1. Introduction
1.1 Purpose
This manual provides comprehensive instructions for the assembly, installation, operation, and troubleshooting of your ECGSOLAX Hybrid Solar Inverter. Please read this manual thoroughly before proceeding with installation and operation to ensure proper functioning and safety.
1.2 Scope
This document covers safety guidelines, installation procedures, and information regarding tools and wiring for the iXCEED 3K24-S120, iXCEED 3.6K24-S120, and iXCEED 5K48-S120 models.
2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION: To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION: Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow the required specifications to select appropriate cable size.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow the installation procedure when disconnecting AC or DC terminals. Refer to the INSTALLATION section for details.
- One 150A fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Comply with local requirements and regulations.
- NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
- Warning: Only qualified service persons are able to service this device. If errors persist after following the troubleshooting table, return the inverter/charger to a local dealer or service center for maintenance.
3. Product Overview
The ECGSOLAX Hybrid Solar Inverter is a multi-function inverter/charger designed to provide uninterruptible power support. It integrates an inverter, solar charger, and battery charger into a compact unit. The comprehensive LCD display allows for user-configurable settings such as battery charging current, AC/solar charger priority, and acceptable input voltage.
3.1 Key Features
- Capable of operating without a battery.
- Wide PV input voltage range: 60V~300Vdc.
- Excellent solar MPPT performance with up to 99% efficiency.
- Displays total and daily PV generated energy.
- Battery wake-up function.
- Communicates with battery BMS via RS-485 interface.
- Pure sine wave output.
- Configurable battery charging or discharging current via LCD settings.
- Configurable AC/Solar Charger priority via LCD settings.
- Built-in protections: Overload, Over temperature, Short circuit.
- Built-in dust filter kit for harsh environments.
- Supports 120Vac single phase and 240Vac split phase.
3.2 Basic System Architecture
The inverter/charger forms the core of a solar power system. A complete system typically includes the inverter/charger, a PV array, and a battery bank (optional for battery-less operation). It can also integrate with a generator or utility grid. Consult with your system integrator for specific architectural needs.
This inverter is designed to power various home and office appliances, including motor-type loads like tube lights, fans, refrigerators, and air conditioners.


3.3 Product Components
The inverter features a user-friendly interface and various connection ports for seamless integration into your solar power system.


4. Installation and Setup
4.1 Unpacking and Inspection
Upon receiving your inverter, carefully inspect the packaging and the unit for any signs of damage. The package should contain:
- The inverter unit x 1
- User manual x 1
- Screws x 2
4.2 Preparation and Mounting
Before making any electrical connections, remove the bottom cover of the unit by unscrewing the two screws. This provides access for wiring.
When selecting a mounting location, consider the following:
- Do not mount the inverter on flammable materials.
- Mount on a solid, non-combustible surface (e.g., concrete).
- Install the inverter at eye level for easy viewing of the LCD display.
- Ensure adequate air circulation for heat dissipation. Allow approximately 20 cm clearance on the sides and 50 cm above and below the unit.
- The optimal ambient temperature for operation is between 0°C and 55°C.
- The recommended installation position is vertically on a wall.
- Ensure sufficient space (50cm) for wiring removal and maintenance.

Install the unit by screwing two M6x50 screws into the wall.
4.3 Battery Connection
CAUTION: For safety and compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. This is crucial even if a disconnect device is not required in some applications. Refer to the table below for recommended fuse or breaker sizes.
WARNING: All wiring must be performed by qualified personnel. Use appropriate cable sizes for battery connection to ensure system safety and efficient operation.
| Model | Wire Size | Cable (mm²) | Torque Value (max) |
|---|---|---|---|
| 3KW/3.6KW | 1x 3 AWG | 25 | 6 N-m |
| 5KW | 1x 3 AWG | 25 | 6 N-m |
Follow these steps for battery connection:
- Remove 18 mm of insulation from the positive and negative conductors.
- It is recommended to use bootlace ferrules on the ends of the wires with a proper crimping tool.
- Connect all battery packs as shown in the diagram.
- Insert the battery wires into the battery connectors of the inverter, ensuring the bolts are tightened with a torque of 6 N-m in a clockwise direction. Verify correct polarity at both the battery and the inverter/charger, and ensure conductors are tightly screwed into the battery terminals.
WARNING: Shock Hazard! Installation must be performed with care due to high battery voltage in series.
CAUTION: Before making the final DC connection or closing the DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) is connected to negative (-).

4.4 AC Input/Output Connection
CAUTION: Install a separate AC breaker between the inverter and the AC input power source. This ensures secure disconnection during maintenance and protection from overcurrent. Recommended AC breaker specs: 32A for 3KW/3.6KW, 50A for 5KW.
CAUTION: The unit has two terminal blocks marked "IN" and "OUT". Do NOT mis-connect input and output connectors.
WARNING: All wiring must be performed by qualified personnel. Use appropriate cable sizes for AC input connection.
| Model | Gauge | Cable (mm²) | Torque Value |
|---|---|---|---|
| 3KW/3.6KW | 10 AWG | 6 | 2 N-m |
| 5KW | 8AWG | 10 | 2 N-m |
Follow these steps for AC input/output connection:
- Before making AC input/output connections, ensure the DC protector or disconnector is open.
- Remove 10 mm of insulation from the six conductors. Shorten phase L and neutral conductor N by 3 mm.
- Insert AC input wires according to the polarities indicated on the terminal block and tighten the terminal screws. Ensure the PE protective conductor (yellow-green) is connected first.
- Then, insert AC output wires according to the polarities indicated on the terminal block and tighten the terminal screws. Ensure the PE protective conductor (yellow-green) is connected first.
- Make sure all wires are securely connected.
WARNING: Ensure the AC power source is disconnected before attempting to hardwire to the unit.
Wiring Color Code:
- Ground: Yellow-green
- LINE: Brown or Black
- Neutral: Blue
4.5 PV Connection
CAUTION: Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.
WARNING: Use appropriate cable for PV module connection. Recommended cable size: 1x 12AWG (4 mm²) with a torque value of 1.2 N-m.
PV Module Selection: When selecting PV modules, consider the following:
- Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter (300Vdc).
- Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.
For example, using 550Wp PV modules, recommended configurations are provided in the manual to ensure optimal performance.
Follow these steps for PV module connection:
- Remove 10 mm of insulation from the positive and negative conductors.
- It is recommended to use bootlace ferrules on the ends of the wires.
- Check the correct polarity of wire connection from PV modules and PV input connectors. Connect the positive pole (+) of the connection wire to the positive pole (+) of the PV input connector. Connect the negative pole (-) of the connection wire to the negative pole (-) of the PV input connector. Screw the two wires tightly in a clockwise direction.
4.6 Communication Connection
The inverter supports BMS RS-485, USB, and Wi-Fi cloud communication.
BMS RS-485 Communication:
- Use the supplied communication cable to connect to the inverter and the Lithium battery Pack's BMS (PYLON communication protocol).
- When communication is established, the battery icon "Li" will blink.
- Reconfigure charging voltage, charging current, battery discharge cut-off voltage, and SOC according to the Lithium battery BMS parameters.
- For lead-acid battery packs, BMS RS-485 communication is not used, and the screen icon displays "SLA".
USB Communication:
- Use a USB cable to connect the inverter to a PC.
- Use the upper computer software to view inverter information.
Wi-Fi Cloud Communication (Optional):
- Use the supplied communication cable to connect the inverter to a Wi-Fi module or directly connect to the inverter and WiFi PLUG.
- Download the APP from the APP store and refer to the "WiFi Plug Quick Installation Guideline" to set up the network and register.
- The inverter status will be displayed on the mobile phone APP or computer webpage.
4.7 Final Assembly
After all wiring connections are complete, reattach the bottom cover by screwing in the four screws.
5. Operation
5.1 Power ON/OFF
Once the unit is properly installed and the batteries are connected, press the On/Off switch (located on the bottom of the case) to turn on the unit.
5.2 Operation and Display Panel
The front panel of the inverter features an LCD display, three indicators, and four function keys to show operating status and power information.
| LED Indicator | Color | Status | Message |
|---|---|---|---|
| INV | Green | Solid On | Output is powered by PV (main) or Bat in Inverter mode. |
| Flashing | Output is powered by bat (main) or PV in Inverter mode. | ||
| BYPASS | Yellow | Solid On | Output is powered by utility in Line mode. |
| Flashing | Output is powered by utility and PV/Bat in Hybrid mode. | ||
| FAULT | Red | Solid On | Fault condition occurs in the inverter. |
| Flashing | Warning condition occurs in the inverter. |
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or display in-turns |
5.3 LCD Display Icons and Information
The LCD displays various icons and information related to input source, configuration, fault conditions, output, and battery status. These include AC, PV, INV indicators, warning/fault codes, output voltage/frequency, load percentage, and battery SOC level.
The LCD display information can be cycled through by pressing the "UP" or "DOWN" keys, or the "ENTER" key. Information displayed includes: Output voltage/load power, Output frequency/load current, PV voltage/PV current, PV generated energy (total and daily), Battery voltage/Battery SOC, Battery charging current/Battery power, Unit temperature/Battery discharging current, Input AC voltage/Input AC frequency, Unit firmware version, and calendar clock.
5.4 LCD Settings
To enter setting mode, press and hold the "ESC" and "ENTER" buttons together for more than 10 seconds. Use "UP" or "DOWN" to select programs, and "ENTER" to confirm or "ESC" to exit.
Key settings include:
- Output Voltage (Program 01): Default 230V. Options: 220V, 230V, 240V.
- Output Frequency (Program 02): Default 50Hz. Options: 50Hz, 60Hz.
- Output Source Priority (Program 03): Configures how the inverter prioritizes power sources (Solar first, SBU priority, Utility first).
- Battery Type (Program 04): Selects battery type (Li Battery, Lead-acid Battery, User-defined).
- Maximum Battery Charging Voltage (Program 05): Sets the upper limit for battery charging.
- Minimum Battery Discharging Voltage (Program 06): Sets the lower limit for battery discharge.
- Battery SOC Reserved for Backup (Program 07): Configures the State of Charge reserved for backup power (Higher SOC Reserved, Lower SOC Reserved).
- Maximum Battery Charging Current (Program 08): Sets the maximum current for battery charging.
- Maximum Battery Discharging Current (Program 09): Sets the maximum current for battery discharging.
- Under Voltage SOC Value Setting (Program 10): Sets the SOC value at which the inverter will switch to another power source due to low battery voltage.
- Enable Second Output and Set SOC Value (Program 11): For specific models (2.2KW/3.2KW/4.2KW models do not have this function).
- Enabling/Disabling Grid Connection Function (Program 12): Default Off (SOF).
- Alarm Control (Program 13): Enables or disables alarms (Default: Alarm on).
- Restore Factory Setting (Program 14): Resets all settings to factory defaults.
- Calendar Clock Setting (Programs 15-19): Sets Year, Month, Day, Hour, Minute for the internal clock.
5.5 Operating Mode Description
The inverter operates in different modes depending on the power sources available and configured priorities:
- Standby Mode: Inverter is off, no AC output, but batteries can be charged by solar or utility.
- Bypass Mode: Load power is supplied only by the mains. Battery can be charged by mains or solar energy.
- Hybrid Mode: Load power is supplied by mains and solar energy or battery. Battery can also be charged by superfluous solar energy. This mode has several sub-conditions:
- If the battery is not connected, solar energy and utility provide loads together.
- If the battery is weak or solar energy is insufficient, or "utility first" is selected, solar energy and utility provide loads, and the battery is charged by extra solar energy.
- If "solar first" or "solar and battery first" is selected and battery SOC is high, battery and utility provide loads, and battery is charged by superfluous solar energy.
- Inverter Mode: Load power is provided by solar energy and battery together. Battery can also be charged by superfluous solar energy. This mode has sub-conditions similar to Hybrid mode, prioritizing solar and battery.
6. Maintenance
To ensure the longevity and optimal performance of your ECGSOLAX Hybrid Solar Inverter, regular maintenance is recommended.
- Dust Filter: The inverter is equipped with a built-in dust filter kit. Regularly inspect and clean the dust filter to prevent accumulation, which can hinder cooling and affect performance.
- Ventilation: Ensure that the inverter's inlet and outlet are not blocked. Maintain recommended clearances around the unit for proper airflow.
- Connections: Periodically check all electrical connections (battery, AC input/output, PV) to ensure they are secure and free from corrosion. Loose connections can lead to poor performance or safety hazards.
- Battery Health: Monitor battery voltage and SOC levels regularly. Ensure batteries are not frozen and are within their optimal operating temperature range.
- Environmental Conditions: Keep the inverter in an environment within the specified operating temperature and humidity ranges.
- Firmware Updates: If available, consider updating the inverter's firmware via USB or Wi-Fi communication to benefit from performance improvements and new features.
7. Troubleshooting
This section provides solutions to common issues you might encounter with your inverter. For persistent problems, contact a qualified service person or your dealer.
| Problem | LCD/LED/Buzzer | Explanation / Possible Cause | What to do |
|---|---|---|---|
| Mains power often outages, battery backup time is insufficient | The inverter works properly. | Poor battery performance or small capacity; Battery SOC is low during power outage. | Increase battery capacity; Select "SBU" priority and set "Battery SOC Reserved" to "High (SoH)", or select "UTL" mains priority to keep battery SOC high. |
| Electricity supply is stable, but electricity bill has not decreased significantly | The inverter works properly. | Insufficient use of solar energy or batteries. | If mains is stable, select SBU and set Battery SOC Reserved to "Low (SoL)" to reduce mains power supply by making full use of solar power and battery energy storage. |
| No reaction after battery is connected | No display | Battery voltage is too low; Battery polarity is reversed; Battery input is insured damaged. | 1. Check battery connection. 2. Charge or replace battery. 3. Replace insurance. |
| After battery is connected, it automatically shuts down during startup | The LCD/LEDs and buzzer work for 3S and then turn off. | Battery voltage is too low. | 1. Re-charge battery. 2. Replace battery. |
| When mains is connected, LCD voltage of inverter is 0 | Input voltage is displayed as O on the LCD and green LED is flashing. | Input protector is tripped. | Check if AC breaker is tripped and AC wiring is connected well. |
| Green LED is flashing. | Insufficient quality of AC power. | 1. Check if AC wires are too thin and/or too long; 2. Check whether mains voltage is normal or input voltage range is set correctly. | |
| Green LED is flashing. | Set "Solar First" as the priority of output source. | Change output source priority to Utility first. | |
| When unit is turned on, internal relay is switched on and off repeatedly | LCD display and LEDs are flashing. | Battery is disconnected. | Check if battery wires are connected well. |
| Buzzer beeps continuously and red LED is on | Fault code 01 | Overload error. | Reduce the connected load by switching off some equipment. |
7.1 Fault Reference Codes
The inverter's LCD will display specific fault codes to indicate various issues:
| Fault Code | Fault Event | What to do |
|---|---|---|
| 01 | Overload time out | Reduce the connected load by switching off some equipment. |
| 02 | Over temperature fault: The temperature of the radiator inside the inverter exceeds 80°C. | Check whether the inlet and outlet of the inverter are blocked or the ambient temperature is too high. |
| 03 | The inverter overflows and internal components fail | Restart the inverter. If it does not work properly, return to the repair center. |
| 04 | Output short circuit | Check if wiring is connected well and remove abnormal load. |
| 05 | High output voltage | Restart the inverter. If it does not work properly, return to the repair center. |
| 06 | Low output voltage | Restart the inverter. If it does not work properly, return to the repair center. |
| 07 | Bus voltage is abnormal | Restart the inverter. If it does not work properly, return to the repair center. |
| 08 | Bus voltage is too high | Restart the inverter. If it does not work properly, return to the repair center. |
| 09 | Bus voltage is too low | Restart the inverter. If it does not work properly, return to the repair center. |
| 10 | PV Over current | Check if wiring is connected well or replace the fan. |
| 11 | Fan error | Check if wiring is connected well or replace the fan. |
| 12 | Battery voltage is too high. | 1. Check if wiring is connected well; 2. Check if spec and quality of batteries are meet requirements. |
| 13 | Battery voltage is too low. | 1. Check if wiring is connected well; 2. Check if spec and quality of batteries are meet requirements. |
| 14 | The battery not connected | 1. Check if wiring is connected well; 2. Check if spec and quality of batteries are meet requirements. |
| 15 | Temperature sensor wire disconnected | Restart the inverter. If it does not work properly, return to the repair center. |
8. Specifications
The following tables detail the technical specifications for the ECGSOLAX Hybrid Solar Inverter models.
| Category | iXCEED 3K-24S120 | iXCEED 3.6K24-S120 | iXCEED 5K48-S120 | |
|---|---|---|---|---|
| PV Array | ||||
| Max. PV Array Power | 3600W | 4200W | 6000W | |
| Max. PV Array Open-Circuit Voltage | 300Vdc | |||
| Start-up Voltage | 60Vdc | |||
| MPPT Operating Voltage Range | 70-280Vdc | |||
| MPPT Efficiency | 99% | |||
| Nominal Input Voltage | 250Vdc | |||
| Max. Input Current MPPT | 30A | |||
| Battery | ||||
| Battery Type | Lead-acid/Li-ion | |||
| Nominal Battery Voltage | 24V | 48V | ||
| Battery Voltage Range | 21-29V | 42-58V | ||
| Max. AC Charging Current | 40A | 50A | 50A | |
| Max. PV Charging Current | 80A | 100A | 100A | |
| Max. Continuous Discharging Current | 100A | 100A | 120A | |
| AC Input | ||||
| Nominal Voltage | 120Vac | |||
| Voltage Range | 90-140Vac | |||
| High Loss Voltage | 140Vac±7V | |||
| Low Loss Voltage | 90Vac±7V(UPS) | |||
| Frequency | 50/60Hz (Auto sensing) | |||
| High Loss Frequency | 65Hz | |||
| Low Loss Frequency | 45Hz | |||
| Max. Input Current | 40A | 50A | ||
| AC Output | ||||
| Nominal Voltage | 120Vac±5% | |||
| Output Voltage Waveform | Pure Sine Wave | |||
| Rated Output Power | 3000VA/3000W | 4200VA/4200W | 5000VA/5000W | |
| Peak Output Power | 4500VA | 5400VA | 7500VA | |
| Nominal Output Frequency | 50/60Hz | |||
| Transfer Time | 10ms | |||
| Max. PV to AC Efficiency | 96.50% | 96.50% | ||
| Max. Battery to AC Efficiency | 91.00% | 93.00% | ||
| Protection | ||||
| Over Temperature Protection | Yes | |||
| Overload Protection | 3s@≥150% load; 10s@110%~150% load | |||
| General Data | ||||
| Operating Temperature Range | -10 ~ +50°C | |||
| Safety Certification | CE | |||
| Relative Humidity | 0~95% Relative Humidity (Non-condensing) | |||
| Max. Operating Altitude | < 4000m | |||
| Cooling Method | Intelligent Fan cooling | |||
| Display | LED + LCD | |||
| Communication with BMS | RS-485 | |||
| Communication with Cloud | WiFi/4G | |||
| Degree of Protection | IP21 | |||
| Weight | 6.5kg | 8.4kg | ||
| Dimension (W*H*D) | 348*95mm*290mm | 370*107*320mm | ||
| Mounting Method | Wall Mounted | |||
9. User Tips
- When testing the inverter, ensure you connect sufficient load to fully evaluate its performance and capacity. For example, a 5KW model might only show partial load if not enough equipment is connected.
10. Warranty and Support
For warranty information, please refer to the documentation provided at the time of purchase or contact your seller. For technical support or service, please reach out to your local dealer or the ECGSOLAX service center. The user manual (PDF) can be found at this link.