PowMr POW-HVM6.2KP

Contents

PowMr Hybrid Solar Inverter User Manual

Model: POW-HVM6.2KP

1. Introduction

This PowMr Hybrid Solar Inverter is a multi-function inverter/charger, combining the functionalities of an inverter, solar charger, and battery charger to provide uninterruptible power support. It features a comprehensive LCD display and user-configurable button operation for settings such as battery charging current, AC/solar charger priority, and acceptable input voltage, adapting to various applications.

1.1 Key Features

  • Pure sine wave inverter.
  • Configurable input voltage range for home appliances and personal computers via LCD setting.
  • Configurable battery charging current based on applications via LCD setting.
  • Configurable AC/Solar Charger priority via LCD setting.
  • Compatible with mains voltage or generator power.
  • Auto restart while AC is recovering.
  • Overload/Over temperature/short circuit protection.
  • Smart battery charger design for optimized battery performance.
  • Cold start function.
  • Supports parallel operation of up to 9 units.

1.2 Basic System Architecture

The inverter can power various appliances in home or industrial environments, including motor-type appliances such as tube lights, fans, refrigerators, and air conditioners. A complete system typically includes the inverter/charger, a generator or utility power source, and PV modules.

System Connection Diagram for PowMr Hybrid Solar Inverter
System Connection Diagram for PowMr Hybrid Solar Inverter, showing connections for Solar Power (PV array), Generator or Utility, 48V Lithium/Lead-Acid Battery, and Home Appliances (refrigerator, light, laptop, fan, air conditioner).

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION: To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION: Only qualified personnel can install this device with a battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow the required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts, which could cause an explosion.
  9. Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Refer to the INSTALLATION section of this manual for details.
  10. One piece of 150A fuse is provided as over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
  12. NEVER cause AC output and DC input to be short-circuited. Do NOT connect to the mains when DC input short circuits.
  13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to a local dealer or service center for maintenance.

WARNING: Shock Hazard

  • Installation must be performed with care due to high battery voltage in series.

CAUTION

  • Before making the final DC connection or closing the DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).

3. Setup (Installation)

3.1 Unpacking and Inspection

Before installation, please inspect the unit to ensure nothing inside the package is damaged. The package should contain:

  • The inverter unit x 1
  • User manual x 1
  • Parallel communication cable x 1
  • Share current wires x 1
  • Expansion screw (M6*80mm) x 2
  • Battery fuse x 1
Unboxing video for the PowMr Hybrid Solar Inverter, showing the contents of the package including the inverter, user manual, communication cables, battery fuse, and expansion screws.

3.2 Preparation

Before connecting any wiring, remove the bottom cover by unscrewing the four screws.

3.3 Mounting the Unit

Consider the following points when selecting an installation location:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install this inverter at eye level to allow the LCD display to be read at all times.
  • For proper air circulation to dissipate heat, allow a clearance of approximately 20 cm to the sides and approximately 50 cm above and below the unit.
  • The ambient temperature should be between 20°C and 35°C to ensure optimal operation.
  • The recommended installation position is to be adhered to the wall vertically.
  • Be sure to keep other objects and surfaces as shown in the diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.
Mounting Clearance Diagram for PowMr Hybrid Solar Inverter
Diagram showing recommended clearances (20cm side, 50cm top/bottom) for proper air circulation around the inverter.

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Install the unit by screwing three screws. Use M6*80mm expansion bolts for suspending and securing the equipment from above. Use M4 or M5 screws in the 3 holes to secure the equipment, as shown in the figure.

NOTICE

  • To avoid potential damage to the terminal base and internal electronic components, it is recommended not to install screws in the mounting hole located at the lower left corner.
Mounting Screw Warning Diagram for PowMr Hybrid Solar Inverter
Diagram highlighting the lower left mounting hole to avoid for screws to prevent damage to the terminal base and internal electronic components.

3.4 Grounding

Please make sure to connect the equipment grounding first, ensuring the device enclosure is reliably grounded before the system is powered on to effectively prevent personal injury caused by accidental leakage.

3.5 Battery Connection

The 6.2KW model supports 48VDC battery systems. Connect all battery banks as shown in the diagram below. It is recommended to install a separate DC over-current protector or disconnect device between the battery and inverter.

Battery Connection Diagram for PowMr Hybrid Solar Inverter
Diagram showing 4x12V batteries connected in series to form a 48V system for the inverter, along with a ring terminal for connection.

Insert the battery wires flatly into the battery connectors of the inverter and make sure the bolts are tightened with a torque of 2 Nm in a clockwise direction. Ensure correct polarity at both the battery and the inverter/charger terminals.

Battery Connection Wiring for PowMr Hybrid Solar Inverter
Close-up image of battery terminal connections (Red(+) and Black(-)) on the inverter.

3.6 AC Input/Output Connection

Before connecting to the AC input power source, install a separate AC breaker between the inverter and the AC input power source. This ensures the inverter can be disconnected during maintenance and is fully protected from overcurrent. The recommended breaker specification is 63A for a 48V system.

There are two terminal blocks with "IN" and "OUT" markings. Do NOT mis-connect input and output connectors.

Follow these steps for AC input/output connection:

  1. Before making AC input/output connections, ensure the DC protector or disconnector is open.
  2. Remove 10mm of insulation sleeve for six conductors. Shorten phase L and N by 3mm.
  3. Insert AC main output wires according to polarities indicated on the terminal block and tighten terminal screws. Be sure to connect the PE protective conductor (Ground) first.
  4. Insert AC second output wires according to polarities indicated on the terminal block and tighten terminal screws. Be sure to connect the PE protective conductor (Ground) first.
  5. Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor (Ground) first.

WARNING

  • Be sure that the AC power source is disconnected before attempting to hardwire it to the unit.
AC Input/Output Connection Wiring Diagram for PowMr Hybrid Solar Inverter
Diagram showing AC output wiring (Ground, Line, Neutral) to the inverter.
AC Input/Output Connection Wiring (continued) for PowMr Hybrid Solar Inverter
Diagrams showing AC second output wiring and AC input wiring to the inverter.

CAUTION

  • Appliances such as air conditioners require at least 2-3 minutes to restart to balance refrigerant gas. If a power shortage occurs and recovers quickly, it can damage connected appliances. Check if your air conditioner has a time-delay function before installation. Otherwise, the inverter/charger may trigger an overload fault to protect the appliance, but internal damage to the air conditioner may still occur.

3.7 PV Connection

Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.

WARNING

  • All wiring must be performed by qualified personnel.
  • It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce the risk of injury, use the proper recommended cable size.

When choosing the right PV module, consider the following:

  1. The open circuit voltage (Voc) of the PV modules must not exceed the maximum PV array open circuit voltage of the inverter.
  2. The maximum supply voltage of the PV modules should be close to the optimal PV access voltage range of the inverter for best performance. If one PV module cannot meet this requirement, connect multiple PV modules in series.

Follow these steps to implement PV modules connection:

  1. Remove 10mm of insulation sleeve for positive and negative conductors.
  2. It is suggested to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Insert PV input wires according to polarities indicated on the terminal block and tighten the terminal screws.
  4. Check the correct polarity of the wire from PV modules and PV input connectors. Then, connect the positive pole (+) of the connection wire to the positive pole (+) of the PV input connector. Connect the negative pole (-) of the connection wire to the negative pole (-) of the PV input connector.
PV Module Wire Connection Diagram for PowMr Hybrid Solar Inverter
Diagram showing PV module wire connections (Red(+) and Black(-)) to the inverter's PV input terminals.

3.8 Final Assembly

After connecting all wirings, please install the bottom cover back by screwing the four screws.

4. Operation

4.1 Power ON/OFF

Once the unit has been properly installed and the batteries are connected, follow the power-on sequence below to start the inverter safely:

  1. Close the battery circuit breaker.
  2. Press the On/Off switch (located on the bottom of the case) to turn on the unit. Wait until the inverter starts up and enters normal operation (inverting).
  3. Close the PV and AC input circuit breakers.
  4. Finally, close the AC output circuit breaker.

To shut down the system, turn off the circuit breakers in the reverse order.

4.1.1 Steps to Start Up

Connect the battery that meets the requirements (battery voltage needs to be beyond 46V) or AC (AC needs to confirm the suitable input range depending on the output mode), then you can start up the inverter.

  • Mains power on: Connect to normal AC power, press the switch, the system will automatically turn on. If you set AC output power priority, after waiting for a period of time, the panel will display AC mode, indicating successful startup, then it will enter AC mode.
  • Battery boot: Connect to battery, press the power-on button to establish a working power source. The system will automatically turn on. After waiting for a period of time, the panel will display battery mode, indicating successful startup, then it will enter battery mode.

4.1.2 Shutdown Steps

When the system is in battery mode or AC mode output, press the switch again, then the system will be turned off.

4.2 Operation and Display Panel

The operation and display panel, located on the front of the inverter, includes three indicators, four function keys, and an LCD display, showing the operating status and input/output power information.

LCD Screen Overview for PowMr Hybrid Solar Inverter
Diagram of the inverter's LCD display and control buttons (ESC, UP, DOWN, ENTER).

4.2.1 Function Keys

Function Key Description
ESC To exit setting mode
UP To go to previous selection
DOWN To go to next selection
ENTER To confirm the selection in setting mode or enter setting mode

4.2.2 LED Indicators

LED Indicator Color Status Messages
AC/INV Green Solid On Output is powered by utility in Line mode.
Flashing Output is powered by battery or PV in battery mode.
CHG Yellow Solid On Battery is fully charged.
Flashing Battery is charging.
FAULT Red Solid On Fault occurs in the inverter.
Flashing Warning condition occurs in the inverter.

4.2.3 LCD Display Icons

The LCD display information switches between input voltage, input frequency, PV voltage, charging current, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, DC discharging current, main board firmware version, and SCC firmware version.

LCD Display Icons for PowMr Hybrid Solar Inverter
Various LCD icons for input source, digital display, warning/fault codes, output information, battery information, and mode operation.

4.3 Operating Mode Description

The inverter operates in various modes depending on the power sources and load conditions. These modes are visually represented on the LCD display.

Operating Mode Description Diagrams for PowMr Hybrid Solar Inverter
Diagrams illustrating different operating modes: Battery charged by utility, Battery charged by PV, Battery charged by utility and PV, Battery charged by PV and feeds grid, No charging, Utility charges battery and provides power to load, Utility and battery power provide power to load, PV energy, battery power and utility provide power to load, PV energy and utility charge battery, PV energy charges battery, PV energy provides power to load and feeds remaining energy to grid, PV energy and battery energy supply power to load, PV energy power to load and charges battery, Battery provides power to load, PV provides power to load.

5. Maintenance

5.1 Battery Equalization Description

The equalization function in the charge controller reverses the buildup of negative chemical effects like stratification and helps remove sulfate crystals that might reduce battery capacity. It is recommended to equalize the battery periodically.

5.1.1 How to Apply Equalization Function

Enable the battery equalization function in LCD setting program 30. Then, you may apply this function by either:

  1. Setting the equalization interval in program 35.
  2. Activating equalization immediately in program 36.

5.1.2 When to Equalize

When the setting equalization interval (battery equalization cycle) is reached, or equalization is active immediately, the controller will start to enter the Equalize stage.

Battery Equalization Graph for PowMr Hybrid Solar Inverter
Graph showing Equalize Voltage, Float Voltage, Bulk, Absorption, Float, and Equalize stages during battery charging.

5.1.3 Equalize Charging Time and Timeout

In the Equalize stage, the controller will supply power to charge the battery as much as possible until the battery voltage reaches the battery equalization voltage. Then, constant-voltage regulation is applied to maintain the battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until the set battery equalized time is reached.

If the battery equalized time expires and the battery voltage doesn't rise to the battery equalization voltage point, the charge controller will extend the battery equalized time until the battery voltage achieves the battery equalization voltage. If the battery voltage is still lower than the battery equalization voltage when the battery equalized timeout setting is over, the charge controller will stop equalization and return to the float stage.

Battery Equalization Graph (continued) for PowMr Hybrid Solar Inverter
Graph showing Equalize Charging Time and Equalize Charging Timeout parameters.

6. Troubleshooting

6.1 Faults Descriptions

When a fault occurs, the inverter enters fault mode, the red LED light is always on, and the LCD displays a fault code.

6.1.1 Fault Reference Code

Fault Code Fault Event What to do
01 Fan is locked when inverter is off. Replace the fan.
02 Over temperature or NTC is not connected well. Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.
03 Battery voltage is too high. Return to repair center. Check if spec and quantity of batteries are meet requirements.
04 Battery voltage is too low. Return to repair center. Check if spec and quantity of batteries are meet requirements.
05 Output short circuited or over temperature is detected by internal converter components. Check if wiring is connected well and remove abnormal load.
06/58 Output abnormal (Inverter voltage below 190Vac or higher than 260Vac). 1. Reduce the connected load. 2. Return to repair center.
07 Overload time out. Reduce the connected load by switching off some equipment.
08/09/53/57 Internal components failed. Return to repair center.
51 Over currents or surge. Restart the unit, if the error happens again, please return to repair center.
52 Bus voltage is too low. Restart the unit, if the error happens again, please return to repair center.
55 Output voltage is unbalanced. Restart the unit, if the error happens again, please return to repair center.
59 PV input voltage is beyond these specification. Reduce the number of PV modules in series.
60 Power feedback protection.
71 Firmware version inconsistent.
72 Current sharing fault.
80 CAN fault.
81 Host loss.
82 Synchronization loss.
83 Battery voltage detected different.
84 AC input voltage and frequency detected different.
85 AC output current unbalance.
86 AC output mode setting is different.

6.2 Warning Descriptions

When an alarm occurs, the red LED flashes, and the LCD displays an alarm code. The inverter does not enter failure mode.

6.2.1 Warning Indicator

Warning Code Warning Event Audible Alarm Icon flashing
01 Fan is locked when inverter is on. Beep three times every second
02 Over temperature None
03 Battery is over-charged Beep once every second
04 Low battery Beep once every second
07 Overload Beep once every 0.5 second
10 Output power derating Beep twice every 3 seconds
15 PV energy is low. Beep twice every 3 seconds
16 High AC input (>280VAC) during BUS soft start None
E9 Battery equalization None
6P Battery is not connected None

6.3 Code Reference

Related information codes will be displayed on the LCD screen. Check the inverter LCD screen for the operation.

Code Description
60 If battery status is not allowed to charge and discharge after successful communication between the inverter and battery, it will show code 60 to stop charging and discharging battery.
61 Communication lost. After battery is connected, if the communication signal is not detected for 1 minute, the buzzer will beep. Communication lost occurs after the inverter and battery are successfully connected, the buzzer beeps immediately.
69 If battery status is not allowed to charge after successful communication between the inverter and battery, it will show code 69 to stop charging battery.
70 If battery status must charge after successful communication between the inverter and battery, it will show code 70 to charge battery.
71 If battery status is not allowed to discharge after successful communication between the inverter and battery, it will show code 71 to stop discharge battery.

7. Specifications

Category Specification Value
AC Input Input Sources L+N+PE
Rated Input Voltage 220/230/240VAC
Voltage Range 90-280VAC±3V (APL Mode); 170-280VAC±3V (UPS Mode)
Frequency 50Hz/60Hz (Auto Adaptive)
Inverter Output Rated Power (Battery Inverter) 6200W
Rated Power (Photovoltaic Inverter) 6500W
Output Voltage 220/230/240VAC±5%
Output Frequency 50Hz/60Hz±0.1%
Waveform Pure Sine Wave
Transfer Time (Adjustable) Computers (UPS Mode) 10ms, Appliance (APL Mode) 20ms
Peak Power 12400VA
Grid-Connected Operation Output Voltage 220/230/240VAC±5%
Feed Into the Grid Voltage Range 170-265VA
Feed Into the Grid Frequency Range 49-51±1Hz/59-61±1Hz
Nominal Output Current 26.9A
Power Factor Range >0.99
Battery Battery Voltage 48Vdc
Constant Charging Voltage (Adjustable) 56.4Vdc
Float Charging Voltage (Adjustable) 54Vdc
PV Input PV Charging Mode MPPT
MAX. PV Input Power 8500W
MPPT Tracking Range 60~500Vdc
Operating Voltage 360~430V
MAX. PV Input Voltage 500Vdc
PV Max Input Current 27A
MAX. PV Charging Current 120A
General Specifications Operating Temperature -10℃~50℃
Humidity 20%~95% (Non-condensing)
Storage Temperature -15℃~60℃
Altitude Not Over 1000m, Derating over 1000m, Max 4000m, Refer to IEC62040
Noise ≤50db
Standards and Certification EN-IEC 60335-1, EN IEC 60335-2-29, IEC 62109-1

8. Parallel Function (Appendix I)

The PowMr Hybrid Solar Inverter supports parallel operation of up to 9 units to create a high-power energy system, allowing for single-phase 230V or three-phase 400V configurations with a maximum output power of 55.8kW.

Flexible Parallel Connection for a High-Power Energy System
Diagram illustrating flexible parallel connection for a high-power energy system, supporting up to 9 units in single-phase 230V or three-phase 400V systems.

8.1 Mounting the Unit (Parallel)

When installing multiple units, follow the same mounting guidelines as for a single unit, ensuring proper air circulation and clearances.

Parallel Operation Diagram for PowMr Hybrid Solar Inverter
Diagram showing up to 9 units operating in single or three-phase configuration with communication connections.

8.2 Wiring Connection (Parallel)

NOTICE: It's required to connect to battery for parallel operation.

WARNING: Do not connect the current sharing cable between inverters which are in different phases. Otherwise, it may damage the inverters.

The cable size of each inverter is shown in the specifications table. Ensure all output N wires of each inverter are connected all the time. Otherwise, it will cause inverter fault (error code #72).

WARNING

  • Be sure the length of all battery cables is the same. Otherwise, there will be a voltage difference between the inverter and battery, causing parallel inverters not to work.

8.2.1 Parallel Operation in Single Phase

Two inverters in parallel: Each photovoltaic panel needs to be connected to an independent system.

Two Inverters in Parallel Power Connection Diagram
Wiring diagram for two inverters in parallel, single phase, showing battery, utility, load, and PV connections.

Communication Connection:

Two Inverters in Parallel Communication Connection Diagram
Communication wiring for two inverters in parallel.

Similar diagrams for three, four, five, six, seven, eight, and nine inverters in parallel, as well as various three-phase configurations, are available in the full user manual (PDF).

8.3 PV Connection (Parallel)

NOTE

  • Each inverter should be connected to an independent photovoltaic array. Multiple inverters must not share the same photovoltaic array, as this may cause irreversible damage to the inverters.

Refer to the schematic diagram below and combine it with the photovoltaic wiring guidelines in the wiring section to complete the connection of the photovoltaic array in parallel operation mode.

PV Connection for Parallel Operation Diagram
Schematic diagram for connecting photovoltaic arrays to multiple inverters in parallel, ensuring each inverter has an independent PV array.

8.4 Commissioning (Parallel)

Parallel in single phase:

Step 1: Check the following requirements before commissioning:

  • Correct wire connection.
  • Ensure all breakers in Line wires of the load side are open, and all Neutral wires of each unit are connected together.

Step 2: Turn on each unit and set "PAL" in LCD setting program 4 of each unit. Then shut down all units.

NOTE: It's necessary to turn off the switch when setting the LCD program. Otherwise, the setting cannot be programmed.

Step 3: Turn on each unit.

LCD Display in Master and Slave Units for Parallel Commissioning
Diagrams showing LCD displays for master and slave units during parallel commissioning, indicating their respective roles.

NOTE: Master and slave units are randomly defined.

9. User Tips

  • Voltage Compatibility: The PowMr Hybrid Solar Inverter is designed for 220/230/240VAC input and output. If your region uses 110V or 120V systems, this inverter may not be directly compatible without additional voltage conversion equipment. Always verify your local grid voltage requirements before installation.
  • Battery Type Selection: Ensure you correctly set the battery type (AGM, GEL, FLD, LI, SLD, USER) in the LCD settings to optimize charging and prolong battery life. For lithium batteries, setting the battery type to LIB will activate the battery via solar energy after 3 seconds.
  • Proper Ventilation: Always maintain the recommended clearances around the inverter (20cm sides, 50cm top/bottom) to ensure adequate airflow and prevent overheating, which can lead to reduced performance or faults.
  • Cable Sizing: Use appropriate cable sizes for battery and AC connections as specified in the manual to ensure system safety and efficient operation. Incorrect cable sizing can lead to power loss and potential hazards.

10. Warranty and Support

The PowMr Hybrid Solar Inverter (POW-HVM6.2KP) comes with a 1-year warranty.

For technical support, inquiries, or service, please contact:

  • Company: SHENZHEN HEHEJIN INDUSTRIAL CO.,LTD
  • Email: support@powmr.com
  • Website: www.powmr.com
  • Tel/Fax: +86755-28219903
  • Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China 55304-200-931

For the complete and most up-to-date user manual, please refer to the official PDF document available at: PowMr Hybrid Solar Inverter User Manual (PDF)


Ask a question about this manual