensure that airflow around the inverter is not obstructed, and remove any dirt or debris from the radiator.
  2. Inspect all exposed wiring for damage caused by sun exposure, friction with surrounding objects, dry rot, or insect or rodent activity. Repair or replace any damaged wiring as necessary.
  3. Verify that the display and instructions are consistent with the actual operation of the equipment. Pay attention to any faults or incorrect displays, and take corrective action if necessary.
  4. Check all terminals for signs of corrosion, insulation damage, high temperature, or burning/discoloration, and tighten the terminal screws.
  5. Check for dirt, nesting insects, and corrosion. Clean the insect netting regularly as needed.
  6. If the lightning arrester has failed, replace it promptly to prevent lightning damage to the inverter or other user equipment.

DANGER:

Prior to any inspection or operation, it is essential to disconnect the inverter from all power sources and ensure that internal capacitors are fully discharged to prevent the risk of electric shock.

5. Troubleshooting

This section provides solutions for common issues. For persistent faults, contact a qualified service center.

Fault CodeMeaningReasonsSolutions
/Screen not displayingNo power input, or device switch is off.Check whether the battery circuit breaker or PV circuit breaker is closed. The switch is in the "ON" state.
01Battery voltage lowThe battery voltage is lower than the value set in the "battery under-voltage warning voltage" parameter.Charge the battery until the battery voltage is higher than the value set in the parameter.
03Battery no connectThe battery is not connected, or the lithium battery BMS is in discharge protection mode.1. Check that the battery is reliably connected; 2. Check that the battery's circuit breaker is closed; 3. Make sure the BMS of the lithium-ion battery can communicate normally.
04Battery undervoltage stops dischargingThe battery voltage is lower than the value set in Over Discharge Voltage.1. Manual reset: Turn off the power and restart 2. Automatic reset: Charge the battery so that the battery voltage is higher than the value set in the parameter "Overcharge Return Voltage"
06Battery charge overvoltage protectionThe battery is overvoltage.Manually turn off the power and restart it. Check whether the battery voltage exceeds the limit. If so, discharge the battery until the voltage is below the over.
13Bypass over load protectionThe bypass output power or output current is overloaded for a certain period of time.Reduce the load power and restart the device. Refer to item 11 in Protection Features for more details.
14Inverter overload protectionThe output power or output current of the inverter is overloaded within a certain period.Reduce the load power and restart the device. Refer to item 11 in Protection Features for more details.
19PV radiator over-temperature protectionThe temperature of the photovoltaic radiator exceeds 80°C for 3s.When the temperature of the radiator cools below the over-temperature recovery temperature, normal charging and discharging are resumed.
20Inverter radiator over-temperature protectionThe temperature of the inverter heat sink exceeds 80°C for 3s.When the temperature of the radiator cools below the over-temperature recovery temperature, normal charging and discharging are resumed.
21Fan failureThe hardware has detected a fan failure.After shutting down the system, manually start the fan and check for any foreign objects obstructing it.
26Inverter AC output fed back to bypass AC outputThe AC output relay is stuck.Restart manually, if the fault occurs again after restarting, you will need to contact after-sales service to repair the machine.
27Mains input phase errorPhase mismatch detected between AC input and output.Ensure that the AC input phase configuration matches the AC output phase configuration. For example, if the output is configured for split-phase operation, the input must also be in split-phase mode.

For a complete list of fault codes and their descriptions, please refer to the full PDF user manual.

6. Specifications

FeatureSpecification
Model Number
ModelECG-LVM12K-SP
Inverter Output
Rated Output Power12000 W
Max. Peak Power24000 W
Rated Output Voltage100V-130V/200V-260V (single/split phase)
On-load Motor Capability6HP
Rated Frequency50/60Hz
Output WaveformPure sine wave
Switching Time10ms (typical value)
Battery
Battery TypeLithium-ion battery/lead-acid battery/User-defined
Rated Battery Voltage48Vdc
Voltage Range40~60Vdc
Max. PV Charging Current200A
Max. Mains/Generator Charging Current100A
Max. Hybrid Charging Current200A
PV Input
MPPT Way Number2
Max. Input Power9000 W + 9000 W
Max. Input Current22A+22A
Max. Open Circuit Voltage500Vdc+500Vdc
MPPT Operating Voltage Range125~425Vdc
Mains/Generator Input
Input Voltage Range90~140Vac
Input Frequency Range50/60Hz
Bypass Overload Current63A
Efficiency
MPPT Tracks Efficiency99.9%
Max. Efficiency of Battery Inverter92%
Universal
Size450*620*142mm
Weight23.5kg
Level of ProtectionIP20, for indoor use only
Ambient Temperature-10 to 55°C, >45°C derated
Noise<60dB
Cooling MethodSmart cooling
Warranty Time3 years
Communication
Built-in InterfaceRS485/ CAN /USB/ Dry contact
Communication ModuleWIFI/Bluetooth
Certified
Safety StandardsUL STD.1741, FCC SDOC Part 15B

7. User Tips

  • When experiencing issues with battery pairing, double-check the communication settings and ensure the battery management system (BMS) is correctly configured and communicating with the inverter. Refer to the "Communication Ports" section for details on RS485-2 and Bluetooth connections.
  • For optimal charging from solar panels, ensure your PV array is correctly sized and connected, as the inverter efficiently charges from panels.

8. Warranty and Support

The ECGSOLAX 12KW Hybrid Solar Inverter comes with a 3-year warranty. For detailed warranty terms and conditions, please refer to the official user manual PDF.

Warranty Exclusions:

The standard warranty does not cover machine issues caused by:

  • The product is beyond the warranty period (except for extended warranty services agreed upon by both parties).
  • Failures or damages resulting from failure to follow the product instructions or installation and maintenance requirements, or caused by operating, storing, or using the product in an environment that does not meet the specified conditions such as improper installation distance, inadequate ventilation, or failure to use waterproof caps correctly.
  • Unauthorized disassembly, repair, or modification of the product.
  • Products obtained through unauthorized channels.
  • Failures or damages caused by unforeseeable circumstances, human factors, or force majeure events, such as storms, floods, lightning strikes, overvoltage, insect infestation, or fire.
  • Unauthorized design changes, modifications, or part replacements.
  • Intentional damage, defacement, permanent markings, or theft.
  • Normal wear and tear.
  • Failure to use the product in accordance with applicable safety standards (e.g., VDE standards).
  • Any other failures or damages not caused by product quality issues.
  • Damage incurred during transportation (including scratches on the casing caused by movement of the packaged product during transit).
  • Rust or corrosion of the enclosure due to exposure to harsh environmental conditions.

For further assistance or to report a fault, please contact your local dealer or service center.

A comprehensive user manual in PDF format is available for download: View User Manual (PDF)