1. Important Safety Instructions
Please save these instructions for future use! Read all of the instructions and cautions in this manual before beginning the installation.
- Non-safety voltage exists inside the all-in-one solar charge inverter. To avoid personal injury, users shall not disassemble the inverter themselves. Contact professional maintenance personnel if repair is needed.
- Do not place the inverter within the reach of children.
- Do not install the inverter in harsh environments such as moist, oily, flammable or explosive, or heavily dusty areas.
- The mains input and AC output are high voltage; do not touch the wiring terminals.
- The housing of the inverter is hot when working. Do not touch it.
- Do not open the terminal protective cover when the inverter is working.
- It is recommended to attach proper fuse or circuit breaker to the outside of the inverter.
- Always disconnect the fuse or circuit breaker near the terminals of PV array, mains, and battery before installing and adjusting wiring.
- After installation, check that all wire connections are tight to avoid heat accumulation due to poor connection.
- The all-in-one solar charge inverter is off-grid. Confirm it is the only input device for load; it is forbidden to use it in parallel with other input AC power to avoid damage.
2. Product Overview
The PowMr POW-SunSmart series is a new all-in-one hybrid solar charge inverter, integrating solar energy storage and AC sine wave output. It features DSP control, advanced algorithms, high response speed, and reliability. It offers four charging modes (Only Solar, Mains Priority, Solar Priority, Mains & Solar hybrid) and two output modes (Inverter and Mains) to suit various applications.

This image displays the PowMr 5.2KW 110V Hybrid Solar Inverter. Key specifications highlighted are: Frequency Range 50Hz/60Hz, Floating Battery Voltage 40-58VDC, MPPT 100A PV Charge Current, and MPPT Voltage Range 120-500VDC. The model is POW-SunSmart SP5.2K and it comes with a 1-year warranty.
2.1 Key Features
- Support for inverter and mains power hybrid output, including use without battery.
- Two output modes: mains bypass and inverter output for uninterrupted power supply.
- Four charging modes: Only Solar, Mains Priority, Solar Priority, and Mains & Solar hybrid charging.
- Advanced MPPT technology with 99.9% efficiency.
- LCD screen and 3 LED indicators for dynamic display of system data.
- Time slot control for setting mains and battery priority based on tariffs.
- Power saving mode to reduce no-load loss.
- Intelligent variable speed fan for efficient heat dissipation.
- Lithium battery activation by PV solar or mains, supporting lead-acid and lithium batteries.
- 360° all-around protection functions (short circuit, over/under voltage, overload, reverse protection, etc.).
2.2 Basic System Introduction
A complete system consists of a PV module, mains or generator, battery, household loads, and the all-in-one solar charge inverter.

This diagram illustrates the typical connections for the PowMr Hybrid Solar Inverter. It shows connections for Solar Panels (PV Input), Mains Power/Generator (AC Input), Home Loads (AC Output), and a 48V Battery. Key specifications detailed in the diagram include: Max PV input current 22A, Max PV input power 6000W, Max PV open circuit voltage 500VDC. Max AC charging current 0-40A, Charge voltage range 40-58Vdc, AC input voltage range 0-140Vac. AC output power 5200W, supporting Single phase/split phase/three phase Output (120/208/240V AC output). The battery can be 48V Lead acid or lithium (minimum starting voltage 44V), with a maximum charge current of 100A, and the system supports batteryless mode.
3. Installation and Setup
3.1 Installation Precautions
- Wear safety goggles when installing lead-acid liquid batteries. Rinse with clean water if battery acid contacts skin.
- Do not place metal objects near the battery to prevent short-circuits.
- Ensure good ventilation as acid gas may be generated during battery charging.
- Leave enough space around the inverter for heat dissipation. Do not install the inverter and lead-acid battery in the same cabinet.
- Only charge batteries that meet the inverter's requirements.
- Ensure all connections are tight and wires are secured to avoid heat generation and potential fires.
- System connection wires should have a current density of not more than 5A/mm².
- Avoid direct sunlight and rainwater infiltration for outdoor installation.
- High voltage may remain inside the unit even after power-off. Do not open or touch internal components until capacitors discharge.
- Do not install in moist, oily, flammable, explosive, or dusty environments.
- Do not reverse battery input polarity.
- Mains input and AC output are high voltage; do not touch wiring terminals.
- Do not touch the fan when it is working.
- Confirm the inverter is the sole input device for load equipment; parallel use with other AC power sources is forbidden.
3.2 Wiring Specifications and Circuit Breaker Selection
Wiring and installation must comply with national and local electrical codes. Refer to the tables below for recommended wire diameters and circuit breaker types.
| Models | Recommended PV Wiring Diameter | Maximum PV Input Current | Recommended Circuit Breaker Type |
|---|---|---|---|
| POW-SunSmart SP5.2K | 6mm²/10AWG | 22A | 2P—25A |
Note: The voltage in series shall not exceed the maximum PV input open circuit voltage.
| Models | Recommended AC Input Wiring Diameter | Maximum Bypass Input Current | Recommended Circuit Breaker Type |
|---|---|---|---|
| POW-SunSmart SP5.2K | 10mm²/7AWG | 63A | 2P—63A |
Note: An appropriate circuit breaker is already present at the Mains input wiring terminal.
| Models | Recommended Battery Wiring Diameter | Rated Battery Discharge | Maximum Charge Current | Recommended Circuit Breaker Type |
|---|---|---|---|---|
| POW-SunSmart SP5.2K | 30mm²/2AWG | 125A | 100A | 2P—200A |
| Models | Recommended AC Output Wiring | Rated Inverter AC Output Current | Maximum Bypass Output Current | Recommended Circuit Breaker Type |
|---|---|---|---|---|
| POW-SunSmart SP5.2K | 10mm²/7AWG | 42A | 63A | 2P—63A |
3.3 Mounting Location
Determine the installation position on a wall surface, ensuring sufficient airflow through the heat sink. Leave at least 200mm space to the left and right air outlets for natural convection heat dissipation.
WARNING: Danger of explosion! Never install the inverter and lead-acid battery in the same confined space, or where battery gas may collect.
3.4 Wiring Connections
Before connecting all wirings, remove the bottom cover of the inverter.
3.4.1 AC Input/Output Wiring
- Before wiring, open the external circuit breaker and confirm the wire thickness.
- Connect the AC input wire: ground wire first, then live wire (L), and neutral wire (N).
- Connect the AC output wire: ground wire first, then live wire (L), and neutral wire (N). The ground wire connects to the grounding screw hole on the cabinet via an O-type terminal.
3.4.2 PV Input Wiring
- Before wiring, disconnect the external circuit breaker and confirm wire thickness.
- Connect the PV input wire: PV+ (positive pole) and PV- (negative pole). For parallel connections, different inverters need to connect to different PV arrays or sources.
3.4.3 Battery Wiring
- Before wiring, disconnect the external circuit breaker and confirm wire thickness. Use an O-type terminal (6mm inner diameter) for BAT wire connection.
- Connect the battery wire: BAT+ (positive electrode) and BAT- (negative electrode).
WARNING: Mains input, AC output, and PV array generate high voltage. Ensure circuit breakers/fuses are open before wiring. Install a circuit breaker at the battery terminal. If in a lightning-prone area, install an external lightning arrester at the PV input terminal.
3.5 Initial Startup
- Close the circuit breaker at the battery terminal.
- Turn the rocker switch on the left side of the machine to