PowMr POW-HVM1K-12V, POW-HVM1.5K-24V

Contents

PowMr Hybrid Solar Inverter Charger User Manual

Models: POW-HVM1K-12V, POW-HVM1.5K-24V

Multi-function inverter/charger combining inverter, solar charger, and battery charger functions.

1. Introduction and Product Overview

This manual provides essential information for the assembly, installation, operation, and troubleshooting of your PowMr Hybrid Solar Inverter Charger. Please read it carefully before installation and operation, and keep it for future reference.

1.1 Key Features

  • Pure sine wave inverter output.
  • Configurable input voltage range for home appliances and personal computers via LCD settings.
  • Configurable battery charging current based on application via LCD settings.
  • Configurable AC/Solar Charger priority via LCD settings.
  • Compatible with mains voltage or generator power.
  • Automatic restart when AC power recovers.
  • Overload, over temperature, and short circuit protection.
  • Smart battery charger design for optimized battery performance.
  • Cold start function.

1.2 Product Components

The PowMr Hybrid Solar Inverter Charger integrates an inverter, solar charger, and battery charger into a single unit. It is designed to provide stable power to various loads in home or office environments, including motor-type appliances like fans, refrigerators, and air conditioners.

PowMr Hybrid Solar Inverter Charger with labeled LCD display and ports

Figure 1: Product Overview with Labeled Components

Key Components:

  1. LCD display
  2. Status indicator
  3. Charging indicator
  4. Fault indicator
  5. Function buttons (ESC, UP, DOWN, ENTER)
  6. Power on/off switch
  7. AC input terminals
  8. AC output terminals
  9. PV input terminals
  10. Battery input terminals
  11. Circuit breaker
  12. AC output receptacles

1.3 Unboxing and Overview Video

Video 1: Unboxing and feature overview of the PowMr Hybrid Solar Inverter Charger, showing included accessories and basic functionalities.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  • Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  • CAUTION: To reduce risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  • Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  • To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  • CAUTION: Only qualified personnel can install this device with battery.
  • NEVER charge a frozen battery.
  • For optimum operation, follow required specifications for cable size.
  • Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  • Strictly follow installation procedures when disconnecting AC or DC terminals.
  • GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Comply with local requirements and regulations.
  • NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
  • Warning: Only qualified service persons are able to service this device. If errors persist after troubleshooting, send the inverter/charger back to a local dealer or service center.

3. Setup (Installation)

3.1 Unpacking and Inspection

Upon receiving the package, inspect the unit for any damage. The package should contain:

  • Inverter unit x 1
  • User manual x 1
  • U-terminal x 2

3.2 Mounting the Unit

Consider the following points for installation:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install at eye level for easy LCD display reading.
  • Allow approximately 20 cm clearance to the sides and 50 cm above and below for proper air circulation.
  • Ambient temperature should be between 0°C and 55°C for optimal operation.
  • The recommended installation position is vertically on the wall.
  • Ensure sufficient space for heat dissipation and wiring.
Mounting dimensions and clearances for PowMr Hybrid Solar Inverter Charger

Figure 2: Recommended Mounting Clearances

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Install the unit by screwing two M4 or M5 screws.

3.3 Battery Connection

CAUTION: For safety and compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. Refer to the table below for required fuse or breaker size.

WARNING! All wiring must be performed by qualified personnel. Use appropriate cable for battery connection to reduce risk of injury.

ModelWire SizeCable (mm²)Torque Value (max)
1.0KW 12V1 x 6AWG145 Nm
1.5KW 24V1 x 6AWG145 Nm

Battery Connection Steps:

  1. Remove 18 mm of insulation from positive and negative conductors.
  2. Use bootlace ferrules on the wire ends with a proper crimping tool.
  3. Connect all battery packs as shown in the diagram below.
  4. Insert battery wires into inverter battery connectors and tighten bolts to 2 Nm (clockwise). Ensure correct polarity (+ to + and - to -).
Battery connection diagram for PowMr Hybrid Solar Inverter Charger

Figure 3: Battery Connection Diagram

3.4 AC Input/Output Connection

CAUTION: Install a separate AC breaker between the inverter and AC input power source. Recommended AC breaker: 20A for 1.0KW and 20A for 1.5KW.

CAUTION: Do NOT mis-connect input and output connectors. There are separate terminal blocks for 'IN' and 'OUT'.

ModelGaugeTorque Value
1.0KW 12V14 AWG2 Nm
1.5KW 24V12 AWG2 Nm

AC Input/Output Connection Steps:

  1. Before connecting, open the DC protector or disconnector.
  2. Remove 10 mm of insulation for six conductors. Shorten phase L and neutral conductor N by 3 mm.
  3. Insert AC input wires according to polarities (L: brown/black, N: blue, PE: yellow-green) and tighten terminal screws.
  4. Insert AC output wires according to polarities (L: brown/black, N: blue) and tighten terminal screws.
AC input and output wiring diagram for PowMr Hybrid Solar Inverter Charger

Figure 4: AC Input/Output Wiring Diagram

3.5 PV Connection

CAUTION: Install a separate DC circuit breaker between the inverter and PV modules.

WARNING! Use appropriate cable for PV module connection.

PV Module Selection Parameters:

  • Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter.
  • Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.

PV Array MPPT Voltage Range:

Inverter ModelMax. PV Array Open Circuit VoltagePV Array MPPT Voltage Range
1.0KW150Vdc20~150Vdc
1.5KW150Vdc30~150Vdc

PV Module Wire Connection Steps:

  1. Remove 10 mm of insulation from positive and negative conductors.
  2. Use bootlace ferrules on the wire ends with a proper crimping tool.
  3. Check correct polarity of wire connection from PV modules and PV input connectors. Connect positive (+) to positive (+) and negative (-) to negative (-).
PV module wire connection diagram for PowMr Hybrid Solar Inverter Charger

Figure 5: PV Module Wire Connection Diagram

3.6 Final Assembly

After connecting all wirings, replace the bottom cover by screwing in the four screws.

4. Operating the Inverter

4.1 Power ON/OFF

Once the unit is properly installed and batteries are connected, press the On/Off switch (located on the side of the case) to turn on the unit.

4.2 Operation and Display Panel

The front panel features an LCD display, three indicators, and four function keys to show operating status and input/output power information.

LED Indicators:

IndicatorColorStatusMessage
INV/ACGreenSolid OnOutput is powered by utility in Line mode.
FlashingOutput is powered by battery or PV in battery mode.
CHGGreenSolid OnBattery is fully charged.
FlashingBattery is charging.
FAULTRedSolid OnFault occurs in the inverter.
FlashingWarning condition occurs in the inverter.

Function Keys:

Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

4.3 LCD Settings

To enter setting mode, press and hold the ENTER button for 3 seconds. Use the UP or DOWN buttons to navigate through settings, and ENTER to confirm or ESC to exit. Key settings include:

  • Program 00: Exit Setting Mode (Escape, One-button restore)
  • Program 01: Output Source Priority (Utility first, Solar first, SBU priority, MKS priority)
  • Program 02: Maximum Charging Current (10A to 80A)
  • Program 03: AC Input Voltage Range (Appliances: 90-280VAC, UPS: 170-280VAC)
  • Program 05: Battery Type (AGM, Flooded, User-Defined)
  • Program 06: Auto Restart When Overload Occurs (Enable/Disable)
  • Program 07: Auto Restart When Over Temperature Occurs (Enable/Disable)
  • Program 09: Output Frequency (50Hz/60Hz)
  • Program 10: Output Voltage (220V, 230V, 240V)
  • Programs 11-36: Further detailed settings for utility charging current, voltage points, battery equalization, and more. Refer to the full PDF manual for a complete list and detailed descriptions of all LCD settings.

5. Maintenance

5.1 Anti-Dust Kit Clearance and Maintenance (Optional)

The inverter comes with an anti-dust kit installed from the factory. This kit helps protect the inverter from dust and improves reliability. It should be cleaned regularly.

  1. Remove the screws securing the dustproof case.
  2. Carefully remove the dustproof case and take out the air filter foam.
  3. Clean the air filter foam and the dustproof case.
  4. Re-assemble the dust-kit back to the inverter.

NOTICE: The anti-dust kit should be cleaned from dust every one month.

Diagram showing how to remove the anti-dust kit for cleaning

Figure 6: Anti-Dust Kit Removal for Maintenance

6. Troubleshooting

If you encounter issues with your inverter, refer to the following tables for fault and warning indicators. If problems persist after following these guidelines, contact customer support.

6.1 Fault Reference Code

Fault CodeFault EventIcon on
01Fan is locked when inverter is off.01
02Over temperature02
03Battery voltage is too high03
04Battery voltage is too low04
05Output short circuited or over temperature is detected by internal converter components.05
06Output voltage is too high.06
07Overload time out07
08Bus voltage is too high08
09Bus soft start failed09
51Over current or surge51
52Bus voltage is too low52
53Inverter soft start failed53
55Over DC voltage in AC output55
57Current sensor failed57
58Output voltage is too low58
59PV voltage is over limitation59

6.2 Warning Indicator

Warning CodeWarning EventAudible AlarmIcon Flashing
01Fan is locked when inverter is on.Beep three times every second01
03Battery is over-chargedBeep once every second03
04Low batteryBeep once every second04
07OverloadBeep once every 0.5 second07
10Output power deratingBeep twice every 3 seconds10
15PV energy is low.Beep twice every 3 seconds15
E9Battery equalizationNoneE9

7. Specifications

The following tables detail the technical specifications for the PowMr Hybrid Solar Inverter Charger models.

7.1 Line Mode Specifications

Feature1.0KW-12V1.5KW-24V
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage170Vac±10V (UPS); 90Vac±10V (Appliances)
Low Loss Return Voltage180Vac±10V (UPS); 100Vac±10V (Appliances)
High Loss Voltage280Vac±10V
High Loss Return Voltage270Vac±10V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionCircuit Breaker
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms

7.2 Inverter Mode Specifications

Feature1.0KW-12V1.5KW-24V
Rated Output Power1000VA/1000W1500VA/1500W
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac±5%
Output Frequency50Hz
Peak Efficiency94%
Overload Protection3s@≥150% load; 5s@100%~150% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage12Vdc24Vdc
Cold Start Voltage11.5Vdc23.0Vdc
Low DC Warning Voltage @ load < 50%11.25Vdc22.5Vdc
Low DC Warning Voltage @ load ≥ 50%11.0Vdc22Vdc
Low DC Warning Return Voltage @ load < 50%11.75Vdc23.5Vdc
Low DC Warning Return Voltage @ load ≥ 50%11.5Vdc23Vdc
Low DC Cut-off Voltage @ load < 50%10.75Vdc21.5Vdc
Low DC Cut-off Voltage @ load ≥ 50%10.5Vdc21Vdc
High DC Recovery Voltage15.5Vdc31Vdc
High DC Cut-off Voltage16.0Vdc32Vdc
No Load Power Consumption<28W

7.3 Charge Mode Specifications

Feature1.0KW-12V1.5KW-24V
Utility Charging Mode
Charging Algorithm3-Step
AC Charging Current (Max)40Amp (@VI/P=230Vac)
Bulk Charging Voltage (Flooded Battery)14.629.2
Bulk Charging Voltage (AGM/Gel Battery)14.128.2
Floating Charging Voltage13.5Vdc27Vdc
MPPT Solar Charging Mode
Max. PV Array Power600W1200W
PV Array MPPT Voltage Range20~150Vdc30~150Vdc
Max. PV Array Open Circuit Voltage150Vdc
Max Solar Charging Current40Amp
Max (AC+Solar) Charging Current80Amp

7.4 General Specifications

Feature1.0KW-12V1.5KW-24V
Safety CertificationCE
Operating Temperature Range-10°C to 50°C
Storage Temperature-15°C ~ 60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm286X240X91
Net Weight, kg33.5
1500W Hybrid Solar Inverter with key specifications like rated output power, nominal DC input voltage, PV array MPPT voltage range, max AC input voltage, and max charging current.

Figure 7: 1500W Model Key Specifications

PowMr Hybrid Solar Inverter Charger compatible with multiple battery types including AGM, GEL, FLD, LI, SLD, and USER defined settings.

Figure 8: Battery Type Compatibility

PowMr Hybrid Solar Inverter Charger with 360 degree protection features including short circuit, over current, over voltage, under voltage, over-load, backfill, over-temperature, and over charge protection.

Figure 9: Comprehensive Protection Features

PowMr Hybrid Solar Inverter Charger showing multi-protection functions and labeled ports: AC input, AC output, USB communication, RS485/WiFi communication, dry contact, grounding screw hole, overload protector, cooling fan, battery input, ON/OFF switch, PV input, touchable buttons, LED indicators, and LCD screen.

Figure 10: Multi-Protection Functions and Port Layout

PowMr Hybrid Solar Inverter Charger compatible with 95% household and office appliances, showing examples like air conditioners, fans, refrigerators, and coffee machines.

Figure 11: Appliance Compatibility

8. User Tips

  • For optimal performance and to prevent voltage drop, use thick cables for battery connections, especially for longer runs.
  • Be aware of the small openings for battery cables; plan your cable size accordingly before installation.
  • The 1KW model is designed for 12V systems, and the 1.5KW model for 24V systems. These models cannot be switched between voltages.
  • The inverter has sufficient surge capacity to start appliances like refrigerators and gas boilers.

9. Warranty and Support

For detailed warranty information and technical support, please contact PowMr directly using the information below. For a comprehensive guide to all settings and advanced features, please refer to the full user manual PDF.

Contact Information:

  • Tel/Fax: +86755-28219903
  • Email: support@powmr.com
  • Web: www.powmr.com
  • Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China

For the complete user manual, download the PDF: PowMr Hybrid Inverter User Manual (PDF)