1. Product Overview
The GEYA GYL9 series Residual Current Circuit Breaker (RCCB) is an electrical safety device designed to protect against electric shock and fire hazards caused by earth leakage currents. It quickly disconnects the circuit when it detects an imbalance in current between the live and neutral conductors, indicating a leakage to earth.
This manual covers the installation, operation, maintenance, and troubleshooting for the 2-pole GYL9 RCCBs, available in Type AC and Type A variants, with various rated residual operating currents.

Key Features:
- Type AC: Detects sinusoidal alternating residual currents.
- Type A: Detects sinusoidal alternating and pulsating direct residual currents.
- High breaking capacity.
- Fast tripping time for enhanced safety.
- DIN rail mounting for easy installation.
- Equipped with a test button for regular functional checks.
2. Safety Information
WARNING: Installation and maintenance should only be performed by qualified electricians. Disconnect all power before working on electrical circuits. Failure to follow these instructions may result in serious injury or death.
- Always ensure the main power supply is switched off before installation or maintenance.
- Use appropriate personal protective equipment (PPE).
- Verify correct wiring connections according to the diagram.
- Do not operate the device if it appears damaged.
3. Setup and Installation
The GYL9 RCCB is designed for mounting on a 35mm DIN rail within an electrical distribution board or enclosure.

Installation Steps:
- Power Disconnection: Ensure the main power supply to the electrical panel is completely disconnected and locked out.
- Mounting: Clip the RCCB onto the 35mm DIN rail. Ensure it is securely seated.
- Wiring: Connect the incoming and outgoing wires according to the wiring diagram printed on the device.

Wiring Diagram Details (Refer to Figure 3):
- Top Terminals:
- N: Incoming Neutral
- 1: Incoming Live/Phase
- Bottom Terminals:
- N: Outgoing Neutral
- 2: Outgoing Live/Phase
- Ensure all connections are tight and secure to prevent overheating and poor contact.
4. Operating Instructions
Once installed and wired correctly, the GYL9 RCCB operates automatically to protect the circuit. It also features a manual test function.
- Power On: After installation, restore power to the main circuit.
- Resetting: If the RCCB has tripped (lever in the down position), move the lever fully down and then up to reset it. If it immediately trips again, there is still a fault in the circuit.
- Test Function: Press the 'Test Monthly' button (marked 'T' or 'Test'). The RCCB should trip immediately. This confirms the internal mechanism is functioning correctly.
- Reset After Test: After a successful test, reset the RCCB by moving the lever down and then up.
5. Maintenance
Regular maintenance ensures the continued reliable operation and safety performance of your GYL9 RCCB.
- Monthly Test: Press the 'Test Monthly' button at least once a month to verify the tripping mechanism is functional.
- Visual Inspection: Periodically inspect the RCCB for any signs of physical damage, discoloration, or loose connections.
- Cleaning: Keep the device clean and free from dust. Use a dry, soft cloth for cleaning. Do not use abrasive cleaners or solvents.
- Professional Check: It is recommended to have a qualified electrician inspect your electrical system, including RCCBs, periodically (e.g., every 1-3 years).
6. Troubleshooting
If your GYL9 RCCB is not functioning as expected, refer to the following troubleshooting guide:
| Problem | Possible Cause | Solution |
|---|---|---|
| RCCB trips frequently | Earth leakage fault in the circuit; faulty appliance; damp conditions; overloaded circuit. | Unplug appliances one by one to identify the faulty one. Check for damaged wiring. Consult an electrician if the cause is not apparent. |
| RCCB does not reset | Persistent earth leakage fault; internal damage to RCCB. | Ensure all appliances are unplugged and try resetting. If it still doesn't reset, the RCCB may be faulty and needs replacement by a qualified electrician. |
| Test button does not trip RCCB | RCCB is faulty; no power to the RCCB. | Check if power is supplied to the RCCB. If power is present and the test button still fails, the RCCB is faulty and must be replaced. |
| RCCB feels hot | Loose connections; overloaded circuit; internal fault. | Immediately disconnect power. Check wiring for tightness. Reduce load. If problem persists, replace the RCCB. Consult an electrician. |
7. Specifications
| Parameter | Value |
|---|---|
| Model Series | GYL9 |
| Type | RCCB (Residual Current Circuit Breaker), Earth Leakage, RCD |
| Poles | 2P |
| Rated Current (In) | 40A |
| Rated Residual Operating Current (IΔn) | 30mA (0.03A), 100mA (0.1A), 300mA (0.3A) |
| Rated Voltage (Ue) | 230V~ |
| Frequency | 50/60Hz |
| Rated Making & Breaking Capacity (Im=IΔm) | 500A |
| Rated Short-Circuit Capacity (Inc=IΔc) | 6000A (6kA) |
| Tripping Time | ≤0.1s |
| Mounting | 35mm DIN Rail |
| Certification | CE |
| Standard | IEC/EN 61008-1 |
| Dimensions (L x W x H) | Approx. 19cm x 12cm x 6cm (Package) |
| Weight | Approx. 0.229 kg (Package) |

8. User Tips
- Select the Correct Type: Ensure you choose the appropriate RCCB type (AC or A) for your specific application to ensure optimal protection. Type A offers broader protection by detecting pulsating DC faults in addition to AC faults.
- Regular Testing is Crucial: Make it a habit to press the test button monthly. This simple action verifies the device's functionality and ensures your safety.
- Professional Installation: While the device is robust, proper installation by a qualified electrician is paramount for safety and compliance.
- Monitor for Frequent Tripping: If your RCCB trips often without an obvious cause, it might indicate an intermittent fault in your electrical system or appliances. Investigate promptly.
9. Frequently Asked Questions (FAQ)
- Q: What is the difference between Type AC and Type A RCCBs?
- A: Type AC RCCBs are designed to detect sinusoidal alternating residual currents. Type A RCCBs detect both sinusoidal alternating residual currents and pulsating direct residual currents, offering broader protection, especially in circuits with electronic devices that might produce pulsating DC leakage currents.
- Q: How often should I test my GYL9 RCCB?
- A: It is recommended to press the 'Test Monthly' button at least once a month to ensure the tripping mechanism is working correctly.
- Q: What should I do if my RCCB trips frequently?
- A: Frequent tripping usually indicates an earth leakage fault. Try unplugging appliances one by one to identify the faulty device. If the issue persists, or you cannot identify the cause, consult a qualified electrician.
- Q: Can this 2-pole RCCB be used in a 3-phase system?
- A: A 2-pole RCCB is typically used for single-phase circuits (one live, one neutral). For 3-phase systems, a 4-pole RCCB is generally required to protect all three phases and the neutral conductor.
10. Warranty and Support
For warranty information, technical support, or service inquiries, please contact your original point of purchase or the manufacturer directly. Ensure you have your product model number and purchase details available.
This product conforms to the EU Declaration of Conformity (DoC) issued by ZHEJIANG GEYA ELECTRICAL CO., LTD., adhering to the 2014/35/EU Low Voltage Directive and standards such as EN 61008-1:2012+A11:2015.
A copy of the EU Declaration of Conformity can be found at this link.