1. Introduction
This manual describes the assembly, installation, operation, and troubleshooting of the PowMr Hybrid Solar Inverter. Please read this manual carefully before installation and operation. Keep this manual for future reference.
This multi-function inverter/charger combines the functions of an inverter, solar charger, and battery charger to offer uninterruptible power support in a portable size. Its comprehensive LCD display provides user-configurable and easy-accessible button operation for settings such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.
1.1 Features
- Pure sine wave inverter
- Configurable input voltage range for home appliances and personal computers via LCD setting
- Configurable battery charging current based on applications via LCD setting
- Configurable AC/Solar Charger priority via LCD setting
- Compatible with mains voltage or generator power
- Auto restart while AC is recovering
- Overload/Over temperature/short circuit protection
- Smart battery charger design for optimized battery performance
- Cold start function
- RS485 is used to communicate with BMS and adjust the charging current of inverter according to battery demand
- Can work with or without batteries
- Intelligent fan speed adjustment, which adjusts the fan speed according to temperature, load, and charging current
- Built-in MPPT, operating voltage range 55V~450V, open circuit voltage 500Voc
- RGB lamp, which displays different colors according to inverter status
- WIFI remote monitoring (optional)
- Offline upgrade function, firmware can be upgraded through COM port
- Grid-connected
- Built-in anti-dust kit for harsh environment
- In battery-free mode, PV systems deliver a better user experience when powering loads
- Equipped with lithium battery activation function
The PowMr Hybrid Solar Inverter, highlighting features like 220V output, 50Hz/60Hz frequency, 24VDC/48VDC battery voltage, MPPT 120A PV charge current, and 60-450VDC MPPT voltage range. Includes a 1-year warranty.
The inverter is compatible with multiple battery types including AGM, GEL, FLD, LI, SLD, and USER-defined. It supports a maximum battery charging current of 120A. Lithium batteries are activated by solar energy after 3 seconds.
The inverter features a Smart Protection System with multiple protection modes, including charge low/high temperature, discharge low/high temperature, overcurrent, undervoltage, short-circuit, solar panel reverse connection, battery overvoltage, over temperature, and overload protection.
Reduce energy costs by choosing a charging mode based on your needs and utilizing solar energy. Options include 'Solar First' (solar charges battery first, utility charges when solar is unavailable), 'Solar and Utility' (both charge battery simultaneously), and 'Only Solar Charging' (solar is the only charger source).
The PowMr Hybrid Solar Inverter is suitable for various applications, including RVs, home storage systems, camping setups, and general solar power systems.
1.2 Basic System Architecture
The following illustration shows a basic application for this inverter/charger. A complete running system typically includes a generator or utility connection and PV modules. Consult with your system integrator for other possible system architectures depending on your requirements. This inverter can power all kinds of appliances in home or office environments, including motor-type appliances such as tube lights, fans, refrigerators, and air conditioners.
Figure 1 (Hybrid Power System diagram from manual page 5) illustrates the connections between solar power, solar inverter, generator/utility, external battery packs, and home appliances.
1.3 Product Overview
The product features an LCD display, status indicator, charging indicator, fault indicator, function buttons, power on/off switch, AC input, main output, second output, battery input, PV input, anti-dust kit, battery communication/RS-485 port, and WIFI communication/RS-232 port.
Front view of the PowMr Hybrid Solar Inverter, showing the LCD display and control buttons.
Rear view of the PowMr Hybrid Solar Inverter, detailing the various connection ports for AC input, AC output, battery, PV, and communication.
2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION - Only qualified personnel can install this device with a battery. NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow the required specifications to select the appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for details.
- One piece of 150A fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to the local dealer or service center for maintenance.
3. Installation
3.1 Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items:
- The unit x 1
- User manual x 1
3.2 Preparation
Before connecting all lines, remove the screws under the machine and remove the bottom cover plate.
3.3 Mounting the Unit
Consider the following points before selecting where to install:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level to allow the LCD display to be read at all times.
- For proper air circulation to dissipate heat, allow a clearance of approximately 20 cm to the side and approximately 50 cm above and below the unit.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Make sure that other objects and surfaces are left with enough space from the machine to ensure adequate heat dissipation and that there is enough room to remove the wires.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing two screws. It's recommended to use M6 screws.
3.4 Battery Connection
CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between the battery and inverter. It may not be requested to have a disconnect device in some applications; however, it's still requested to have over-current protection installed. Please refer to the typical amperage in the table below for the required fuse or breaker size.
WARNING! All wiring must be performed by qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce the risk of injury, please use the proper recommended cable as below.
Recommended battery cable size:
| Model | Wire Size | Cable (mm²) | Torque value (max) |
|---|---|---|---|
| 4.2KW/6.2KW | 1 x 2AWG | 25 | 2 Nm |
Follow these steps to implement battery connection:
- Remove insulation sleeve 18 mm for positive and negative conductors.
- Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Connect all battery packs as shown in the manual's diagram (Figure 1, page 7), typically in series for higher voltage systems.
- Insert the battery wires flatly into the battery connectors of the inverter and make sure the bolts are tightened with a torque of 2 Nm in a clockwise direction. Ensure polarity at both the battery and the inverter/charger is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.
WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.
CAUTION!! Before making the final DC connection or closing the DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
3.5 AC Input/Output Connection
CAUTION!! Before connecting to the AC input power source, please install a separate AC breaker between the inverter and the AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from overcurrent of AC input. The recommended specification for the AC breaker is 32A for 4.2KW and 50A for 6.2KW.
CAUTION!! There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce the risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires:
| Model | Gauge | Cable (mm²) | Torque Value |
|---|---|---|---|
| 4.2KW | 12 AWG | 4 | 1.2 Nm |
| 6.2KW | 10 AWG | 6 | 1.2 Nm |
Follow these steps to implement AC input/output connection:
- Before making AC input/output connection, be sure to open the DC protector or disconnector first.
- Remove insulation sleeve 10mm for six conductors. Shorten phase L and neutral conductor N by 3 mm.
- Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. (L→LINE (brown or black), N→Neutral (blue)).
WARNING: Be sure that the AC power source is disconnected before attempting to hardwire it to the unit.
- Then, insert AC output wires according to polarities indicated on the terminal block and tighten the terminal screws. (L→LINE (brown or black), N→Neutral (blue)).
- Make sure the wires are securely connected.
CAUTION: Appliances such as air conditioners require at least 2-3 minutes to restart due to the need to balance refrigerant gas inside circuits. If a power shortage occurs and recovers quickly, it can damage connected appliances. Check if your air conditioner manufacturer specifies a time-delay function before installation. Otherwise, this inverter/charger will trigger an overload fault and cut off output to protect your appliance, but internal damage to the air conditioner may still occur.
3.6 PV Connection
CAUTION: Before connecting to PV modules, please install a separate DC circuit breaker between the inverter and PV modules.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce the risk of injury, please use the proper recommended cable size as below.
Recommended cable requirement for PV module connection:
| Model | Wire Size | Cable (mm²) | Torque value (max) |
|---|---|---|---|
| 4.2KW/6.2KW | 1 x 12AWG | 4 | 1.2 Nm |
PV Module Selection:
When selecting proper PV modules, please be sure to consider these parameters:
- Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.
| INVERTER MODEL | 4.2KW | 6.2KW |
|---|---|---|
| Max. PV Array Open Circuit Voltage | 500Vdc | |
| PV Array MPPT Voltage Range | 60Vdc~450Vdc | |
| IMax.PV | 27A | |
Example PV module configurations (using 250Wp PV module as reference):
| Solar Panel Spec. (reference) | SOLAR INPUT (Min in serial: 6 pcs, max. in serial: 13 pcs) | Q'ty of panels | Total input power |
|---|---|---|---|
| 250Wp Vmp: 30.1Vdc Imp: 8.3A Voc: 37.7Vdc Isc: 8.4A Cells: 60 | 6 pcs in serial | 6 pcs | 1500W |
| 8 pcs in serial | 8 pcs | 2000W | |
| 12 pcs in serial | 12 pcs | 3000W | |
| 13 pcs in serial | 13 pcs | 3250W | |
| 8 pieces in serial and 2 sets in parallel | 16 pcs | 4000W | |
| 10 pieces in serial and 2 sets in parallel | 20 pcs | 5000W | |
| 12 pieces in serial and 2 sets in parallel | 24 pcs | 6500W | |
| 10 pieces in serial and 3 sets in parallel | 30 pcs | 7500W |
PV Module Wire Connection:
Follow these steps to implement PV module connection:
- Remove insulation sleeve 10 mm for positive and negative conductors.
- Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Check correct polarity of wire connection from PV modules and PV input connectors. Then, connect the positive pole (+) of the connection wire to the positive pole (+) of the PV input connector. Connect the negative pole (-) of the connection wire to the negative pole (-) of the PV input connector. Recommended tool: 4mm blade screwdriver.
3.7 Final Assembly
After connecting all wirings, please put the bottom cover back by screwing two screws.
3.8 Communication Connection
1. Wi-Fi cloud communication (option):
Please use the supplied communication cable to connect to the inverter and Wi-Fi module. Download the APP from the APP store and refer to the "Wi-Fi Plug Quick Installation Guideline" to set up the network and register. The inverter status will be shown by the mobile phone APP or webpage of a computer.
2. GPRS cloud communication (option):
Please use the supplied communication cable to connect to the inverter and GPRS module, and then apply external power to the GPRS module. Download the APP from the APP store and refer to the "GPRS RTU Quick Installation Guideline" to set up the network and register. The inverter status will be shown by the mobile phone APP or webpage of a computer.
3. Battery communication:
Communication between the battery and the inverter is realized through the battery communication interface, allowing the inverter and the lithium battery to exchange information (Baud rate: 9600).
4. Lithium battery and inverter connection:
If choosing a lithium battery for the inverter, only lithium batteries that have been matched with the BMS communication protocol are allowed.
- Connect the battery according to the recommended battery cable specifications.
- Insert the ring terminal of the battery cable into the battery connector of the inverter flatly, and ensure that the bolts are tightened with a torque of 2-3 Nm. Make sure that the polarities of the battery and inverter are connected correctly, and that the ring terminal is tightened with the battery terminal.
- Connect one side of the RJ45 cable to the BMS communication port of the inverter.
- Insert the other side of the RJ45 cable into the RS485 communication port on the lithium battery.
NOTE: If you choose a lithium battery, please make sure to connect the battery and inverter with the BMS communication cable, and select the battery type as "LIB-485" mode.
Communication And Setting Of Lithium Battery:
- Connect the RJ45 communication cable between the inverter and battery. Please confirm that the lithium battery BMS port's PIN corresponds with the inverter BMS communication port. The inverter BMS port's PIN definition is as below:
| Pin number | Port definitions |
|---|---|
| 1 | RS485B |
| 2 | RS485A |
| 3 | NG |
| 4 | NG |
| 5 | NG |
| 6 | NG |
| 7 | RS485A |
| 8 | RS485B |
To communicate with the lithium battery BMS, press the "ENTER" button for a long time, and set the battery type as "LIB-485" in program 05. Then select the matching battery protocol in Program 43.
CAUTION: When the battery type is set to "LIB-485", the setting items 12, 13 and 29 are displayed in percentage.
In "LIB-485" mode, press and hold the "ESC" button to view the information of the lithium battery. The inverter display screen will show the total battery voltage and remaining battery capacity. Press the "DOWN" button to display other data in turn, such as battery charging/discharge current, rated battery capacity, battery charge cycles, minimum/maximum MOS temperature, single battery cell voltage, and battery cell temperatures.
4. Operation
4.1 Power ON/OFF
Once the unit has been properly installed and the batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.
4.2 Operation and Display Panel
The operation and display panel is on the front of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.
LED Indicator:
| Indicator | LED State | Messages |
|---|---|---|
| INV/AC (Green) | Solid On | Output is powered by utility in Line mode. |
| Flashing | Output is powered by battery or PV in battery mode. | |
| CHG (Green) | Solid On | Battery is fully charged. |
| Flashing | Battery is charging. | |
| FAULT (Red) | Solid On | Fault occurs in the inverter. |
| Flashing | Warning condition occurs in the inverter. |
Function Keys:
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
4.3 LCD Display Icons
The LCD display provides various icons to indicate the inverter's status and operation. These include:
- Input Source Information: Icons for AC input, PV input, and a combined display for input voltage, frequency, PV voltage, charger current, charger power, and battery voltage.
- Configuration Program and Fault Information: Icons for setting programs, warning codes (flashing), and fault codes (solid).
- Output Information: Icons for output voltage, frequency, load percent, load in VA, load in Watt, and discharging current.
- Battery Information: An icon representing the battery status.
- Load Information: An icon indicating overload.
- Mode Operation Information: Icons for unit connected to mains, unit connected to PV panel, load supplied by utility power, utility charger circuit working, DC/AC inverter circuit working.
- Mute Operation: An icon indicating unit alarm is disabled.
4.4 LCD Setting
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Use the "UP" or "DOWN" buttons to select setting programs, then press "ENTER" to confirm or "ESC" to exit.
Key settings include:
- Program 00: Exit setting mode or One-button restore setting options.
- Program 01: Output source priority: Configure load power source priority (Utility first, Solar first, SBU priority, MKS priority).
- Program 02: Maximum charging current: Configure total charging current for solar and utility chargers.
- Program 03: AC input voltage range: Set acceptable AC input voltage range (Appliances or UPS).
- Program 04: Power saving mode enable/disable: Enable or disable power saving mode.
- Program 05: Battery type: Select battery type (AGM, Flooded, User-Defined, LIB-485).
- Program 06: Auto restart when overload occurs.
- Program 07: Auto restart when over temperature occurs.
- Program 09: Output frequency: Set output frequency (50Hz/60Hz).
- Program 10: Output voltage: Set output voltage (220V, 230V, 240V).
- Program 11: Maximum utility charging current: Set maximum charging current from utility.
- Program 12: Setting voltage point back to utility source: When selecting "SBU priority" or "Solar first" in program 01.
- Program 13: Setting voltage point back to battery mode: When selecting "SBU priority" or "Solar first" in program 01.
- Program 16: Charger source priority: Configure charger source priority (Solar first, Solar and Utility, Only Solar).
- Program 18: Alarm control: Enable or disable alarms.
- Program 19: Auto return to default display screen.
- Program 20: Backlight control: Turn backlight on or off.
- Program 22: Beeps while primary source is interrupted.
- Program 23: Overload bypass: Enable or disable bypass when overload occurs in battery mode.
- Program 25: Record Fault code: Enable or disable fault code recording.
- Program 26: Bulk charging voltage (C.V voltage).
- Program 27: Floating charging voltage.
- Program 29: Low DC cut-off voltage.
- Program 30: Battery equalization: Enable or disable battery equalization.
- Program 31: Battery equalization voltage.
- Program 33: Battery equalized time.
- Program 34: Battery equalized timeout.
- Program 35: Equalization interval.
- Program 36: Equalization activated immediately.
- Program 37: GRID-tie operation: Set operation mode (Off grid, Hybrid).
- Program 38: GRID-tie current.
- Program 39: Led pattern light.
- Program 41: Dual output.
- Program 42: Enter the dual output functional voltage point.
- Program 43: Lithium battery protocol: Select protocol (PYLON, PACE).
- Program 44: Delayed grid access.
- Program 45: Maximum Second Load.
4.5 Operating Mode Description
The inverter operates in several modes, each with specific characteristics:
- Standby Mode: The inverter is not turned on, but can still charge batteries without AC output. No output is supplied by the unit, but it can still charge batteries.
- Line Mode: The unit provides output power from the mains and also charges the battery.
- Grid-Tie Operation: When working in Grid-Tie mode, the unit will flash 3S/times.
- Battery Mode: The unit provides output power from the battery and power.
4.6 RGB Light (option)
- Green light: Inverter state.
- Blue light: Utility state.
- Red light: Failure state.
4.7 Battery Equalization Description
Equalization function is added to the charge controller to reverse the buildup of negative chemical effects like stratification and to remove sulfate crystals. This process helps maintain overall battery capacity. It is recommended to equalize the battery periodically.
How to Apply Equalization Function:
You must enable the battery equalization function in monitoring LCD setting program 30 first. Then, you may apply this function by either of the following methods:
- Setting the equalization interval in program 35.
- Activating equalization immediately in program 36.
When to Equalize:
In the float stage, when the setting equalization interval (battery equalization cycle) is reached, or equalization is active immediately, the controller will start to enter the Equalize stage.
The manual includes a diagram (page 32) illustrating the Equalize Voltage and Float Voltage stages, including BULK, ABSORPTION, FLOAT, and EQUALIZE phases.
Equalize charging time and timeout:
In the Equalize stage, the controller supplies power to charge the battery until the battery voltage reaches the battery equalization voltage. Constant-voltage regulation is then applied to maintain the battery voltage at this level. The battery remains in the Equalize stage until the setting battery equalized time is reached.
If, in the Equalize stage, the battery equalized time expires and the battery voltage does not rise to the battery equalization voltage point, the charge controller will extend the battery equalized time until the battery voltage achieves the battery equalization voltage. If the battery voltage is still lower than the battery equalization voltage when the battery equalized timeout setting is over, the charge controller will stop equalization and return to the float stage.
4.8 Mains and Lithium Battery Activation Function
- After 90 seconds of mains power connection to the inverter, the machine connects to the mains and starts to work.
- If the inverter is in lithium battery mode (item 05 is Llb or Llb-485), and the mains are connected but the battery is not, the mains activation function is automatically enabled.
5. Maintenance
5.1 Clearance and Maintenance for Anti-Dust Kit
Every inverter is already installed with an anti-dust kit from the factory. The inverter will automatically detect this kit and activate an internal thermal sensor to adjust the internal temperature. This kit also keeps dust out of your inverter and increases product reliability in harsh environments.
- Step 1: Loosen the screw in the counterclockwise direction on the top of the inverter.
- Step 2: The dustproof case can then be removed, and the air filter foam taken out.
- Step 3: Clean the air filter foam and dustproof case. After cleaning, re-assemble the dust-kit back to the inverter.
NOTICE: The anti-dust kit should be cleaned from dust every one month.
6. Troubleshooting
6.1 Fault Reference Code
The inverter provides fault codes to help diagnose issues:
| Fault Code | Fault Event | Icon on |
|---|---|---|
| 21 | Battery Cell Over Voltage | 21 ERROR |
| 22 | Battery Cell Under Voltage | 22 ERROR |
| 23 | Battery Pack Over Voltage | 23 ERROR |
| 24 | Battery Pack Under Voltage | 24 ERROR |
| 25 | Charging Over Current | 25 ERROR |
| 26 | Discharging Over Current | 26 ERROR |
| 27 | Charging Cell Over Temperature | 27 ERROR |
| 28 | Discharging Cell Over Temperature | 28 ERROR |
| 29 | Charging Cell Under Temperature | 29 ERROR |
| 30 | Discharging Cell Under Temperature | 30 ERROR |
| 31 | Ambient Over Temperature | 31 ERROR |
| 32 | Ambient Under Temperature | 32 ERROR |
| 33 | MOS Over Temperature | 33 ERROR |
| 35 | Battery Short Circuit | 35 ERROR |
| 36 | Charge Overvoltage | 36 ERROR |
| 37 | System Failure | 37 ERROR |
| 39 | Charging MOS Fault | 39 ERROR |
| 40 | Discharge MOS Fault | 40 ERROR |
| 41 | Temperature Sensor Fault | 41 ERROR |
| 42 | Battery Cell Fault | 42 ERROR |
| 43 | Sampling Communication Failure | 43 ERROR |
| 61 | Communication Failure | 61 ERROR |
6.2 Warning Indicator
The inverter provides warning codes and audible alarms for various conditions:
| Warning Code | Warning Event | Audible Alarm | Icon flashing |
|---|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep three times every second | 01 |
| 03 | Battery is over-charged | Beep once every second | 03 |
| 04 | Low battery | Beep once every second | 04 |
| 07 | Overload | Beep once every 0.5 second | 07 |
| 10 | Output power derating | Beep twice every 3 seconds | 10 |
| 15 | PV energy is low. | Beep twice every 3 seconds | 15 |
| 16 | AC voltage is over limitation | Beep twice every 3 seconds | 16 |
| E9 | Battery equalization | None | E9 |
| 6P | Battery is not connected | None | 6P |
6.3 Troubleshooting Table
This table provides common problems, their LCD/LED/Buzzer indications, possible causes, and recommended actions:
| Problem | LCD/LED/Buzzer | Explanation / Possible cause | What to do |
|---|---|---|---|
| Unit shuts down automatically during startup process. | LCD/LEDs and buzzer will be active for 3 seconds and then complete off. | The battery voltage is too low (<1.91V/Cell) | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | No indication. | 1. The battery voltage is far too low. (<1.4V/Cell) 2. Internal fuse tripped. | 1. Contact repair center for replacing the fuse. 2. Re-charge battery. 3. Replace battery. |
| Mains exist but the unit works in battery mode. | Input voltage is displayed as 0 on the LCD and green LED is flashing. | Input protector is tripped | Check if AC breaker is tripped and AC wiring is connected well. |
| Green LED is flashing. | Insufficient quality of AC power. (Shore or Generator) | 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS/Appliance) | |
| When the unit is turned on, internal relay is switched on and off repeatedly. | Green LED is flashing. | Set "Solar First" as the priority of output source. | Change output source priority to Utility first. |
| LCD display and LEDs are flashing | Battery is disconnected. | Check if battery wires are connected well. | |
| Buzzer beeps continuously and red LED is on. | Fault code 07 | Overload error. The inverter is overload 110% and time is up. | Reduce the connected load by switching off some equipment. |
| Fault code 05 | Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
| Fault code 02 | Temperature of internal converter component is over 120°C. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
| Fault code 03 | Battery is over-charged. | Return to repair center. | |
| The battery voltage is too high. | Check if spec and quantity of batteries are meet requirements. | ||
| Fault code 01 | Fan fault | Replace the fan. | |
| Fault code 06/58 | Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) | 1. Reduce the connected load. 2. Return to repair center | |
| Fault code 08/09/53/57 | Internal components failed. | Return to repair center. | |
| Fault code 51 | Over current or surge. | Restart the unit, if the error happens again, please return to repair center. | |
| Fault code 52 | Bus voltage is too low. | ||
| Fault code 55 | Output voltage is unbalanced. |
7. Specifications
7.1 Line Mode Specifications
| INVERTER MODEL | 4.2KW | 6.2KW |
|---|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) | |
| Nominal Input Voltage | 230Vac | |
| Low Loss Voltage | 170Vac±7V (UPS); 90Vac±7V (Appliances) | |
| Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) | |
| High Loss Voltage | 280Vac±7V | |
| High Loss Return Voltage | 270Vac±7V | |
| Max AC Input Voltage | 300Vac | |
| Nominal Input Frequency | 50Hz / 60Hz (Auto detection) | |
| Low Loss Frequency | 40±1Hz | |
| Low Loss Return Frequency | 42±1Hz | |
| High Loss Frequency | 65±1Hz | |
| High Loss Return Frequency | 63±1Hz | |
| Output Short Circuit Protection | Circuit Breaker | |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) | |
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) | |
Output power derating:
When AC input voltage drops to 170V, the output power will be derated. (Refer to the Output Power Derating graph on manual page 35).
7.2 Inverter Mode Specifications
| INVERTER MODEL | 4.2KW | 6.2KW |
|---|---|---|
| Rated Output Power | 4.2KW | 6.2KW |
| Output Voltage Waveform | Pure Sine Wave | |
| Output Voltage Regulation | 230Vac±5% | |
| Output Frequency | 50Hz | |
| Peak Efficiency | 93% | |
| Overload Protection | 3s@≥150% load; 30s@101%~150% load | |
| Surge Capacity | 2* rated power for 3 seconds | |
| Nominal DC Input Voltage | 24Vdc | 48Vdc |
| Cold Start Voltage | 23.0Vdc | 46.0Vdc |
| Low DC Warning Voltage | 22.0Vdc (@load < 50%) | 44.0Vdc (@load < 50%) |
| 21.0Vdc (@load ≥ 50%) | 42.0Vdc (@load ≥ 50%) | |
| Low DC Warning Return Voltage | 22.5Vdc (@load < 50%) | 45.0Vdc (@load < 50%) |
| 22.0Vdc (@load ≥ 50%) | 44.0Vdc (@load ≥ 50%) | |
| Low DC Cut-off Voltage | 20.5Vdc (@load < 50%) | 41.0Vdc (@load < 50%) |
| 20.0Vdc (@load ≥ 50%) | 40.0Vdc (@load ≥ 50%) | |
| High DC Recovery Voltage | 32Vdc | 62Vdc |
| High DC Cut-off Voltage | 33Vdc | 63Vdc |
| No Load Power Consumption | 25W | 50W |
| Saving Mode Power Consumption | < 10W | < 15W |
7.3 Two Load Output Power
| INVERTER MODEL | 4.2KW | 6.2KW |
|---|---|---|
| Full Load | 4200W | 6200W |
| Maximum Main Load | 4200W | 6200W |
| Second Load Range | 840W~2940W | 1240W~4340W |
| Main Load Cut Off Voltage | 22VDC | 44VDC |
| Main Load Return Voltage | 26VDC | 52VDC |
7.4 Charge Mode Specifications
| Utility Charging Mode | 4.2KW | 6.2KW |
|---|---|---|
| Charging Algorithm | 3-Step | |
| AC Charging Current (Max) | 100Amp (@VI/P=230Vac) | |
| Bulk Charging: Flooded Battery | 29.2 | 58.4 |
| AGM / Gel Battery Voltage | 28.2 | 56.4 |
| Floating Charging Voltage | 27Vdc | 54Vdc |
The manual includes a diagram (page 37) illustrating the Charging Curve, showing Battery Voltage per cell and Charging Current over time, with Bulk (Constant Current), Absorption (Constant Voltage), and Maintenance (Float) phases.
| MPPT Solar Charging Mode | 4.2KW | 6.2KW |
|---|---|---|
| Max. PV Array Power | 6200W | 8000W |
| Nominal PV Voltage | 240Vdc | 360Vdc |
| PV Array MPPT Voltage Range | 60Vdc~450Vdc | |
| Max. PV Array Open Circuit Voltage | 500Vdc | |
| Max Charging Current (AC charger plus solar charger) | 120Amp | |
7.5 General Specifications
| INVERTER MODEL | 4.2KW | 6.2KW |
|---|---|---|
| Safety Certification | CE | |
| Operating Temperature Range | -10°C to 50°C | |
| Storage temperature | -15°C~60°C | |
| Humidity | 5% to 95% Relative Humidity (Non-condensing) | |
| Dimension (D*W*H), mm | 423×344×112 | |
| Net Weight, kg | 7.2 | 8.2 |
7.6 Approximate Back-up Time Table
This table provides approximate backup times for different loads and battery configurations:
4.2KW Model:
| Load (W) | Backup Time @ 24Vdc 100Ah (min) | Backup Time @ 24Vdc 200Ah (min) |
|---|---|---|
| 300 | 449 | 1100 |
| 600 | 222 | 525 |
| 900 | 124 | 303 |
| 1200 | 95 | 227 |
| 1500 | 68 | 164 |
| 1800 | 56 | 126 |
| 2100 | 48 | 108 |
| 2400 | 35 | 94 |
| 2700 | 31 | 74 |
| 3200 | 28 | 67 |
| 3600 | 25 | 60 |
| 4200 | 22 | 53 |
6.2KW Model:
| Load (W) | Backup Time @ 48Vdc 100Ah (min) | Backup Time @ 48Vdc 200Ah (min) |
|---|---|---|
| 500 | 613 | 1288 |
| 1000 | 268 | 613 |
| 1500 | 158 | 402 |
| 2000 | 111 | 271 |
| 2500 | 90 | 215 |
| 3200 | 76 | 182 |
| 3500 | 65 | 141 |
| 4000 | 50 | 112 |
| 4500 | 44 | 100 |
| 5000 | 40 | 90 |
| 6200 | 36 | 80 |
Note:
- Backup time depends on the quality of the battery, age of battery, and type of battery. Specifications of batteries may vary depending on different manufacturers.
- The final interpretation right of this product belongs to the company.
8. User Tips
- Always ensure proper ventilation around the inverter to prevent overheating, especially during high load operation.
- Regularly check battery connections for tightness and corrosion to maintain optimal performance and safety.
- For optimal battery life, consider enabling the battery equalization function if your battery type supports it and requires it.
- When configuring settings, double-check the battery type and voltage ranges to match your specific battery bank.
- If using the Wi-Fi or GPRS communication modules, ensure they are correctly connected and configured according to their respective quick installation guidelines for remote monitoring.
9. Warranty and Support
The PowMr Hybrid Solar Inverter comes with a 1-year warranty.
For technical support, service, or inquiries, please contact:
SHENZHEN HEHEJIN INDUSTRIAL CO.,LTDTel/Fax: +86755-28219903
Email: support@powmr.com
Web: www.powmr.com
Add: Henggang Street, Longgang District, Shenzhen, Guangdong, China
If errors persist after following the troubleshooting guide, please contact the support team or return the inverter/charger to your local dealer or service center for maintenance.