ECGSOLAX ECO-LV 3.6K

Contents

ECGSOLAX 3.6KW Hybrid Solar Inverter User Manual

Model: ECO-LV 3.6K | Brand: ECGSOLAX

1. Introduction

1.1 Purpose and Scope

This manual provides detailed instructions for the assembly, installation, operation, and troubleshooting of the ECGSOLAX 3.6KW Hybrid Solar Inverter. It includes essential safety guidelines, installation procedures, and information on tools and wiring. Please read this manual carefully before installation and operation, and keep it for future reference.

1.2 Features

  • Pure sine wave inverter
  • Configurable input voltage range for home appliances and personal computers via LCD setting
  • Configurable battery charging current based on applications via LCD setting
  • Configurable AC/Solar Charger priority via LCD setting
  • Compatible with mains voltage or generator power
  • Auto restart while AC is recovering
  • Overload, over temperature, and short circuit protection
  • Smart battery charger design for optimized battery performance
  • Cold start function

1.3 Basic System Architecture

The ECGSOLAX Hybrid Solar Inverter is a multi-function unit combining inverter, solar charger, and battery charger capabilities to provide uninterruptible power support. It features a comprehensive LCD display for user-configurable settings.

A complete running system typically includes the inverter, a generator or utility power source, PV modules, and external battery packs. The inverter can power various home and office appliances, including motor-type appliances like refrigerators and air conditioners.

System Connection Diagram
Figure 1: System Connection Diagram
This diagram illustrates how the ECGSOLAX Hybrid Solar Inverter connects to solar panels (PV), a generator or utility power, batteries, and various home appliances. It shows the inverter receiving input from solar power, generator/utility, and a 24V lithium or lead-acid battery, then supplying single-phase 110V output to home appliances like refrigerators, lights, laptops, fans, and air conditioners. Max. VOC is 500V DC, PV Array MPPT Voltage Range is 60-500V DC, and Max. PV Array Power is 4200W. Max charging current is 120A (AC charger + solar charger).
Multi-Battery Connectivity
Figure 2: Seamless Multi-Battery Connectivity and Battery-Free Use
This image highlights the inverter's compatibility with various battery types including AGM, GEL, FLD, LI, and SLD. It also notes that for Lithium Battery BMS Communication, the battery BMS must be PylonTech.

1.4 Product Overview

The inverter's front panel features an LCD display, status indicator, charging indicator, fault indicator, and function buttons. The side panels include an anti-dust kit, and the bottom panel houses the power on/off switch, AC input, main output, second output, battery input, PV input, WIFI communication/RS-232 port, battery communication/RS-485 port, and a circuit breaker.

Product Overview Diagram
Figure 3: Product Overview Diagram with Labeled Components
This diagram shows the front and side views of the inverter, labeling key components such as the LCD display, status/charging/fault indicators, function buttons, power on/off switch, AC input/output, battery input, PV input, anti-dust kit, communication ports (WIFI/RS-232, RS-485), and circuit breaker.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION: To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce the risk of electric shock, disconnect all wiring before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION: Only qualified personnel can install this device with a battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation, follow the required specifications to select the appropriate cable size.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts, which could cause an explosion.
  9. Strictly follow the installation procedure when disconnecting AC or DC terminals. Refer to the INSTALLATION section for details.
  10. A 150A fuse is provided for over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Comply with local requirements and regulations.
  12. NEVER cause AC output and DC input short-circuited. Do NOT connect to the mains when DC input short circuits.
  13. Warning!! Only qualified service persons are able to service this device. If errors persist after following the troubleshooting table, send this inverter/charger back to a local dealer or service center for maintenance.

3. Installation

3.1 Unpacking and Inspection

Before installation, carefully inspect the unit. Ensure that nothing inside the package is damaged. The package should contain the inverter unit and a user manual.

3.2 Preparation

Before connecting any wiring, remove the bottom cover by unscrewing the two screws.

3.3 Mounting the Unit

When selecting an installation location, consider the following:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install at eye level for easy LCD display reading.
  • Allow approximately 20 cm clearance to the sides and 50 cm above and below the unit for proper air circulation and heat dissipation.
  • The ambient temperature should be between 0°C and 55°C for optimal operation.
  • The recommended installation position is vertically on a wall.
  • Ensure sufficient space for heat dissipation and wire removal.

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Install the unit by screwing two M6 screws into the wall.

3.4 Battery Connection

CAUTION: For safety and regulatory compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. Ensure over-current protection is installed. Refer to the table below for required fuse or breaker size.

WARNING! All wiring must be performed by qualified personnel. Use appropriate cable for battery connection to reduce risk of injury.

Recommended Battery Cable Size:

ModelWire SizeCable (mm²)Torque Value (max)
3.6KW/6.2KW1 x 2AWG252 Nm

Battery Connection Steps:

  1. Remove 18 mm of insulation sleeve from positive and negative conductors.
  2. (Optional) Put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Connect all battery packs as shown in the system connection diagram (Figure 1).
  4. Insert the battery wires flatly into the inverter's battery connectors. Ensure bolts are tightened with a torque of 2 Nm in a clockwise direction. Verify correct polarity at both the battery and the inverter/charger, and ensure conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.

WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.

CAUTION!! Before making the final DC connection or closing the DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) is connected to negative (-).

Battery Connection Example
Figure 4: Battery Connection Example
This image shows the inverter connected to two batteries, illustrating a typical battery setup. The wiring includes a red positive cable and a black negative cable, with a circuit breaker on the positive line.

3.5 AC Input/Output Connection

CAUTION!! Before connecting to an AC input power source, install a separate AC breaker between the inverter and the AC input power source. This ensures the inverter can be securely disconnected during maintenance and fully protected from overcurrent of AC input. Recommended AC breaker spec: 32A for 3.6KW and 50A for 6.2KW.

CAUTION!! There are two terminal blocks with "IN" and "OUT" markings. Do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by qualified personnel. Use appropriate cable for AC input connection to reduce risk of injury.

Suggested Cable Requirement for AC Wires:

ModelGaugeCable (mm²)Torque Value
3.6KW12 AWG41.2 Nm
6.2KW10 AWG61.2 Nm

AC Input/Output Connection Steps:

  1. Before making AC input/output connections, open the DC protector or disconnector.
  2. Remove 10mm of insulation sleeve for six conductors. Shorten phase L and neutral conductor N by 3 mm.
  3. Insert AC input wires according to the polarities indicated on the terminal block (L-LINE (brown or black), N-Neutral (blue)) and tighten the terminal screws.
  4. Insert AC output wires according to the polarities indicated on the terminal block (L-LINE (brown or black), N-Neutral (blue)) and tighten the terminal screws.
  5. Ensure all wires are securely connected.

WARNING: Be sure that the AC power source is disconnected before attempting to hardwire it to the unit.

CAUTION: Appliances like air conditioners require 2-3 minutes to restart. If a power shortage occurs and recovers quickly, it can damage connected appliances. Check if the air conditioner manufacturer specifies a time-delay function. Otherwise, the inverter/charger may trigger an overload fault and cut off output, potentially causing internal damage to the air conditioner.

3.6 PV Connection

CAUTION: Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.

WARNING! Use appropriate cable for PV module connection for system safety and efficient operation. Refer to the table below for recommended cable size.

Recommended Cable Size for PV Modules:

ModelWire SizeCable (mm²)Torque Value (max)
3.6KW/6.2KW1 x 12AWG41.2 Nm

PV Module Selection:

When selecting PV modules, consider the following parameters:

  1. The Open Circuit Voltage (Voc) of PV modules should not exceed the max. PV array open circuit voltage of the inverter (500Vdc).
  2. The Open Circuit Voltage (Voc) of PV modules should be higher than the minimum battery voltage.

Inverter Model PV Specifications:

INVERTER MODEL3.6KW6.2KW
Max. PV Array Open Circuit Voltage500Vdc
PV Array MPPT Voltage Range60Vdc~450Vdc
Solar Panel Specifications and Connection Diagram
Figure 5: Solar Panel Specifications and Connection Diagram
This image provides a table of solar panel specifications including Max. PV Array Power (4200W), Max. PV Array Open Circuit Voltage (500VDC), Max. PV Array MPPT Voltage Range (60-450VDC), PV Wire Size (12AWG), Battery Wire Size (18A, 2AWG), and Max. PV charge current (120A). It also shows a visual representation of solar panels connected to the inverter and battery.

PV Module Wire Connection Steps:

  1. Remove 10 mm of insulation sleeve from positive and negative conductors.
  2. (Optional) Put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Check correct polarity of wire connection from PV modules and PV input connectors. Connect positive pole (+) of connection wire to positive pole (+) of PV input connector. Connect negative pole (-) of connection wire to negative pole (-) of PV input connector. Recommended tool: 4mm blade screwdriver.

3.7 Final Assembly

After connecting all wiring, replace the bottom cover by screwing the two screws back into place.

3.8 Communication Connection

The inverter supports Wi-Fi and GPRS cloud communication options:

  • Wi-Fi Cloud Communication: Use the supplied communication cable to connect the inverter to the Wi-Fi module. Download and install the APP from the APP store. Refer to the "Wi-Fi Plug Quick Installation Guideline" to set up the network and register. The inverter status will be displayed on the mobile phone APP or computer webpage.
  • GPRS Cloud Communication: Use the supplied communication cable to connect the inverter to the GPRS module, and then apply external power to the GPRS module. Download and install the APP from the APP store. Refer to the "GPRS RTU Quick Installation Guideline" to set up the network and register. The inverter status will be displayed on the mobile phone APP or computer webpage.
  • Battery Communication: Communication between the battery and the inverter can be established through the battery communication interface, allowing the inverter and lithium battery to exchange information.

4. Operation

4.1 Power ON/OFF

Once the unit is properly installed and the batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.

4.2 Operation and Display Panel

The operation and display panel is located on the front of the inverter. It includes three indicators (LED), four function keys, and an LCD display. These components show the operating status and input/output power information.

LED Indicators:

IndicatorColorStatusMessage
INV/ACGreenSolid OnOutput is powered by utility in Line mode.
FlashingOutput is powered by battery or PV in battery mode.
CHGGreenSolid OnBattery is fully charged.
FlashingBattery is charging.
FAULTRedSolid OnFault occurs in the inverter.
FlashingWarning condition occurs in the inverter.

Function Keys:

Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

4.3 LCD Display Icons

The LCD display provides various icons to indicate input source information, configuration programs, fault information, output information, battery information, load information, mode operation information, and mute status. These icons help users quickly understand the inverter's current state and any active warnings or faults.

Input Source Information: Icons indicate AC input, PV input, and display values for input voltage, input frequency, PV voltage, charger current, charger power, and battery voltage.

Configuration Program and Fault Information: Icons display setting programs, warning codes (flashing), and fault codes (solid light).

Output Information: Icons show output voltage, output frequency, load percentage, load in VA, load in Watt, and discharging current.

Battery Information: Icons represent battery status.

Load Information: An 'OVER LOAD' icon indicates an overload condition.

Mode Operation Information: Icons show if the unit is connected to mains, PV panel, if load is supplied by utility power, if utility charger circuit is working, or if DC/AC inverter circuit is working.

Mute Operation: An icon indicates if the unit alarm is disabled.

4.4 LCD Setting

To enter setting mode, press and hold the ENTER button for 3 seconds. Use the UP or DOWN buttons to select programs, and ENTER to confirm or ESC to exit. The manual provides detailed tables for various settings including:

  • Program 00: Exit setting mode (One-button restore setting options).
  • Program 01: Output source priority (Utility first, Solar first, SBU priority).
  • Program 02: Maximum charging current (10A to 60A).
  • Program 03: AC input voltage range (Appliances, UPS).
  • Program 05: Battery type (AGM, Flooded, User-Defined, Lithium with/without WIFI).
  • Program 06: Auto restart when overload occurs (Disable/Enable).
  • Program 07: Auto restart when over temperature occurs (Disable/Enable).
  • Program 09: Output frequency (50Hz/60Hz).
  • Program 10: Output voltage (100V, 105V, 110V, 115V, 120V).
  • Program 11: Maximum utility charging current (2A to 30A).
  • Program 12: Setting voltage point back to utility source when selecting "SBU priority" or "Solar first" (21.0V to 25.5V for 3.6KW, 42V to 51V for 6.2KW).
  • Program 13: Setting voltage point back to battery mode when selecting "SBU priority" or "Solar first" (24V to 29V for 3.6KW, 48V to 54V for 6.2KW).
  • Program 16: Charger source priority (Solar first, Solar and Utility, Only Solar).
  • Program 18: Alarm control (Alarm on/off).
  • Program 19: Auto return to default display screen (Return to default/Stay at latest screen).
  • Program 20: Backlight control (Backlight on/off).
  • Program 22: Beeps while primary source is interrupted (Alarm on/off).
  • Program 23: Overload bypass (Bypass disable/enable).
  • Program 25: Record Fault code (Record enable/disable).
  • Program 26: Bulk charging voltage (C.V voltage) (28.2V for 3.6KW, 56.4V for 6.2KW).
  • Program 27: Floating charging voltage (27.0V for 3.6KW, 54.0V for 6.2KW).
  • Program 29: Low DC cut-off voltage (20.0V for 3.6KW, 40.0V for 6.2KW).
  • Program 30: Battery equalization (Enable/Disable).
  • Program 31: Battery equalization voltage (29.2V for 3.6KW, 58.4V for 6.2KW).
  • Program 33: Battery equalized time (60min to 900min).
  • Program 34: Battery equalized timeout (120min to 900min).
  • Program 35: Equalization interval (30 days to 90 days).
  • Program 36: Equalization activated immediately (Enable/Disable).
  • Program 37: GRID-tie operation (Off grid, Hybrid).
  • Program 38: GRID-tie current (10A, increment of 2A).
  • Program 39: Led pattern light (Led pattern off/on).
  • Program 41: Dual output (Disable/Use).
  • Program 42: Enter the dual output functional voltage point (22.0V for 3.6KW, 44.0V for 6.2KW).

4.5 Display Setting

The LCD display information can be switched by pressing the "UP" or "DOWN" keys. Selectable information includes input voltage, input frequency, PV voltage, charging current, charging power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, load in Watt, DC discharging current, and main CPU Version.

4.6 Operating Mode Description

The inverter supports various operating modes, including Standby mode, Line mode, and Grid-Tie Operation. The LCD display will show different information depending on the active mode and power conditions (charged state, discharged state, power less than 1kW, power greater than 1kW).

4.7 Battery Equalization Description

The equalization function reverses the buildup of negative chemical effects like stratification and helps remove sulfate crystals from battery plates. This process is crucial for maintaining battery capacity and is recommended periodically.

How to Apply Equalization Function:

  1. Enable the battery equalization function in LCD setting program 30.
  2. Set the equalization interval in program 35, or activate equalization immediately in program 36.

When to Equalize:

In float stage, when the set equalization interval is reached or equalization is actively initiated, the controller will enter the Equalize stage.

Equalize Charging Time and Timeout:

During the Equalize stage, the controller charges the battery until it reaches the equalization voltage. It then maintains this voltage until the set equalized time expires. If the battery does not reach the equalization voltage within the set time, the controller extends the equalized time. If the battery voltage is still low after the equalized timeout, the controller stops equalization and returns to the float stage.

5. Maintenance

5.1 Anti-Dust Kit Clearance and Maintenance

Every inverter comes with a factory-installed anti-dust kit. This kit helps prevent dust from entering the inverter, enhancing product reliability in harsh environments. The inverter automatically detects this kit and adjusts its internal thermal sensor to regulate temperature.

Maintenance Steps:

  1. Loosen the screw on the top of the inverter in a counterclockwise direction.
  2. Remove the dustproof case and take out the air filter foam.
  3. Clean the air filter foam and the dustproof case.
  4. After cleaning, re-assemble the dust-kit back into the inverter.

NOTICE: The anti-dust kit should be cleaned from dust every one month.

6. Troubleshooting

6.1 Fault Reference Code

The inverter displays specific fault codes on the LCD to indicate various issues:

Fault CodeFault EventIcon on
01Fan is locked when inverter is off.01 ERROR
02Over temperature02 ERROR
03Battery voltage is too high03 ERROR
04Battery voltage is too low04 ERROR
05Output short circuited or over temperature is detected by internal converter components.05 ERROR
06Output voltage is too high.06 ERROR
07Overload time out07 ERROR
08Bus voltage is too high08 ERROR
09Bus soft start failed09 ERROR
51Over current or surge51 ERROR
52Bus voltage is too low52 ERROR
53Inverter soft start failed53 ERROR
55Over DC voltage in AC output55 ERROR
57Current sensor failed57 ERROR
58Output voltage is too low58 ERROR
59PV voltage is over limitation59 ERROR

6.2 Warning Indicator

The inverter provides audible alarms and icon flashing for various warning events:

Warning CodeWarning EventAudible AlarmIcon flashing
01Fan is locked when inverter is on.Beep three times every second01
03Battery is over-chargedBeep once every second03
04Low batteryBeep once every second04
07OverloadBeep once every 0.5 second07
10Output power deratingBeep twice every 3 seconds10
15PV energy is low.Beep twice every 3 seconds15
E9Battery equalizationNoneE9
bPBattery is not connectedNonebP

6.3 Troubleshooting Table

This table provides common problems, their LCD/LED/Buzzer indications, possible causes, and recommended actions:

ProblemLCD/LED/BuzzerExplanation / Possible causeWhat to do
Unit shuts down automatically during startup process.LCD/LEDs and buzzer active for 3 seconds then off.Battery voltage is too low (<1.91V/Cell)1. Re-charge battery.
2. Replace battery.
No response after power on.No indication.1. Battery voltage is far too low (<1.4V/Cell)
2. Internal fuse tripped.
1. Contact repair center for fuse replacement.
2. Re-charge battery.
3. Replace battery.
Input voltage displayed as 0 on LCD and green LED flashing.Input protector is trippedCheck if AC breaker is tripped and AC wiring is connected well.
Mains exist but unit works in battery mode.Green LED is flashing.Insufficient quality of AC power (Shore or Generator)1. Check if AC wires are too thin and/or too long.
2. Check if generator (if applied) is working well or if input voltage range setting is correct (UPS Appliance).
Green LED is flashing.Set "Solar First" as the priority of output source.Change output source priority to Utility first.
When unit is turned on, internal relay switches on and off repeatedly.LCD display and LEDs are flashingBattery is disconnected.Check if battery wires are connected well.
Fault code 07Overload error. Inverter is overload 110% and time is up.Reduce connected load by switching off some equipment.
Fault code 05Output short circuited.Check if wiring is connected well and remove abnormal load.
Fault code 02Temperature of internal converter component is over 120°C. Internal temperature of inverter component is over 100°C.Check whether air flow of unit is blocked or ambient temperature is too high.
Buzzer beeps continuously and red LED is on.Fault code 03Battery is over-charged. The battery voltage is too high.Return to repair center. Check if specifications and quantity of batteries meet requirements.
Fault code 01Fan faultReplace the fan.
Fault code 06/58Output abnormal (Inverter voltage below 190Vac or higher than 260Vac)1. Reduce the connected load.
2. Return to repair center.
Fault code 08/09/53/57Internal components failed.Return to repair center.
Fault code 51/52/55Over current or surge. Bus voltage is too low. Output voltage is unbalanced.Restart the unit. If the error happens again, return to repair center.

7. Specifications

7.1 Table 1 Line Mode Specifications

INVERTER MODEL3.6KW6.2KW
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage100Vac
Low Loss Voltage90Vac±5V (UPS); 90Vac±5V (Appliances)
Low Loss Return Voltage95Vac±5V (UPS); 95Vac±5V (Appliances)
High Loss Voltage145Vac±5V
High Loss Return Voltage140Vac±5V
Max AC Input Voltage150Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionCircuit Breaker
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)

7.2 Table 2 Inverter Mode Specifications

INVERTER MODEL3.6KW6.2KW
Rated Output Power3.6KW6.2KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation100/105/110/115/120Vac±5%
Output Frequency50Hz / 60Hz
Peak Efficiency93%
Overload Protection3s @≥150%; 5s@101%~150% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage24Vdc48Vdc
Cold Start Voltage23.0Vdc46.0Vdc
Low DC Warning Voltage (<50% load)22.0Vdc44.0Vdc
Low DC Warning Voltage (≥50% load)21.0Vdc42.0Vdc
Low DC Warning Return Voltage (<50% load)22.5Vdc45.0Vdc
Low DC Warning Return Voltage (≥50% load)22.0Vdc44.0Vdc
Low DC Cut-off Voltage (<50% load)20.5Vdc41.0Vdc
Low DC Cut-off Voltage (≥50% load)20.0Vdc40.0Vdc
High DC Recovery Voltage32Vdc62Vdc
High DC Cut-off Voltage33Vdc63Vdc
No Load Power Consumption45W50W

7.3 Table 3 Two Load Output Power

INVERTER MODEL3.6KW6.2KW
Full Load3600W6200W
Maximum Main Load3600W6200W
Maximum Second Load (battery model)1200W2066W
Main Load Cut Off Voltage26VDC52VDC
Main Load Return Voltage27VDC54VDC

7.4 Table 4 Charge Mode Specifications

UTILITY CHARGING MODE3.6KW6.2KW
Charging Algorithm3-Step
AC Charging Current (Max)80Amp (@VI/P=100 Vac)
Bulk Charging Flooded Battery29.258.4
Voltage AGM / Gel Battery28.256.4
Floating Charging Voltage27Vdc54Vdc
MPPT SOLAR CHARGING MODE3.6KW6.2KW
Max. PV Array Power4200W6500W
Nominal PV Voltage240Vdc360Vdc
PV Array MPPT Voltage Range60Vdc~500Vdc
Max. PV Array Open Circuit Voltage500Vdc
Max Charging Current (AC charger plus solar charger)120Amp120Amp

7.5 Table 5 Grid-Tie Operation

INVERTER MODEL3.6KW6.2KW
Nominal Output Voltage100/105/110/115/120VAC
Feed-in Grid Voltage Range90~150VAC
Feed-in Grid Frequency Range49~51±1Hz/59~61±1Hz
Nominal Output Current30A51.7A
Power Factor Range>0.99
Maximum Conversion Efficiency (DC/AC)97%

7.6 Table 6 General Specifications

INVERTER MODEL3.6KW6.2KW
Safety CertificationCE
Operating Temperature Range-10°C to 50°C
Storage temperature-15°C~60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm110X334X423
Net Weight, kg910

7.7 Appendix: Approximate Back-up Time Table

The backup time depends on the quality, age, and type of battery. Specifications may vary between manufacturers.

ModelLoad (W)Backup Time @ 24Vdc 100Ah (min)Backup Time @ 24Vdc 200Ah (min)
3.6KW3004491100
600222525
900124303
120095227
150068164
180056126
210048108
24003594
27003174
32002867
36002560
6.2KW5006131288
1000268613
1500158402
2000111271
250090215
320076182
350065141
400050112
450044100
50004090
62003680

8. User Tips

  • This inverter can function effectively as an Uninterruptible Power Supply (UPS) even before solar panels are installed, providing backup power from batteries.
  • The unit supports both UPS mode and Grid-Tie mode, offering flexibility in how it integrates with your power system.
  • For users in the US requiring 220VAC split-phase output, consider purchasing the larger units as this model (3.6KW) typically provides 110V/120V single-phase output.
  • The inverter features dual outputs, which can be useful for managing different load requirements.

9. Warranty and Support

For detailed warranty information and a complete set of instructions, please refer to the full user manual available as a PDF document: ECGSOLAX Hybrid Inverter User Manual (PDF).

If errors persist after following the troubleshooting steps in this manual, or for any service and repair needs, please contact your local dealer or an authorized service center. Only qualified service personnel should attempt repairs on this device.