1. About This Manual
This manual describes the assembly, installation, operation, and troubleshooting of the PowMr 4KW 120V Off-Grid Solar Inverter Charger. Please read this manual carefully before installation and operation, and keep it for future reference.
1.1. Purpose
This manual provides detailed instructions for the proper use and maintenance of your inverter charger.
1.2. Scope
This manual covers safety guidelines, installation procedures, and information regarding tools and wiring for the inverter charger.
2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION: To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION: Only qualified personnel can install this device with a battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow the required specifications to select appropriate cable sizes. It is very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Refer to the INSTALLATION section of this manual for details.
- GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to a local dealer or service center for maintenance.
3. Introduction
The PowMr 4KW 120V Off-Grid Solar Inverter Charger is a multi-function inverter/charger, combining the functions of an inverter, MPPT solar charger, and battery charger to offer uninterruptible power support in a portable size. Its comprehensive large LCD display offers user-configurable and easy-accessible touch button operation for settings such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.
3.1. Features
- Off-grid solar inverter
- No battery function available
- Under Battery Mode, AC voltage can be adjusted to 100VAC, 110VAC, and 120VAC.
- Utility power, battery, and PV power complement each other
- Pure sine wave solar inverter
- Unique glass top cover design with 6.25-inch LCD display and touchable buttons
- Built-in 150A MPPT (Max PV 7200W) solar charger
- High PV input range from 55V-450Vdc
- Smart battery charger design for optimized battery performance
- Configurable AC/Battery input priority via LCD setting
- Auto restart while PV is recovering
- Over-load, over temperature, and output short circuit protection
- Cold restart function
- Built-in lithium battery automatic activation
- Communication with RS232/RS485
- WiFi monitoring function (optional)
- Anti-dust kit for harsh environments (optional)
- Restore default settings with one click
3.2. Basic System Architecture
The following illustration shows the basic application for this inverter/charger. It includes connections to a generator or utility, and optional PV modules. This inverter can power various home or office appliances, including motor-type appliances like tube lights, fans, refrigerators, and air conditioners.

4. Installation
4.1. Unpacking and Inspection
Before installation, please inspect the unit. Ensure that nothing inside the package is damaged. The package should contain the unit (x1) and the user manual (x1).
4.2. Preparation
Before connecting all wirings, remove the bottom cover by unscrewing two screws.
4.3. Mounting the Unit
Consider the following points when selecting where to install the unit:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level for easy LCD display readability.
- The ambient temperature should be between 0°C and 55°C for optimal operation.
- The recommended installation position is vertically on the wall.
- Ensure sufficient heat dissipation and space for wiring by maintaining clearances as shown in the diagram.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Install the unit by screwing two screws after mounting.
4.4. Battery Connection
CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to the typical amperage in the table below for required fuse or breaker size.
WARNING! All wiring must be performed by qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable and terminal size as below.

| Model | Typical Amperage | Battery Capacity | Wire Size | Cable mm² | Ring Terminal Dimensions (D mm) | Ring Terminal Dimensions (L mm) | Ring Terminal Dimensions (M mm) | Torque Value |
|---|---|---|---|---|---|---|---|---|
| 3.0KW 24V | 110A | 100AH/200AH | 1*4AWG | 22 | 8 | 44 | 18.2 | 2~3 Nm |
| 4.0KW 24V | 150A | 200AH | 1*2AWG | 35 | 8 | 44 | 18.2 | 2~3 Nm |
Follow these steps to connect the battery:
- Assemble the battery ring terminal based on the recommended battery cable and terminal size.
- Connect all battery packs as required by the unit.
- NOTE: Please only use sealed lead-acid battery or sealed GEL/AGM lead-acid battery or lithium battery.
- Insert the ring terminal of the battery cable flatly into the battery connector of the inverter and ensure the bolts are tightened with a torque of 2-3 Nm. Ensure polarity at both the battery and the inverter/charger is correctly connected, and ring terminals are tightly screwed to the battery terminals.

WARNING: Shock Hazard! Installation must be performed with care due to high battery voltage in series.
CAUTION!! Do not place anything between the flat part of the inverter terminal and the ring terminal. Otherwise, overheating may occur.
CAUTION!! Do not apply anti-oxidant substance on the terminals before terminals are connected tightly.
CAUTION!! Before making the final DC connection or closing the DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
4.5. AC Input/Output Connection
CAUTION!! Before connecting to the AC input power source, please install a separate AC breaker between the inverter and the AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from overcurrent of AC input. The recommended spec of AC breaker is 32A for 3.0KW and 40A for 4.0KW.
CAUTION!! There are two terminal blocks with "INPUT" and "OUTPUT" markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.
| Model | Gauge | Torque Value |
|---|---|---|
| 3.0KW | 10 AWG | 1.2~1.6 Nm |
| 4.0KW | 8 AWG | 1.4~1.6 Nm |
Follow these steps to implement AC input/output connection:
- Before making AC input/output connection, be sure to open the DC protector or disconnector first.
- Remove insulation sleeve 10mm for six conductors. Shorten phase L and neutral conductor N by 3 mm.
- Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws.

WARNING: Be sure that the AC power source is disconnected before attempting to hardwire it to the unit.
- Then, insert AC output wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor (Ground, green) first.
- Make sure the wires are securely connected.
CAUTION: Important! Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are worked in parallel operation.
CAUTION: Appliances such as air conditioners require at least 2-3 minutes to restart to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers quickly, it can damage connected appliances. Check if your air conditioner has a time-delay function. Otherwise, the inverter/charger may trigger an overload fault to protect the appliance, but internal damage may still occur.
4.6. PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between the inverter and PV modules.
WARNING! All wiring must be performed by qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.
| Model | Wire Size | Cable (mm²) | Torque Value (max) |
|---|---|---|---|
| 3.0KW/4.0KW | 1 x 12AWG | 4 | 1.2 Nm |
PV Module Selection: When selecting proper PV modules, consider these parameters:
- Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than the min. PV Array MPPT Voltage range.
| INVERTER MODEL | 3.0KW | 4.0KW |
|---|---|---|
| Max. PV Array Open Circuit Voltage | 350Vdc | |
| PV Array MPPT Voltage Range | 55Vdc~350Vdc | |
Follow these steps to implement PV module connection:
- Remove insulation sleeve 10 mm for positive and negative conductors.
- Check correct polarity of connection cable from PV modules and PV input connectors. Then, connect the positive pole (+) of the connection cable to the positive pole (+) of the PV input connector. Connect the negative pole (-) of the connection cable to the negative pole (-) of the PV input connector.

- Make sure the wires are securely connected.
4.7. Final Assembly
After connecting all wirings, please put the bottom cover back by screwing the two screws.

5. Operation
5.1. Power ON/OFF
Once the unit has been properly installed and the batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.

5.2. Operation and Display Panel
The operation and display panel, located on the front of the inverter, includes three indicators, four function keys, and an LCD display. These components show the operating status and input/output power information.

| LED Indicator | Color | Status | Messages |
|---|---|---|---|
| AC/INV | Green | Solid On | Output is powered by utility in Line mode. |
| Flashing | Output is powered by battery or PV in battery mode. | ||
| CHG | Green | Solid On | Battery is fully charged. |
| Flashing | Battery is charging. | ||
| FAULT | Red | Solid On | Fault occurs in the inverter. |
| Flashing | Warning condition occurs in the inverter. |
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
5.3. LCD Display Icons
The LCD displays various icons to provide information about the inverter's status, input sources, configuration, faults, output, and battery.
| Icon | Function Description |
|---|---|
| AC | Indicates the AC input. |
| PV | Indicates the PV input. |
| INPUT/BATTERY (with values) | Indicates input voltage, input frequency, PV voltage, battery voltage, and charger current. |
| Gear icon | Indicates the setting programs. |
| Warning/Fault icon | Indicates the warning and fault codes. |
| Warning (flashing) | Flashing with warning code. |
| Fault (solid) | Solid lighting with fault code. |
| OUTPUT/LOAD (with values) | Indicates output voltage, output frequency, load percent, load in VA, load in Watt, and discharging current. |
| Battery icon (flashing bar) | Left side flashing bar and battery icon indicates battery level by 0-20%, 20-40%, 40-60%, and 80-100% in battery mode and charging status in line mode. |
| OVER LOAD | Indicates overload. Right side flashing bar and load icon indicates the load level by 0-24%, 25-50%, 50-75%, and 75-100%. |
| Mains connection icon | Indicates unit connects to the mains. |
| PV panel icon | Indicates unit connects to the PV panel. |
| BYPASS | Indicates load is supplied by utility power. |
| Utility charger icon | Indicates the utility charger circuit is working. |
| DC/AC inverter icon | Indicates the DC/AC inverter circuit is working. |
| Mute icon | Indicates unit alarm is disabled. |
5.4. LCD Setting
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Use the "UP" or "DOWN" buttons to select setting programs. Then, press "ENTER" to confirm the selection or "ESC" to exit.
| Program | Description | Selectable Option | Details |
|---|---|---|---|
| 00 | Exit setting mode | 00 ESC | Exits the setting menu. |
| 01 | Output source priority | 01 S06 (Solar first) | Solar energy provides power to loads as first priority. If solar energy is insufficient, utility power supplies loads. |
| 01 S60 (SBU priority) | Solar energy provides power to loads as first priority. If solar energy is insufficient, battery energy supplies loads. Utility power supplies loads only when battery voltage drops below warning or setting point (program 13). | ||
| 02 | Maximum charging current | 02 10A to 02 140A | Configures total charging current for solar and utility chargers. (Max. charging current = utility charging current + solar charging current) |
| 03 | AC input voltage range | 03 APL (Appliances) | Acceptable AC input voltage range: 90-140 VAC. |
| 03 UPS (UPS) | Acceptable AC input voltage range: 90-140 VAC. | ||
| 04 | Power saving mode enable/disable | 04 SdS (Disable) | Inverter output is not affected by load level. |
| 04 SEn (Enable) | Inverter output turns off when connected load is very low or not detected. | ||
| 05 | Battery type | 05 AGn (AGM) | Flooded battery type. |
| 05 FLd (Flooded) | Flooded battery type. | ||
| 05 LIb (Lithium) | Floating charge cancelled. Battery charge voltage and low DC cut-off voltage can be set in programs 26 and 29. | ||
| 05 USE (User-Defined) | Battery charge voltage and low DC cut-off voltage can be set in programs 26, 27, and 29. | ||
| LIb 05 485 (Lithium with communication) | If "485" is selected, programs 12, 13, 29 are converted to display SOC. | ||
| 06 | Auto restart when overload occurs | 06 LFd (Restart disable) | Disables auto restart. |
| 06 LYE (Restart enable) | Enables auto restart. | ||
| 07 | Auto restart when over temperature occurs | 07 LFd (Restart disable) | Disables auto restart. |
| 07 EFE (Restart enable) | Enables auto restart. | ||
| 08 | Output voltage | 08 120V (default) | Sets output voltage to 120V. (Range: 100V, 110V, 120V) |
| 09 | Output frequency | 09 50Hz | Sets output frequency to 50Hz. |
| 09 60Hz (default) | Sets output frequency to 60Hz. | ||
| 11 | Maximum utility charging current | 11 10A to 11 140A | Sets the maximum charging current from utility. |
| 12 | Setting voltage point back to utility source when selecting "SBU priority" | 12 22.0V to 12 25.5V (24V models) | Sets the battery voltage threshold for switching back to utility. |
| 13 | Setting voltage point back to battery mode when selecting "SBU priority" | 13 24.0V to 13 29.0V (24V models) | Sets the battery voltage threshold for switching back to battery mode. |
| 16 | Charger source priority | 16 CSO (Solar first) | Solar energy charges battery first. Utility charges only if solar is unavailable. |
| 16 SNU (Solar and Utility) | Solar energy and utility charge battery at the same time. | ||
| 16 OSO (Only Solar) | Only solar energy charges battery, regardless of utility availability. | ||
| 18 | Alarm control | 18 bON (Alarm on) | Enables audible alarms. |
| 18 bOF (Alarm off) | Disables audible alarms. | ||
| 19 | Auto return to default display screen | 19 ESP (Default display) | Automatically returns to default display after 1 minute of inactivity. |
| 19 HEP (Stay at latest) | Stays on the last viewed screen. | ||
| 20 | Backlight control | 20 LON (Backlight on) | Keeps backlight on. |
| 20 LOF (Backlight off) | Turns backlight off. | ||
| 22 | Beeps while primary source is interrupted | 22 AON (Alarm on) | Enables beeping when primary source is interrupted. |
| 22 AOF (Alarm off) | Disables beeping when primary source is interrupted. | ||
| 25 | Record Fault code | 25 FEn (Record enable) | Enables fault code recording. |
| 25 FdS (Record disable) | Disables fault code recording. | ||
| 26 | Bulk charging voltage (C.V voltage) | 26 28.2V (24V default) | Sets the bulk charging voltage. Range: 24.0V-29.2V (24V model), 48.0V-58.4V (48V model). Increment: 0.1V. |
| 27 | Floating charging voltage | 27 27.0V (24V default) | Sets the floating charging voltage. Range: 24.0V-29.2V (24V model), 48.0V-58.4V (48V model). Increment: 0.1V. |
| 29 | Low DC cut-off voltage | 29 21.0V (24V default) | Sets the low DC cut-off voltage. Range: 20.0V-24.0V (24V model), 40.0V-48.0V (48V model). Increment: 0.1V. |
| 30 | Restore default settings | FES 30 ON | Restores all settings to factory defaults. |
| 33 | Battery equalization | E9 33 ON | Enables battery equalization. (Only for FLD, USE battery types) |
| 34 | Battery equalization voltage | 34 29.2V (24V default) | Sets the battery equalization voltage. Range: 25.0V-29.5V (24V model), 50V-59V (48V model). Increment: 0.1V. |
| 35 | Battery equalized time | 35 60 (60 min default) | Sets the duration of battery equalization. Range: 5-900 min. Increment: 5 min. |
| 36 | Battery equalized timeout | 36 120 (120 min default) | Sets the timeout for battery equalization. Range: 5-900 min. Increment: 5 min. |
| 37 | Equalization interval | 37 30d (30 days default) | Sets the interval between battery equalizations. Range: 0-90 days. Increment: 1 day. |
| 39 | Equalization activated immediately | 39 on (Enable) | Activates battery equalization immediately. |
5.5. Lithium Battery Connection
If the inverter is matched with lithium batteries, only lithium batteries that have been matched with the BMS communication protocol are allowed to be used.
Follow these steps to implement lithium battery connection:
- Assemble battery ring terminal based on recommended battery cable and terminal specifications.
- Insert the ring terminal of battery cable flatly into battery connector of inverter and make sure the bolts are tightened with torque of 2-3Nm. Make sure polarity at both the battery and the inverter/charge is correctly connected and ring terminals are tightly screwed to the battery terminals.
- Connect the RJ45 connector to the COMM port on the inverter.
- Connect the other end of the RJ45 plug to the battery communication port (RS485). Ensure that the battery signal cable RS485-A is connected to the RS485-A of the COMM port, and the battery signal cable RS485-B is connected to the RS485-B of the COMM port.
Note: If choosing a lithium battery, make sure to connect the BMS communication cable between the battery and the inverter. You need to choose battery type as "Lib-485" mode.
5.5.1. Lithium Battery Communication and Setting
To communicate with the battery BMS, you should set the battery type to "Lib-485" in Program 5.
5.5.2. Connect the end of RJ45 of battery to BMS communication port of inverter
Ensure that the BMS port of the lithium battery corresponds to the pin of the BMS communication port of the inverter. The pin of the inverter BMS interface is defined as shown in the following figure:

| Pin number | Definition |
|---|---|
| 1 | RX |
| 2 | TX |
| 3 | VCC |
| 4 | VCC |
| 5 | RS485-A |
| 6 | RS485-B |
| 7 | GND |
| 8 | GND |
Note: When communication fails, the LCD will display error code 61, and the inverter will cut off output. If the communication protocol does not match, you can select "LIB" mode.
5.5.3. Lithium Battery Information Display
After pressing and holding the "ESC" button for 3 seconds, enter the lithium battery page. The initial display interface shows the total battery voltage and remaining battery capacity.
| LCD Data on the Left | LCD Data on the Right | Instruction |
|---|---|---|
| Total battery voltage | Remaining battery capacity | |
| Battery charging current | Battery discharge current | |
| Battery capacity | Battery charge/discharge times | Warning in the middle |
| BMS board temperature | Mosfet temperature of BMS board | |
| Maximum voltage of a single battery cell | Minimum voltage of a single battery cell | |
| Maximum temperature of a single battery cell | Minimum temperature of a single battery cell |
5.6. Display Setting
The LCD display information will be switched by pressing the "UP" or "DOWN" key. The selectable information includes input voltage, input frequency, PV voltage, MPPT charging current, MPPT charging power, battery voltage, output voltage, output frequency, load percentage, load in VA, load in Watt, DC discharging current, and main CPU Version.
5.7. Operating Mode Description
The inverter operates in various modes, providing different power supply behaviors. The LCD display will show the current operating mode.
| Operation Mode | Description | LCD Display |
|---|---|---|
| Standby mode / Power saving mode | No output is supplied by the unit, but it can charge batteries. | Charging by utility and PV energy, Charging by utility, Charging by PV energy, No charging. |
| Fault mode | Errors due to internal circuit or external reasons (e.g., over temperature, output short circuit). Red fault indicator is solid, buzzer alarm sounds. Inverter disconnects all inputs and outputs. | Over-temperature, Output low voltage, Output overcurrent, Battery low. |
| Line Mode | The unit provides output power from the mains and charges the battery. | Charging by utility and PV energy, Charging by utility, Power from utility. |
| Battery Mode | The unit provides output power from battery and PV power. | Power from battery and PV energy, PV energy supplies power and charges battery, Power from battery only, Power from PV energy only. |
5.8. Battery Equalization Description
The equalization function is added to the charge controller to reverse the buildup of negative chemical effects like stratification and to remove sulfate crystals from the battery plates. This process helps maintain the overall capacity of the battery.
5.8.1. How to Apply Equalization Function
You must enable the battery equalization function in monitoring LCD setting program 33 first. Then, you may apply this function by either:
- Setting the equalization interval in program 37.
- Activating equalization immediately in program 39.
5.8.2. When to Equalize
In the float stage, when the setting equalization interval (battery equalization cycle) is reached, or equalization is activated immediately, the controller will enter the Equalize stage.

5.8.3. Equalize Charging Time and Timeout
In the Equalize stage, the controller will supply power to charge the battery as much as possible until the battery voltage reaches the battery equalization voltage. Then, constant-voltage regulation is applied to maintain the battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until the setting battery equalized time is reached.

However, in the Equalize stage, if the battery equalized time expires and the battery voltage doesn't rise to the battery equalization voltage point, the charge controller will extend the battery equalized time until the battery voltage achieves the battery equalization voltage. If the battery voltage is still lower than the battery equalization voltage when the battery equalized timeout setting is over, the charge controller will stop equalization and return to the float stage.
6. Troubleshooting
6.1. Fault Reference Code
The following table lists fault codes and their corresponding events.
| Fault Code | Fault Event | Icon on |
|---|---|---|
| 01 | Fan is locked when inverter is off. | |
| 02 | Over temperature | |
| 03 | Battery voltage is too high | |
| 04 | Battery voltage is too low | |
| 05 | Output short circuited or over temperature is detected by internal converter components. | |
| 06 | Output voltage is too high. | |
| 07 | Overload time out | |
| 08 | Bus voltage is too high | |
| 09 | Bus soft start failed | |
| 11 | Main relay failed | |
| 51 | Over current or surge | |
| 52 | Bus voltage is too low | |
| 53 | Inverter soft start failed | |
| 55 | Over DC voltage in AC output | |
| 56 | Battery connection is open | |
| 57 | Current sensor failed | |
| 58 | Output voltage is too low |
6.2. Warning Indicator
The following table lists warning codes and their corresponding events and audible alarms.
| Warning Code | Warning Event | Audible Alarm | Icon Flashing |
|---|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep twice every second | |
| 03 | Battery is over-charged | Beep twice every second | |
| 04 | Low battery | Beep twice every second | |
| 07 | Overload | Beep twice every second | |
| 10 | Output power derating | Beep twice every second | |
| 12 | Solar charger stops due to low battery. | ||
| 13 | Solar charger stops due to high PV voltage. | ||
| 14 | Solar charger stops due to overload. | ||
| 15 | PV is weak | ||
| 61 | When the battery communication is abnormal, stop charging and discharging. |
6.3. Troubleshooting Table
This table provides solutions for common issues encountered with the inverter charger.
| Problem | LCD/LED/Buzzer | Explanation / Possible Cause | What to Do |
|---|---|---|---|
| Unit shuts down automatically during startup process. | LCD/LEDs and buzzer active for 3 seconds, then complete off. | The battery voltage is too low (<1.91V/Cell) | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | No indication. | 1. Battery voltage is far too low (<1.4V/Cell) 2. Battery polarity is connected reversed. | 1. Check if batteries and wiring are connected well. 2. Re-charge battery. 3. Replace battery. |
| Input voltage displayed as 0 on LCD and green LED is flashing. | Input protector is tripped | Check if AC breaker is tripped and AC wiring is connected well. | |
| Mains exist but the unit works in battery mode. | Green LED is flashing. | Insufficient quality of AC power (Shore or Generator) | 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct (UPS Appliance). |
| Green LED is flashing. | Set "Solar First" as the priority of output source. | Change output source priority to Utility first. | |
| When the unit is turned on, internal relay is switched on and off repeatedly. | LCD display and LEDs are flashing | Battery is disconnected. | Check if battery wires are connected well. |
| Fault code 07 | Overload error. The inverter is overload 110% and time is up. | Reduce the connected load by switching off some equipment. | |
| Fault code 05 | Output short circuited. Temperature of internal converter component is over 120°C. | Check if wiring is connected well and remove abnormal load. Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
| Fault code 02 | Internal temperature of inverter component is over 100°C. | Return to repair center. | |
| Buzzer beeps continuously and red LED is on. | Battery is over-charged. | Check if spec and quantity of batteries are meet requirements. | |
| Fault code 01 | Fan fault | Replace the fan. | |
| Fault code 06/58 | Output abnormal (Inverter voltage below 190Vac or higher than 260Vac) | 1. Reduce the connected load. 2. Return to repair center. | |
| Fault code 08/09/53/57 | Internal components failed. | Return to repair center. | |
| Fault code 51 | Over current or surge. | Restart the unit, if the error happens again, please return to repair center. | |
| Fault code 52 | Bus voltage is too low. | ||
| Fault code 55 | Output voltage is unbalanced. | ||
| Fault code 56 | Battery is not connected well or fuse is burnt. | If the battery is connected well, please return to repair center. |
7. Specifications
Detailed technical specifications for the PowMr 4KW 120V Off-Grid Solar Inverter Charger are provided in the tables below.
| INVERTER MODEL | 3.0KW/24V | 4.0KW/24V |
|---|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) | |
| Nominal Input Voltage | 120Vac | |
| Low Loss Voltage | 95Vac±5V(UPS); 65Vac±7V(Appliances) | |
| Low Loss Return Voltage | 100Vac±5V(UPS); 70Vac±5V(Appliances) | |
| High Loss Voltage | 140Vac±5V | |
| High Loss Return Voltage | 135Vac±5V | |
| Max AC Input Voltage | 150Vac | |
| Nominal Input Frequency | 50Hz / 60Hz (It can be set in program 09) | |
| Low Loss Frequency | 45±1Hz/55±1Hz | |
| Low Loss Return Frequency | 47±1Hz/57±1Hz | |
| High Loss Frequency | 55±1Hz/65±1Hz | |
| High Loss Return Frequency | 53±1Hz/63±1Hz | |
| Output Short Circuit Protection | Line mode: Circuit Breaker Battery mode: Electronic Circuits | |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) | |
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) | |
| INVERTER MODEL | 3.0KW/24V | 4.0KW/24V |
|---|---|---|
| Rated Output Power | 3.0KW | 4.0KW |
| Output Voltage Waveform | Pure Sine Wave | |
| Output Voltage Regulation | 120Vac±5% | |
| Output Frequency | 60Hz or 50Hz | |
| Peak Efficiency | 94% | |
| Overload Protection | 5s@≥150% load; 10s@110%~150% load | |
| Surge Capacity | 2* rated power for 5 seconds | |
| Nominal DC Input Voltage | 24Vdc | |
| Cold Start Voltage | 23.0Vdc | |
| Low DC Warning Voltage | 22.0Vdc | |
| Low DC Warning Return Voltage | 23.0Vdc | |
| Low DC Cut-off Voltage | 21.0Vdc | |
| High DC Recovery Voltage | 29Vdc | |
| High DC Cut-off Voltage | 31Vdc | |
| No Load Power Consumption | <35W | |
| INVERTER MODEL | 3.0KW/24V | 4.0KW/24V | |
|---|---|---|---|
| Charging Current (UPS) @ Nominal Input Voltage | 80A | 110A | |
| Bulk Charging Voltage | Flooded Battery | 29.2Vdc | |
| AGM / Gel Battery | 28.2Vdc | ||
| Floating Charging Voltage | 27Vdc | ||
| Charging Algorithm | 3-Step | ||
| Solar Charging Mode | |||
| Rated Power | 5600W | ||
| PV Charge Current | 100A | 140A | |
| Efficiency | 98.0% max. | ||
| Max. PV Array Open Circuit Voltage | 350Vdc | ||
| PV Array MPPT Voltage Range | 55-350Vdc | ||
| Standby Power Consumption | 2W | ||
| Battery Voltage Accuracy | +/-0.3% | ||
| PV Voltage Accuracy | +/-2V | ||
| Charging Algorithm | 3-Step | ||
| INVERTER MODEL | 3.0KW/24V | 4.0KW/24V |
|---|---|---|
| Safety Certification | CE | |
| Operating Temperature Range | 0°C to 55°C | |
| Storage temperature | -15°C~60°C | |
| Dimension (D*W*H), mm | 400*250*89mm | |
| Net Weight, kg | 7.5kg | 8.5kg |
7.1. Appendix: Approximate Back-up Time Table
This table provides approximate back-up times for different loads and battery capacities.
| Model | Load (W) | Backup Time @ 24Vdc 100Ah (min) | Backup Time @ 24Vdc 200Ah (min) |
|---|---|---|---|
| 4.0KW | 300 | 449 | 1100 |
| 600 | 222 | 525 | |
| 900 | 124 | 303 | |
| 1200 | 95 | 227 | |
| 1500 | 68 | 164 | |
| 1800 | 56 | 126 | |
| 2100 | 48 | 108 | |
| 2400 | 35 | 94 | |
| 2700 | 31 | 74 | |
| 3200 | 28 | 67 |
Note: Backup time depends on the quality of the battery, age of battery, and type of battery. Specifications of batteries may vary depending on different manufacturers.
* Product technical specifications are subject to change without notice.
8. User Tips
- Easy Wi-Fi Setup: Many users find the Wi-Fi configuration straightforward, and the accompanying app is user-friendly for monitoring.
- Solid Build: The inverter is noted for its robust and solid construction.
- Grid Testing: The inverter performs excellently when tested with grid power.
9. Warranty and Support
For detailed warranty information, technical support, or service, please contact PowMr customer service.