PowMr POW-HVM Series

Contents

PowMr Solar Hybrid Inverter User Manual

Model: POW-HVM Series | Brand: PowMr

PowMr Hybrid Inverter with 6200W/4200W power, 24/48V/230V AC, 500Vdc Max PV Input, MPPT 120A

PowMr Hybrid Inverter with 6200W/4200W power, 24/48V/230V AC, 500Vdc Max PV Input, MPPT 120A.

1. Introduction

This manual describes the assembly, installation, operation, and troubleshooting of the PowMr Solar Hybrid Inverter. Please read this manual carefully before installations and operations and keep it for future reference. This document provides safety and installation guidelines as well as information on tools and wiring.

1.1 Features

  • Pure sine wave inverter
  • Configurable input voltage range for home appliances and personal computers via LCD setting
  • Configurable battery charging current based on applications via LCD setting
  • Configurable AC/Solar Charger priority via LCD setting
  • Compatible with mains voltage or generator power
  • Auto restart while AC is recovering
  • Overload/Over temperature/short circuit protection
  • Smart battery charger design for optimized battery performance
  • Cold start function

1.2 Basic System Architecture

The inverter/charger combines functions of an inverter, solar charger, and battery charger to offer uninterruptible power support. Its comprehensive LCD display allows user-configurable and easy-accessible button operation.

The basic application involves connecting solar power, a generator or utility, the solar inverter, external battery packs, and home appliances. The inverter manages the power flow between these components to ensure continuous power supply.

Diagram illustrating multiple charging and output modes for the inverter

This diagram illustrates various charging and output modes, including Solar priority, Solar+Utility, Only solar, SBU mode, and Utility priority, demonstrating how the inverter manages power sources.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION – To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION – Only qualified personnel can install this device with battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for details.
  10. One piece of 150A fuse is provided as over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS – This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
  12. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
  13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
Inverter protection features including short circuit, over current, over voltage, and over temperature

The inverter is equipped with 360-degree protection features, including safeguards against Short Circuit, Over Current, Over Voltage, Under Voltage, Over-Load, Backfill, Over-Temperature, and Over Charge.

3. Setup (Installation)

3.1 Unpacking and Inspection

Before installation, please inspect the unit. Ensure nothing inside the package is damaged. You should have received the unit and this user manual.

3.2 Mounting the Unit

Consider the following points when selecting where to install the inverter:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install at eye level for easy LCD display reading.
  • Allow a clearance of approximately 20 cm to the side and 50 cm above and below the unit for proper air circulation and heat dissipation.
  • The ambient temperature should be between 0°C and 55°C for optimal operation.
  • The recommended installation position is vertically on the wall.
  • Ensure enough space around the machine for adequate heat dissipation and wire removal.

WARNING: SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Install the unit by screwing two M6 screws. Before connecting all lines, remove the screws under the machine and remove the bottom cover plate.

3.3 Battery Connection

CAUTION: For safety and regulation compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. Refer to the table below for required fuse or breaker size.

WARNING! All wiring must be performed by qualified personnel. Use appropriate cable for battery connection to reduce risk of injury.

ModelWire SizeCable (mm²)Torque value (max)
3.6KW/4.2KW/6.2KW1 x 2AWG252 Nm

Battery Connection Steps:

  1. Remove 18 mm of insulation sleeve for positive and negative conductors.
  2. Suggest putting bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Connect all battery packs as shown in the diagram (e.g., for 3.6KW/4.2KW, two 12V batteries in series; for 6.2KW, four 12V batteries in series).
  4. Insert the battery wires flatly into the inverter's battery connectors. Tighten bolts with a torque of 2 Nm in a clockwise direction. Ensure correct polarity (+ to + and - to -) and tight connections. Recommended tool: #2 Pozi Screwdriver.

WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.

CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).

3.4 AC Input/Output Connection

CAUTION!! Install a separate AC breaker between the inverter and AC input power source. This ensures safe disconnection during maintenance and over-current protection. Recommended AC breaker spec: 32A for 3.6KW/4.2KW, 50A for 6.2KW.

CAUTION!! There are two terminal blocks: "IN" and "OUT". Do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by qualified personnel. Use appropriate cable for AC input connection. Refer to the table below for recommended cable size.

Suggested Cable Requirement for AC Wires:

ModelGaugeCable (mm²)Torque Value
3.6KW/4.2KW12 AWG41.2 Nm
6.2KW10 AWG61.2 Nm

AC Input/Output Connection Steps:

  1. Before making AC input/output connection, open the DC protector or disconnector first.
  2. Remove 10mm of insulation sleeve for six conductors. Shorten phase L and neutral conductor N by 3 mm.
  3. Insert AC input wires according to polarities (L→LINE brown or black, N→Neutral blue) indicated on the terminal block and tighten the terminal screws.
  4. WARNING: Be sure that AC power source is disconnected before attempting to hardwire to the unit.
  5. Insert AC output wires according to polarities (L→LINE brown or black, N→Neutral blue) indicated on the terminal block and tighten the terminal screws.
  6. Make sure the wires are securely connected.

CAUTION: Appliances like air conditioners require 2-3 minutes to restart. If a power shortage occurs and recovers quickly, it can damage connected appliances. Check if your appliance has a time-delay function. Otherwise, the inverter may trigger an overload fault and cut off output, but internal damage to the appliance can still occur.

3.5 PV Connection

CAUTION: Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.

WARNING! Use appropriate cable for PV module connection for system safety and efficient operation. Refer to the table below for recommended cable size.

ModelWire SizeCable (mm²)Torque value (max)
3.6KW/4.2KW/6.2KW1 x 12AWG41.2 Nm

PV Module Selection:

When selecting PV modules, consider these parameters:

  • Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter.
  • Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.
INVERTER MODEL3.6KW/4.2KW6.2KW
Max. PV Array Open Circuit Voltage500Vdc
PV Array MPPT Voltage Range60Vdc~450Vdc

PV Module Wire Connection Steps:

  1. Remove 10 mm of insulation sleeve for positive and negative conductors.
  2. Suggest putting bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Check correct polarity of wire connection from PV modules and PV input connectors. Connect positive pole (+) of connection wire to positive pole (+) of PV input connector. Connect negative pole (-) of connection wire to negative pole (-) of PV input connector. Recommended tool: 4mm blade screwdriver.

3.6 Final Assembly

After connecting all wirings, put the bottom cover back by screwing two screws.

3.7 Communication Connection

Wi-Fi Cloud Communication (option):

Use the supplied communication cable to connect to the inverter and Wi-Fi module. Download the APP, install it, and refer to the "Wi-Fi Plug Quick Installation Guideline" to set up the network and register. The inverter status will be shown by the mobile phone APP or computer webpage.

GPRS Cloud Communication (option):

Use the supplied communication cable to connect to the inverter and GPRS module, then apply external power to the GPRS module. Download the APP, install it, and refer to the "GPRS RTU Quick Installation Guideline" to set up the network and register. The inverter status will be shown by the mobile phone APP or computer webpage.

Battery Communication:

Communication between the battery and the inverter is realized through the battery communication interface, allowing the inverter and lithium battery to exchange information at a Baud rate of 9600.

Lithium Battery and Inverter Connection:

Use power cables and communication cables for lithium batteries and inverters. Ensure correct installation of lithium battery and inverter positive and negative positions. The RJ45 connector of the communication cable connects to the BMS port of the inverter, and the other RJ45 connector connects to the RS485 port of the lithium battery. Before connecting, ensure both the lithium battery and inverter are turned off. It is recommended to install a circuit breaker for the power cables of the lithium battery and the inverter battery interface to prevent sparks.

The lithium battery communication cable interface involves connecting an RJ45 cable from the inverter's BMS port to the lithium battery's RS485 port. The inverter connection port includes PWR, RUN, ALM, and SOC indicators, while the lithium battery connection diagram shows RST, ADD, DRY CONTACT, RS485, CAN, RS232, RS485A, and RS485B ports.

4. Operating

4.1 Power ON/OFF

Once the unit is properly installed and the batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.

4.2 Operation and Display Panel

The front panel of the inverter features an LCD display, three indicators, and four function keys, providing operating status and input/output power information.

LED Indicators:

IndicatorColorStateMessage
INV/ACGreenSolid OnOutput is powered by utility in Line mode.
FlashingOutput is powered by battery or PV in battery mode.
CHGGreenSolid OnBattery is fully charged.
FlashingBattery is charging.
FAULTRedSolid OnFault occurs in the inverter.
FlashingWarning condition occurs in the inverter.

Function Keys:

Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

4.3 LCD Display Icons

The LCD display shows various icons to indicate input source, configuration, fault information, output information, battery information, load information, and mode operation.

Mode Operation Information:

IconFunction Description
Indicates unit connects to the mains.
Indicates unit connects to the PV panel.
AC BYPASSIndicates load is supplied by utility power.
Indicates the utility charger circuit is working.
Indicates the DC/AC inverter circuit is working.
Indicates unit alarm is disabled.

4.4 LCD Setting

Press and hold the ENTER button for 3 seconds to enter setting mode. Use the UP or DOWN buttons to select programs, then ENTER to confirm or ESC to exit. Key settings include:

  • Program 00 (Exit setting mode): Options for one-button restore settings.
  • Program 01 (Output source priority): Configure load power source priority (Utility first, Solar first, SBU priority, MKS priority).
  • Program 02 (Maximum charging current): Configure total charging current for solar and utility chargers.
  • Program 03 (AC input voltage range): Set acceptable AC input voltage range (e.g., 90-280VAC for appliances, 170-280VAC for UPS).
  • Program 05 (Battery type): Select battery type (AGM, Flooded, User-Defined, LIB-485). If LIB-485 is selected, items 12, 13, and 29 are displayed in percentage, and maximum charging current cannot be modified.
  • Program 12 (SBU mode SOC point for utility source): Set battery SOC point for switching to utility source input when SBU mode is selected.
  • Program 13 (SBU mode SOC point for battery mode): Set battery SOC point for switching to battery mode when SBU mode is selected.
  • Program 16 (Charger source priority): Configure charger source priority (Solar first, Solar and Utility, Only Solar).
  • Program 29 (LIB-485 low SOC shutdown point): Set battery low SOC shutdown point if LIB-485 is selected.
  • Program 30 (Battery equalization): Enable or disable battery equalization.
  • Program 43 (Lithium battery protocol): Select matching battery protocol (PYLON, PACE) if LIB-485 is selected in Program 05.

CAUTION: When the battery type is set to "LIB-485", the setting items 12, 13, and 29 are displayed in percentage. The user cannot modify the maximum charging current. If communication fails, the inverter will cut off the output.

4.5 Display Setting

The LCD display information can be switched by pressing the "UP" or "DOWN" key. Information displayed includes input voltage, input frequency, PV voltage, charging current, charging power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, DC discharging current, and main CPU Version.

4.6 Operating Mode Description

The inverter supports various operating modes:

  • Standby Mode/Power Saving Mode: No output is supplied, but the unit can still charge batteries. In power saving mode, the inverter output is off if the connected load is very low.
  • Line Mode: The unit provides output power from the mains and charges the battery.
  • Grid-Tie Operation: When working in Grid-Tie mode, the unit flashes every 3 seconds. It can operate in off-grid (solar energy powers loads first, then charges) or hybrid mode (solar energy powers loads first, then charges, excess energy feeds to grid).
  • Battery Mode: The unit provides output power from the battery and solar power.

4.7 Battery Equalization Description

Equalization reverses the buildup of negative chemical effects like stratification and removes sulfate crystals from battery plates, optimizing battery performance. You must enable battery equalization in LCD setting program 30. Equalization can be applied by setting an interval in program 35 or by activating it immediately in program 36.

During the Equalize stage, the controller charges the battery until it reaches the equalization voltage, then maintains this voltage. If the battery equalized time expires and the voltage hasn't reached the target, the controller extends the time. If the voltage is still low after the timeout, equalization stops, and the unit returns to float stage.

Battery Equalization Stages Graph

This graph illustrates the Battery Equalization stages: Bulk, Absorption, Float, Equalize, Float, showing voltage levels over time.

4.8 Mains and Lithium Battery Activation Function

  1. After 90 seconds of mains power connection, the inverter connects to the mains and starts working.
  2. If the inverter is in lithium battery mode (item 05 is Llb or Llb-485), and the mains are connected but the battery is not, the mains activation function is automatically enabled.

5. Maintenance

5.1 Clearance and Maintenance for Anti-Dust Kit

Every inverter comes with an anti-dust kit installed from the factory. The inverter automatically detects this kit and activates an internal thermal sensor to adjust internal temperature. This kit also protects the inverter from dust, increasing product reliability in harsh environments.

Maintenance Steps:

  1. Loosen the screw on the top of the inverter in a counterclockwise direction.
  2. Remove the dustproof case and take out the air filter foam.
  3. Clean the air filter foam and dustproof case.
  4. After cleaning, re-assemble the dust-kit back to the inverter.

NOTICE: The anti-dust kit should be cleaned from dust every one month.

Diagram showing how to remove the anti-dust kit for cleaning

This diagram illustrates the process of loosening the screw, removing the dustproof case, and accessing the air filter foam for cleaning.

6. Troubleshooting

6.1 Fault Reference Code

Fault CodeFault Event
01Fan is locked when inverter is off.
02Over temperature
03Battery voltage is too high
04Battery voltage is too low
05Output short circuited or over temperature is detected by internal converter components.
06Output voltage is too high.
07Overload time out
08Bus voltage is too high
09Bus soft start failed
51Over current or surge
52Bus voltage is too low
53Inverter soft start failed
55Over DC voltage in AC output
57Current sensor failed
58Output voltage is too low
59PV voltage is over limitation

6.2 Warning Indicator

Warning CodeWarning EventAudible Alarm
01Fan is locked when inverter is on.Beep three times every second
03Battery is over-chargedBeep once every second
04Low batteryBeep once every second
07OverloadBeep once every 0.5 second
10Output power deratingBeep twice every 3 seconds
15PV energy is low.Beep twice every 3 seconds
E9Battery equalizationNone
bPBattery is not connectedNone

6.3 General Troubleshooting

ProblemExplanation / Possible CauseWhat to do
Unit shuts down automatically during startup process.The battery voltage is too low (<1.91V/Cell)1. Re-charge battery.
2. Replace battery.
No response after power on.1. The battery voltage is far too low. (<1.4V/Cell)
2. Internal fuse tripped.
1. Contact repair center for replacing the fuse.
2. Re-charge battery.
3. Replace battery.
Mains exist but the unit works in battery mode.Insufficient quality of AC power. (Shore or Generator)1. Check if AC wires are too thin and/or too long.
2. Check if generator (if applied) is working well or if input voltage range setting is correct.
When the unit is turned on, internal relay is switched on and off repeatedly.Battery is disconnected.Check if battery wires are connected well.
Buzzer beeps continuously and red LED is on.Temperature of internal converter component is over 120°C.Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.
Battery is over-charged.Return to repair center.
The battery voltage is too high.Check if spec and quantity of batteries are meet requirements.
Fan faultReplace the fan.
Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac)1. Reduce the connected load.
2. Return to repair center
Internal components failed.Return to repair center.
Over current or surge.Restart the unit, if the error happens again, please return to repair center.

7. Specifications

Specifications for 4.2KW Hybrid Solar Inverter

Detailed specifications for the 4.2KW Hybrid Solar Inverter, including AC output power, charging current, PV array voltage, and no-load power consumption.

7.1 Line Mode Specifications

INVERTER MODEL3.6KW4.2KW6.2KW
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage170Vac±7V (UPS); 90Vac±7V (Appliances)
Low Loss Return Voltage180Vac±7V (UPS); 100Vac±7V (Appliances)
High Loss Voltage280Vac±7V
High Loss Return Voltage270Vac±7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionCircuit Breaker
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)

7.2 Inverter Mode Specifications

INVERTER MODEL3.6KW4.2KW6.2KW
Rated Output Power3.6KW4.2KW6.2KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac±5%
Output Frequency50Hz
Peak Efficiency93%
Overload Protection3s@≥150% load; 5s@101%~150% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage24Vdc48Vdc
Cold Start Voltage23.0Vdc46.0Vdc
Low DC Warning Voltage @ load < 50%22.0Vdc44.0Vdc
Low DC Warning Voltage @ load ≥ 50%21.0Vdc42.0Vdc
Low DC Warning Return Voltage @ load < 50%22.5Vdc45.0Vdc
Low DC Warning Return Voltage @ load ≥ 50%22.0Vdc44.0Vdc
Low DC Cut-off Voltage @ load < 50%20.5Vdc41.0Vdc
Low DC Cut-off Voltage @ load ≥ 50%20.0Vdc40.0Vdc
High DC Recovery Voltage32Vdc62Vdc
High DC Cut-off Voltage33Vdc63Vdc
No Load Power Consumption30W35W50W

7.3 Two Load Output Power

INVERTER MODEL3.6KW4.2KW6.2KW
Full Load3600W4200W6200W
Maximum Main Load3600W4200W6200W
Second Load Range720W-2520W840W~2940W1240W~4340W
Main Load Cut Off Voltage22VDC44VDC
Main Load Return Voltage26VDC52VDC

7.4 Charge Mode Specifications

INVERTER MODEL3.6KW4.2KW6.2KW
Utility Charging Mode
Charging Algorithm3-Step
AC Charging Current (Max)100Amp (@VI/P=230Vac)
Bulk Charging Flooded Battery Voltage29.258.4
Bulk Charging AGM / Gel Battery Voltage28.256.4
Floating Charging Voltage27Vdc54Vdc
MPPT Solar Charging Mode
Max. PV Array Power6200W6500W
Nominal PV Voltage240Vdc360Vdc
PV Array MPPT Voltage Range60Vdc~500Vdc
Max. PV Array Open Circuit Voltage500Vdc
Max Charging Current (AC charger plus solar charger)120Amp120Amp120Amp

7.5 Grid-Tie Operation

INVERTER MODEL3.6KW4.2KW6.2KW
Nominal Output Voltage220/230/240 VAC
Feed-in Grid Voltage Range195~253VAC
Feed-in Grid Frequency Range50±1Hz/60±1Hz
Nominal Output Current15.7A18.2A26.9A
Power Factor Range>0.99
Maximum Conversion Efficiency (DC/AC)97%

7.6 General Specifications

INVERTER MODEL3.6KW4.2KW6.2KW
Safety CertificationCE
Operating Temperature Range-10°C to 50°C
Storage temperature-15°C~60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm358×442×116
Net Weight, kg8.08.08.9

7.7 Approximate Back-up Time Table

ModelLoad (W)Backup Time @ 24Vdc 100Ah (min)Backup Time @ 24Vdc 200Ah (min)
3.6KW/4.2KW3004491100
600222525
900124303
120095227
150068164
180056126
210048108
24003594
27003174
32002867
36002560
42002253
6.2KW5006131288
1000268613
1500158402
2000111271
250090215
320076182
350065141
400050112
450044100
50004090
62003680

Note: Backup time depends on the quality, age, and type of battery. Specifications of batteries may vary depending on different manufacturers. The final interpretation right of this product belongs to the company.

8. User Tips

  • Always prioritize safety: Carefully read and understand all safety instructions before installation and operation.
  • Ensure proper wiring: Use the recommended cable sizes for battery, AC, and PV connections to ensure efficient and safe operation. Incorrect wiring can lead to damage or injury.
  • Regular maintenance: Clean the anti-dust kit monthly to maintain optimal performance and prolong the inverter's lifespan.
  • Monitor the display: Familiarize yourself with the LCD display icons, fault codes, and warning indicators to quickly diagnose and address any issues.
  • Battery compatibility: When using lithium batteries, ensure the correct battery type (LIB-485) and protocol are selected in the LCD settings for proper communication and charging.

9. Warranty & Support

For technical support, service, or warranty inquiries, please contact PowMr directly using the information below:

  • Tel/Fax: +86755-28219903
  • Email: support@powmr.com
  • Web: www.powmr.com
  • Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China

Only qualified service personnel should attempt repairs. If issues persist after following troubleshooting steps, return the inverter/charger to your local dealer or service center for maintenance.

Ask a question about this manual