1. Introduction
This is a multi-function inverter/charger, combining functions of inverter, solar charger and battery charger to offer uninterruptible power support with portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.
1.1 Features
- Pure sine wave inverter
- Configurable input voltage range for home appliances and personal computers via LCD setting
- Configurable battery charging current based on applications via LCD setting
- Configurable AC/Solar Charger priority via LCD setting
- Compatible to mains voltage or generator power
- Auto restart while AC is recovering
- Overload/ Over temperature/ short circuit protection
- Smart battery charger design for optimized battery performance
- Cold start function
1.2 Basic System Architecture
The following illustration shows basic application for this inverter/charger. It also includes following devices to have a complete running system: Generator or Utility, and PV modules. Consult with your system integrator for other possible system architectures depending on your requirements. This inverter can power all kinds of appliances in home or office environment, including motor-type appliances such as tube light, fan, refrigerator and air conditioner.

Description: This diagram illustrates how the inverter can reduce energy costs by choosing a charging mode based on needs and utilizing solar energy. The modes include 'Solar First' (solar charges battery, utility only when solar unavailable), 'Solar and Utility' (both charge battery simultaneously), and 'Only Solar Charging' (solar is the only charger source, regardless of utility availability).

Description: This infographic highlights key features: 50Hz/60Hz frequency range, 1KW 12V / 1.5KW 24V battery voltage compatibility, MPPT 80A maximum charge current, and a 30-150VDC MPPT voltage range. It also mentions a 1-year warranty.
2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries and all appropriate sections of this manual.
- CAUTION – To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION - Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.
- GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
- NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
3. Installation
3.1 Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items:
- The unit x 1
- User manual x 1
- U-terminal x 2

Description: The package includes the inverter unit, a user manual, and a set of U-shaped terminals for connections.
3.2 Preparation
Before connecting all wirings, please take off the bottom cover by removing two screws.
3.3 Mounting the Unit
Consider the following points before selecting where to install:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level in order to allow the LCD display to be read at all times.
- For proper air circulation to dissipate heat, allow a clearance of approximately 20 cm to the side and approximately 50 cm above and below the unit.
- The ambient temperature should be between $0^{\circ}C$ and $55^{\circ}C$ to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Be sure to keep other objects and surfaces as shown in the diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing two screws. It's recommended to use M4 or M5 screws.

Description: This image shows the side of the inverter, featuring the power switch and the AC output socket. Proper ventilation around these areas is crucial for operation.
3.4 Battery Connection
CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to typical amperage in below table as required fuse or breaker size.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable as below.
Recommended battery cable size:
| Model | Wire Size | Cable (mm²) | Torque value (max) |
|---|---|---|---|
| 1.0KW 12V | 1 x 6AWG | 14 | 5 Nm |
| 1.5KW 24V | 1 x 6AWG | 14 | 5 Nm |
Please follow below steps to implement battery connection:
- Remove insulation sleeve 18 mm for positive and negative conductors.
- Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Connect all battery packs as shown in the diagram on page 7 of the PDF manual. For 1.0KW/12V, connect two 12V batteries in parallel. For 1.5KW/24V, connect two 12V batteries in series.
- Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charge is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.
WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.
CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
3.5 AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 20A for 1.0KW and 20A for 1.5KW.
CAUTION!! There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires:
| Model | Gauge | Torque Value |
|---|---|---|
| 1.0KW 12V | 14 AWG | 2 Nm |
| 1.5KW 24V | 12 AWG | 2 Nm |
Please follow below steps to implement AC input/output connection:
- Before making AC input/output connection, be sure to open DC protector or disconnector first.
- Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
- Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure to connect PE protective conductor (yellow-green) first. L→ LINE (brown or black), N→ Neutral (blue).
WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
- Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws. L→ LINE (brown or black), N→ Neutral (blue).
- Make sure the wires are securely connected.
CAUTION: Appliances such as air conditioner are required at least 2-3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check manufacturer of air conditioner if it's equipped with time-delay function before installation. Otherwise, this inverter/charger will trig overload fault and cut off output to protect your appliance but sometimes it still causes internal damage to the air conditioner.
3.6 PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for PV wires:
| Model | Wire Size | Torque value (max) |
|---|---|---|
| 1.0KW 12V / 1.5KW 24V | 1x12AWG | 2 Nm |
PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:
- Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
| INVERTER MODEL | 1.0KW | 1.5KW |
|---|---|---|
| Max. PV Array Open Circuit Voltage | 150Vdc | |
| PV Array MPPT Voltage Range | 20~150Vdc | 30~150Vdc |
Take 250Wp PV module as an example. After considering above two parameters, the recommended module configurations are listed as below table.
| Solar Panel Spec. (reference) | SOLAR INPUT (Min in serial: 4 pcs, max. in serial: 12 pcs) | Q'ty of panels | Total input power |
|---|---|---|---|
| - 250Wp Vmp: 30.1Vdc Imp: 8.3A Voc: 37.7Vdc Isc: 8.4A Cells: 60 | 2 pcs in serial | 2 pcs | 500W |
| 3 pcs in serial | 3 pcs | 750W | |
| 4 pcs in serial | 4 pcs | 1000W |
PV Module Wire Connection:
- Remove insulation sleeve 10 mm for positive and negative conductors.
- Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Check correct polarity of wire connection from PV modules and PV input connectors. Then, connect positive pole (+) of connection wire to positive pole (+) of PV input connector. Connect negative pole (-) of connection wire to negative pole (-) of PV input connector. Recommended tool: 4mm blade screwdriver.
3.7 Final Assembly
After connecting all wirings, please put the bottom cover back by screwing four screws.
4. Operation
4.1 Power ON/OFF
Once the unit has been properly installed and the batteries are connected well, simply press the On/Off switch (located on the button of the case) to turn on the unit.
4.2 Operation and Display Panel
The operation and display panel, shown below, is on the front panel of the inverter. It includes three indicators, four function keys and an LCD display, indicating the operating status and input/output power information.

Description: This image provides a detailed front view of the inverter, highlighting the LCD display, function buttons (ESC, UP, DOWN, ENTER), and various input/output terminals including AC IN, AC OUT, Battery, and PV IN. It also shows the input breaker and warning labels.
LED Indicator:
| Indicator | LED Color | Status | Messages |
|---|---|---|---|
| INV/AC | Green | Solid On Flashing | Output is powered by utility in Line mode. Output is powered by battery or PV in battery mode. |
| CHG | Green | Solid On Flashing | Battery is fully charged. Battery is charging. |
| FAULT | Red | Solid On Flashing | Fault occurs in the inverter. Warning condition occurs in the inverter. |
Function Keys:
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
4.3 LCD Setting
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Press "UP" or "DOWN" button to select setting programs. And then, press "ENTER" button to confirm the selection or ESC button to exit. Refer to the PDF manual (pages 11-16) for a complete list of programmable settings including:
- Output source priority (Utility first, Solar first, SBU priority, MKS priority)
- Maximum charging current (10A to 80A)
- AC input voltage range (Appliances, UPS)
- Battery type (AGM, Flooded, User-Defined)
- Auto restart settings (when overload or over temperature occurs)
- Output frequency (50Hz, 60Hz)
- Output voltage (220V, 230V, 240V)
- Maximum utility charging current
- Setting voltage point back to utility source
- Setting voltage point back to battery mode
- Maximum battery discharge current
- Record Fault code
- Bulk charging voltage (C.V voltage)
- Floating charging voltage
- Low DC cut-off voltage
- Battery equalization settings (voltage, time, timeout, interval, immediate activation)
5. Clearance and Maintenance for Anti-Dust Kit (Optional)
5.1 Overview
Every inverter is already installed with an anti-dust kit from the factory. The inverter will automatically detect this kit and activate an internal thermal sensor to adjust the internal temperature. This kit also keeps dust from your inverter and increases product reliability in harsh environments.
5.2 Clearance and Maintenance
- Step 1: Remove the screws holding the dustproof case.
- Step 2: Then, the dustproof case can be removed, and the air filter foam can be taken out.
- Step 3: Clean the air filter foam and dustproof case. After cleaning, re-assemble the dust-kit back to the inverter.
NOTICE: The anti-dust kit should be cleaned from dust every one month.
6. Troubleshooting
6.1 Fault Reference Code
| Fault Code | Fault Event | Icon on |
|---|---|---|
| 01 | Fan is locked when inverter is off. | 01 |
| 02 | Over temperature | 02 |
| 03 | Battery voltage is too high | 03 |
| 04 | Battery voltage is too low | 04 |
| 05 | Output short circuited or over temperature is detected by internal converter components. | 05 |
| 06 | Output voltage is too high. | 06 |
| 07 | Overload time out | 07 |
| 08 | Bus voltage is too high | 08 |
| 09 | Bus soft start failed | 09 |
| 51 | Over current or surge | 51 |
| 52 | Bus voltage is too low | 52 |
| 53 | Inverter soft start failed | 53 |
| 55 | Over DC voltage in AC output | 55 |
| 57 | Current sensor failed | 57 |
| 58 | Output voltage is too low | 58 |
| 59 | PV voltage is over limitation | 59 |
6.2 Warning Indicator
| Warning Code | Warning Event | Audible Alarm | Icon flashing |
|---|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep three times every second | 01 |
| 03 | Battery is over-charged | Beep once every second | 03 |
| 04 | Low battery | Beep once every second | 04 |
| 07 | Overload | Beep once every 0.5 second | 07 |
| 10 | Output power derating | Beep twice every 3 seconds | 10 |
| 15 | PV energy is low. | Beep twice every 3 seconds | 15 |
| E9 | Battery equalization | None | E9 |
7. Specifications
7.1 Line Mode Specifications
| INVERTER MODEL | 1.0KW-12V | 1.5KW-24V |
|---|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) | |
| Nominal Input Voltage | 230Vac | |
| Low Loss Voltage | 170Vac±10V (UPS); 90Vac±10V (Appliances) | |
| Low Loss Return Voltage | 180Vac±10V(UPS); 100Vac±10V(Appliances) | |
| High Loss Voltage | 280Vac±10V | |
| High Loss Return Voltage | 270Vac±10V | |
| Max AC Input Voltage | 300Vac | |
| Nominal Input Frequency | 50Hz / 60Hz (Auto detection) | |
| Low Loss Frequency | 40±1Hz | |
| Low Loss Return Frequency | 42±1Hz | |
| High Loss Frequency | 65±1Hz | |
| High Loss Return Frequency | 63±1Hz | |
| Output Short Circuit Protection | Circuit Breaker | |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) | |
| Transfer Time | 10ms | |
7.2 Inverter Mode Specifications
| INVERTER MODEL | 1.0KW-12V | 1.5KW-24V |
|---|---|---|
| Rated Output Power | 1000VA/1000W | 1500VA/1500W |
| Output Voltage Waveform | Pure Sine Wave | |
| Output Voltage Regulation | 230Vac±5% | |
| Output Frequency | 50Hz | |
| Peak Efficiency | 94% | |
| Overload Protection | 3s@≥150% load; 5s@100%~150% load | |
| Surge Capacity | 2* rated power for 5 seconds | |
| Nominal DC Input Voltage | 12Vdc | 24Vdc |
| Cold Start Voltage | 11.5Vdc | 23.0Vdc |
| Low DC Warning Voltage @ load < 50% | 11.25Vdc | 22.5Vdc |
| Low DC Warning Voltage @ load ≥ 50% | 11.0Vdc | 22Vdc |
| Low DC Warning Return Voltage @ load < 50% | 11.75Vdc | 23.5Vdc |
| Low DC Warning Return Voltage @ load ≥ 50% | 11.5Vdc | 23Vdc |
| Low DC Cut-off Voltage @ load < 50% | 10.75Vdc | 21.5Vdc |
| Low DC Cut-off Voltage @ load ≥ 50% | 10.5Vdc | 21Vdc |
| High DC Recovery Voltage | 15.5Vdc | 31Vdc |
| High DC Cut-off Voltage | 16.0Vdc | 32Vdc |
| No Load Power Consumption | <28W | <28W |
7.3 Charge Mode Specifications
Utility Charging Mode:
| INVERTER MODEL | 1.0KW-12V | 1.5KW-24V |
|---|---|---|
| Charging Algorithm | 3-Step | |
| AC Charging Current (Max) | 40Amp (@VI/P=230Vac) | |
| Bulk Charging Voltage (Flooded Battery) | 14.6 | 29.2 |
| Bulk Charging Voltage (AGM / Gel Battery) | 14.1 | 28.2 |
| Floating Charging Voltage | 13.5Vdc | 27Vdc |
MPPT Solar Charging Mode:
| INVERTER MODEL | 1.0KW-12V | 1.5KW-24V |
|---|---|---|
| Max. PV Array Power | 600W | 1200W |
| PV Array MPPT Voltage Range | 20~150Vdc | 30~150Vdc |
| Max. PV Array Open Circuit Voltage | 150Vdc | |
| Max solar charging current | 40Amp | |
| Max(AC+Solar) Charging current | 80Amp | |
7.4 General Specifications
| INVERTER MODEL | 1.0KW-12V | 1.5KW-24V |
|---|---|---|
| Safety Certification | CE | |
| Operating Temperature Range | -10°C to 50°C | |
| Storage temperature | -15°C ~ 60°C | |
| Humidity | 5% to 95% Relative Humidity (Non-condensing) | |
| Dimension (D*W*H), mm | 286X240X91 | |
| Net Weight, kg | 3 | 3.5 |
8. User Tips
- Ventilation: Ensure adequate ventilation around the inverter, especially when operating under heavy loads or during charging. Some users have noted that internal components can get hot at idle or during high charging currents, suggesting that improved airflow or fan upgrades might be beneficial for sustained performance.
- Overheat Protection: If the unit enters overheat protection during high charging (e.g., 40A), verify that the installation location provides sufficient cooling and consider enhancing the cooling system if necessary.
9. Warranty & Support
For technical support, warranty claims, or service, please contact:
SHENZHEN HEHEJIN INDUSTRIAL CO.,LTDTel/Fax: +86 755-28219903
Email: support@powmr.com
Web: www.powmr.com
Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China
10. Additional Resources
A detailed PDF version of this user manual is available for download. This document provides comprehensive diagrams and in-depth instructions for advanced configurations and troubleshooting.
You can access the PDF manual here: PowMr Hybrid Inverter User Manual (PDF)
Product Video Overview
Watch an official video demonstrating the product's unboxing and key features:
Description: This video provides a visual guide to the product's contents and highlights its main functionalities and design aspects.

Description: This diagram details the inverter's multiple protection modes, including charge low/high temperature, discharge low/high temperature, discharge overcurrent, charging overcurrent, charging undervoltage, short-circuit, solar panel reverse connection, battery overvoltage, over temperature, and overload protection.