1. Introduction
1.1 Purpose
This manual describes the assembly, installation, operation and troubleshooting of this unit. Please read this manual carefully before installations and operations. Keep this manual for future reference.
1.2 Scope
This manual provides safety and installation guidelines as well as information on tools and wiring.
1.3 Features
- Pure sine wave inverter
- Configurable input voltage range for home appliances and personal computers via LCD setting
- Configurable battery charging current based on applications via LCD setting
- Configurable AC/Solar Charger priority via LCD setting
- Compatible to mains voltage or generator power
- Auto restart while AC is recovering
- Overload/ Over temperature/ short circuit protection
- Smart battery charger design for optimized battery performance
- Cold start function
- RS485 is used to communicate with BMS and adjust the charging current of inverter according to battery demand
- It can work with or without batteries
- Intelligent fan speed adjustment, which adjusts the fan speed according to temperature, load and charging current
- Built-in MPPT, operating voltage range 55V~450V, open circuit voltage 500Voc
- RGB lamp, which displays different colors according to inverter status
- WIFI remote monitoring (optional)
- Offline upgrade function, firmware can be upgraded through COM port
- Grid-connected
- Built-in anti-dust kit for harsh environment
- In battery-free mode, PV systems deliver a better user experience when powering loads
- Equipped with lithium battery activation function
1.4 Basic System Architecture
The following illustration shows basic application for this inverter/charger. It also includes following devices to have a complete running system:
- Generator or Utility.
- PV modules
Consult with your system integrator for other possible system architectures depending on your requirements. This inverter can power all kinds of appliances in home or office environment, including motor-type appliances such as tube light, fan, refrigerator and air conditioner.

1.5 Product Overview

The operation and display panel, shown in the diagram below, is on the front panel of the inverter. It includes three indicators, four function keys and an LCD display, indicating the operating status and input/output power information.

Key Components:
- LCD display
- Status indicator
- Charging indicator
- Fault indicator
- Function buttons
- Power on/off switch
- AC input
- Main output
- Second output
- Battery input
- PV input
- Anti dust kit
- Battery communication/RS-485 port
- WIFI communication/RS-232 port
2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries and all appropriate sections of this manual.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
CAUTION: Only qualified personnel can install this device with battery. NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.
- One piece of 150A fuse is provided as over-current protection for the battery supply.
GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
- NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
3. Setup (Installation)
3.1 Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside of package:
- The unit x 1
- User manual x 1
3.2 Preparation
Before connecting all lines, remove the screws under the machine and remove the bottom cover plate.
3.3 Mounting the Unit
Consider the following points before selecting where to install:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level in order to allow the LCD display to be read at all times.
- For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below the unit.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Make sure that other objects and surfaces are left with enough space from the machine to ensure adequate heat dissipation and that there is enough room to remove the wires.
WARNING: SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing two screws. It's recommended to use M6 screws.
3.4 Battery Connection
CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to typical amperage in below table as required fuse or breaker size.
WARNING! All wiring must be performed by a qualified personnel. WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable as below.
| Model | Wire Size | Cable (mm²) | Torque value (max) |
|---|---|---|---|
| 4.2KW/6.2KW | 1 x 2AWG | 25 | 2 Nm |
Please follow below steps to implement battery connection:
- Remove insulation sleeve 18 mm for positive and negative conductors.
- Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Connect all battery packs as below chart.

- Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charge is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver
WARNING: Shock Hazard Installation must be performed with care due to high battery voltage in series.
CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
3.5 AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 32A for 4.2KW and 50A for 6.2KW. CAUTION!! There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by a qualified personnel. WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.
| Model | Gauge | Cable (mm²) | Torque Value |
|---|---|---|---|
| 4.2KW | 12 AWG | 4 | 1.2 Nm |
| 6.2KW | 10 AWG | 6 | 1.2 Nm |
Please follow below steps to implement AC input/output connection:
- Before making AC input/output connection, be sure to open DC protector or disconnector first.
- Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
- Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. (L→LINE (brown or black), N→Neutral (blue))

WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
- Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws. (L→LINE (brown or black), N→Neutral (blue))
- Make sure the wires are securely connected.
CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check manufacturer of air conditioner if it's equipped with time-delay function before installation. Otherwise, this inverter/charger will trig overload fault and cut off output to protect your appliance but sometimes it still causes internal damage to the air conditioner.
3.6 PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.
| Model | Wire Size | Cable (mm²) | Torque Value (max) |
|---|---|---|---|
| 4.2KW/6.2KW | 1 x 12AWG | 4 | 1.2 Nm |
PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:
- Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
| INVERTER MODEL | 4.2KW | 6.2KW |
|---|---|---|
| Max. PV Array Open Circuit Voltage | 500Vdc | |
| PV Array MPPT Voltage Range | 60Vdc~450Vdc | |
| IMax.PV | 27A | |
PV Module Wire Connection Steps:
- Remove insulation sleeve 10 mm for positive and negative conductors.
- Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Check correct polarity of wire connection from PV modules and PV input connectors. Then, connect positive pole (+) of connection wire to positive pole (+) of PV input connector. Connect negative pole (-) of connection wire to negative pole (-) of PV input connector. Recommended tool: 4mm blade screwdriver

3.7 Final Assembly
After connecting all wirings, please put bottom cover back by screwing two screws.
3.8 Communication Connection
Wi-Fi cloud communication (optional):
Please use supplied communication cable to connect to inverter and Wi-Fi module. Download APP and installed from APP store, and Refer to "Wi-Fi Plug Quick Installation Guideline" to set up network and registering. The inverter status would be shown by mobile phone APP or webpage of computer.
GPRS cloud communication (optional):
Please use supplied communication cable to connect to inverter and GPRS module, and then applied external power to GPRS module. Download APP and installed from APP store, and Refer to "GPRS RTU Quick Installation Guideline" to set up network and registering. The inverter status would be shown by mobile phone APP or webpage of computer.
Battery communication:
The communication between the battery and the inverter can be realized through the battery communication interface, so that the inverter and the lithium battery can exchange information (Baud rate: 9600).
Lithium battery and inverter connection:
If choosing lithium battery for the inverter, only lithium batteries that have been matched with BMS communication protocol are allowed.
- Connect the battery according to the recommended battery cable specifications.
- Insert the ring terminal of the battery cable into the battery connector of the inverter flatly, and ensure that the bolts are tightened with a torque of 2-3 Nm. Make sure that the polarities of the battery and inverter are connected correctly, and that the ring terminal is tightened with the battery terminal.
- Connect one side of RJ45 cable to the BMS communication port of inverter.
- Insert the other side of RJ45 cable into RS485 communication port on lithium battery.
NOTE: If you choose a lithium battery, please make sure to connect the battery and inverter with BMS communication cable, and select the battery type as "LIB-485" mode.
Communication And Setting Of Lithium Battery
Connect the RJ45 communication cable between inverter and battery. Please confirm that the lithium battery BMS port's PIN is correspond with the inverter BMS communication port. The inverter BMS port'PIN definition as below:
| Pin number | Port definitions |
|---|---|
| 1 | RS485B |
| 2 | RS485A |
| 3 | NG |
| 4 | NG |
| 5 | NG |
| 6 | NG |
| 7 | RS485A |
| 8 | RS485B |
In order to communicate with the lithium battery BMS, you should press the "ENTER" button for a long time, and set the battery type as "LIB-485" in program 05. Then select the matching battery protocol in Program 43.
CAUTION: When the battery type is set to "LIB-485", the setting items 12, 13 and 29 are displayed in percentage.
4. Operation
4.1 Power ON/OFF
Once the unit has been properly installed and the batteries are connected well, simply press On/Off switch (located on the button of the case) to turn on the unit.
4.2 Operation and Display Panel
The operation and display panel, shown in the product overview, is on the front panel of the inverter. It includes three indicators, four function keys and a LCD display, indicating the operating status and input/output power information.
| LED Indicator | State | Messages |
|---|---|---|
| INV/AC (Green) | Solid On | Output is powered by utility in Line mode. |
| Flashing | Output is powered by battery or PV in battery mode. | |
| CHG (Green) | Solid On | Battery is fully charged. |
| Flashing | Battery is charging. | |
| FAULT (Red) | Solid On | Fault occurs in the inverter. |
| Flashing | Warning condition occurs in the inverter. |
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
4.3 LCD Display Icons
The LCD display provides various icons to indicate the system's status and information. These include:
- Input Source Information: Indicates AC input, PV input, input voltage, frequency, PV voltage, charger current, charger power, battery voltage.
- Configuration Program and Fault Information: Indicates setting programs, warning and fault codes.
- Output Information: Indicates output voltage, frequency, load percent, load in VA, load in Watt, and discharging current.
- Battery Information: Displays battery status.
- Load Information: Indicates overload status.
- Mode Operation Information: Indicates connection to mains, PV panel, load supplied by utility power, utility charger circuit working, DC/AC inverter circuit working.
- Mute Operation: Indicates unit alarm is disabled.
4.4 LCD Setting
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Use the "UP" or "DOWN" buttons to select setting programs, and "ENTER" to confirm or "ESC" to exit.
The manual provides detailed tables for each setting program (00-45), including selectable options and their descriptions. These settings cover:
- Output source priority (Utility first, Solar first, SBU priority, MKS priority)
- Maximum charging current
- AC input voltage range
- Power saving mode enable/disable
- Battery type (AGM, Flooded, User-Defined, LIB-485)
- Auto restart settings for overload and over temperature
- Output frequency and voltage
- Maximum utility charging current
- Voltage points for switching back to utility source or battery mode
- Battery equalization settings (enable/disable, time, timeout, interval)
- GRID-tie operation and current
- LED pattern light
- Dual output and functional voltage points
- Lithium battery protocol and delayed grid access
- Maximum Second Load
4.5 Operating Mode Description
The inverter operates in several modes, each with specific behavior and display indications:
- Stand bymode: Inverter is not turned on but can charge the battery without AC output. No output is supplied to loads.
- Line Mode: Unit provides output power from the mains and charges the battery.
- Grid-Tie operation: When working in Grid-Tie mode, the unit will flash every 3 seconds.
- Battery Mode: Unit provides output power from battery and solar.
4.6 RGB Light (optional)
The RGB lamp indicates the inverter's status:
- Green light: Inverter state
- Blue light: Utility state
- Red light: Failure state
4.7 Battery Equalization Description
The equalization function reverses the buildup of negative chemical effects like stratification and removes sulfate crystals, optimizing battery performance. It can be applied by setting an equalization interval (program 35) or activating it immediately (program 36).
Equalize Charging Time and Timeout:
In Equalize stage, the controller supplies power to charge the battery until it reaches the equalization voltage. Constant-voltage regulation maintains this level. If the battery doesn't reach the voltage within the equalized time, the controller extends the time. If still not reached after timeout, equalization stops and returns to float stage.
4.8 Mains and Lithium Battery Activation Function
- After 90s of mains power connection to the inverter, the machine is connected to the mains and starts to work.
- If the inverter is in lithium battery mode (item 05 is Llb or Llb-485), and the mains is connected but the battery is not, the mains activation function is automatically enabled.
5. Maintenance
5.1 Clearance and Maintenance for Anti-Dust Kit
Overview:
Every inverter is already installed with an anti-dust kit from the factory. The inverter will automatically detect this kit and activate an internal thermal sensor to adjust the internal temperature. This kit also keeps dust from your inverter and increases product reliability in harsh environments.
Maintenance Steps:
- Step 1: Please loosen the screw in counterclockwise direction on the top of the inverter.
- Step 2: Then, the dustproof case can be removed, and the air filter foam taken out.

- Step 3: Clean the air filter foam and dustproof case. After clearance, re-assemble the dust-kit back to the inverter.
NOTICE: The anti-dust kit should be cleaned from dust every one month.
6. Troubleshooting
6.1 Fault Reference Code
The inverter provides various fault codes to help diagnose issues. Refer to the LCD display for the specific code.
| Fault code | Fault event | The icon is long and bright |
|---|---|---|
| 21 | Battery Cell Over Voltage | [21] ERROR |
| 22 | Battery Cell Under Voltage | [22] ERROR |
| 23 | Battery Pack Over Voltage | [23] ERROR |
| 24 | Battery Pack Under Voltage | [24] ERROR |
| 25 | Charging Over Current | [25] ERROR |
| 26 | Discharging Over Current | [26] ERROR |
| 27 | Charging Cell Over Temperature | [27] ERROR |
| 28 | Discharging Cell Over Temperature | [28] ERROR |
| 29 | Charging Cell Under Temperature | [29] ERROR |
| 30 | Discharging Cell Under Temperature | [30] ERROR |
| 31 | Ambient Over Temperature | [31] ERROR |
| 32 | Ambient Under Temperature | [32] ERROR |
| 33 | MOS Over Temperature | [33] ERROR |
| 35 | Battery Short Circuit | [35] ERROR |
| 36 | Charge Overvoltage | [36] ERROR |
| 37 | System Failure | [37] ERROR |
| 39 | Charging MOS Fault | [39] ERROR |
| 40 | Discharge MOS Fault | [40] ERROR |
| 41 | Temperature Sensor Fault | [41] ERROR |
| 42 | Battery Cell Fault | [42] ERROR |
| 43 | Sampling Communication Failure | [43] ERROR |
| 61 | Communication Failure | [61] ERROR |
6.2 Warning Indicator
The inverter provides various warning codes and audible alarms to alert users of potential issues.
| Alarm code | Alarm event | Icon flashing |
|---|---|---|
| 21 | Battery Cell Over Voltage | (21) |
| 22 | Battery Cell Under Voltage | (22) |
| 23 | Battery Pack Over Voltage | (23) |
| 24 | Battery Pack Under Voltage | (24) |
| 25 | Charging Over Current | (25) |
| 26 | Discharging Over Current | (26) |
| 27 | Charging Cell Over Temperature | [27] |
| 28 | Discharging Cell Over Temperature | (28) |
| 29 | Charging Cell Under Temperature | (29) |
| 30 | Discharging Cell Under Temperature | (30) |
| 34 | Battery capacity is too low | (34) |
| 44 | Battery Cell Voltage Imbalance | (44) |
| 45 | Battery Cell Temperature Imbalance | (45) |
| 46 | Internal Communication Alarm | (46) |
| Warning Code | Warning Event | Audible Alarm | Icon flashing |
|---|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep three times every second | 01 |
| 03 | Battery is over-charged | Beep once every second | 03 |
| 04 | Low battery | Beep once every second | 04 |
| 07 | Overload | Beep once every 0.5 second | 07 |
| 10 | Output power derating | Beep twice every 3 seconds | 10 |
| 15 | PV energy is low. | Beep twice every 3 seconds | 15 |
| 16 | AC voltage is over limitation | Beep twice every 3 seconds | 16 |
| 49 | Battery equalization | None | E9 |
| 6P | Battery is not connected | None | 6P |
6.3 Troubleshooting Table
| Problem | LCD/LED/Buzzer | Explanation / Possible cause | What to do |
|---|---|---|---|
| Unit shuts down automatically during startup process. | LCD/LEDs and buzzer will be active for 3 seconds and then complete off. | The battery voltage is too low (<1.91V/Cell) | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | No indication. | 1. The battery voltage is far too low. (<1.4V/Cell) 2. Internal fuse tripped. | 1. Contact repair center for replacing the fuse. 2. Re-charge battery. 3. Replace battery. |
| Mains exist but the unit works in battery mode. | Input voltage is displayed as 0 on the LCD and green LED is flashing. | Input protector is tripped | Check if AC breaker is tripped and AC wiring is connected well. |
| Green LED is flashing. | Insufficient quality of AC power. (Shore or Generator) | 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS Appliance) | |
| When the unit is turned on, internal relay is switched on and off repeatedly. | Green LED is flashing. | Set "Solar First" as the priority of output source. | Change output source priority to Utility first. |
| LCD display and LEDs are flashing | Battery is disconnected. | Check if battery wires are connected well. | |
| Buzzer beeps continuously and red LED is on. | Fault code 07 | Overload error. The inverter is overload 110% and time is up. | Reduce the connected load by switching off some equipment. |
| Fault code 05 | Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
| Fault code 02 | Temperature of internal converter component is over 120°C. Internal temperature of inverter component is over 100°C. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
| Fault code 03 | Battery is over-charged. | Return to repair center. | |
| The battery voltage is too high. | Check if spec and quantity of batteries are meet requirements. | ||
| Fault code 01 | Fan fault | Replace the fan. | |
| Fault code 06/58 | Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) | 1. Reduce the connected load. 2. Return to repair center | |
| Fault code 08/09/53/57 | Internal components failed. | Return to repair center. | |
| Fault code 51 | Over current or surge. | Restart the unit, if the error happens again, please return to repair center. | |
| Fault code 52 | Bus voltage is too low. | ||
| Fault code 55 | Output voltage is unbalanced. |
7. Specifications
7.1 General Product Properties
- Brand Name: PowMr
- Model Number: POW-HVM4.2K-24V-E/POW-HVM6.2K-48V-E
- Size: 45*36*15cm
- Output Type: DUAL
- Weight: 8KG
- Output Frequency: 50Hz/60Hz
- Output Current: MPPT 120A
- Is Smart Device: Yes
- Origin: Mainland China
- Certification: CE
- Net Weight: 7.2 - 8.2 kg
7.2 Table 1 Line Mode Specifications
| INVERTER MODEL | 4.2KW | 6.2KW |
|---|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) | |
| Nominal Input Voltage | 230Vac | |
| Low Loss Voltage | 170Vac±7V (UPS); 90Vac±7V (Appliances) | |
| Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) | |
| High Loss Voltage | 280Vac±7V | |
| High Loss Return Voltage | 270Vac±7V | |
| Max AC Input Voltage | 300Vac | |
| Nominal Input Frequency | 50Hz / 60Hz (Auto detection) | |
| Low Loss Frequency | 40±1Hz | |
| Low Loss Return Frequency | 42±1Hz | |
| High Loss Frequency | 65±1Hz | |
| High Loss Return Frequency | 63±1Hz | |
| Output Short Circuit Protection | Circuit Breaker | |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) | |
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) | |
7.3 Table 2 Inverter Mode Specifications
| INVERTER MODEL | 4.2KW | 6.2KW |
|---|---|---|
| Rated Output Power | 4.2KW | 6.2KW |
| Output Voltage Waveform | Pure Sine Wave | |
| Output Voltage Regulation | 230Vac±5% | |
| Output Frequency | 50Hz | |
| Peak Efficiency | 93% | |
| Overload Protection | 3s@≥150% load; 30s@101%~150% load | |
| Surge Capacity | 2* rated power for 3 seconds | |
| Nominal DC Input Voltage | 24Vdc | 48Vdc |
| Cold Start Voltage | 23.0Vdc | 46.0Vdc |
| Low DC Warning Voltage @load < 50% | 22.0Vdc | 44.0Vdc |
| Low DC Warning Voltage @load ≥ 50% | 21.0Vdc | 42.0Vdc |
| Low DC Warning Return Voltage @load < 50% | 22.5Vdc | 45.0Vdc |
| Low DC Warning Return Voltage @load ≥ 50% | 22.0Vdc | 44.0Vdc |
| Low DC Cut-off Voltage @load < 50% | 20.5Vdc | 41.0Vdc |
| Low DC Cut-off Voltage @load ≥ 50% | 20.0Vdc | 40.0Vdc |
| High DC Recovery Voltage | 32Vdc | 62Vdc |
| High DC Cut-off Voltage | 33Vdc | 63Vdc |
| No Load Power Consumption | 25W | 50W |
| Saving Mode Power Consumption | < 10W | < 15W |
7.4 Table 3 Two Load Output Power
| INVERTER MODEL | 4.2KW | 6.2KW |
|---|---|---|
| Full Load | 4200W | 6200W |
| Maximum Main Load | 4200W | 6200W |
| Second Load Range | 840W~2940W | 1240W~4340W |
| Main Load Cut Off Voltage | 22VDC | 44VDC |
| Main Load Return Voltage | 26VDC | 52VDC |
7.5 Table 4 Charge Mode Specifications
| UTILITY CHARGING MODE | 4.2KW | 6.2KW |
|---|---|---|
| Charging Algorithm | 3-Step | |
| AC Charging Current (Max) | 100Amp (@VI/P=230Vac) | |
| Bulk Charging: Flooded Battery | 29.2 | 58.4 |
| AGM / Gel Battery Voltage | 28.2 | 56.4 |
| Floating Charging Voltage | 27Vdc | 54Vdc |
| Max Charging Current (AC charger plus solar charger) | 120Amp | |
7.6 Table 5 General Specifications
| INVERTER MODEL | 4.2KW | 6.2KW |
|---|---|---|
| Safety Certification | CE | |
| Operating Temperature Range | -10°C to 50°C | |
| Storage temperature | -15°C~60°C | |
| Humidity | 5% to 95% Relative Humidity (Non-condensing) | |
| Dimension (D*W*H), mm | 423×344×112 | |
| Net Weight, kg | 7.2 | 8.2 |
8. User Tips
- The inverter supports operation without a battery, relying solely on solar input. It also functions with a battery for energy storage.
- Grid-tie functionality allows for selling excess electricity back to the grid, and UPS (Uninterruptible Power Supply) mode can be enabled or disabled in the settings.
- While WiFi monitoring is available, some users have noted that it may only display cumulative production data, not daily production.
- Consider the inverter's noise level and its non-waterproof design. It is recommended to install the unit indoors to protect it from environmental elements and reduce noise impact.
- When connecting solar panels, ensure the total voltage and current are within the inverter's specifications. For example, a setup with 12 serial 250W 37V panels can achieve significant daily production.
9. Warranty and Support
9.1 Warranty Information
This PowMr Hybrid Inverter comes with a 1-year warranty, ensuring peace of mind for your investment.
9.2 Contact Information
For technical support, service, or any inquiries regarding your PowMr Hybrid Inverter, please use the following contact details:
- Tel/Fax: +86755-28219903
- Email: support@powmr.com
- Website: www.powmr.com
- Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China
9.3 Additional Resources
A detailed user manual in PDF format is available for download. This document provides comprehensive instructions and diagrams for installation, operation, and troubleshooting. You can access it via the following link: PowMr Hybrid Inverter User Manual (PDF)