1. Introduction
This PowMr Hybrid Solar Inverter is a multi-function inverter/charger, combining the functionalities of an inverter, solar charger, and battery charger to provide uninterruptible power support. It features a comprehensive LCD display and user-configurable button operation for settings such as battery charging current, AC/solar charger priority, and acceptable input voltage, adapting to various applications.
1.1 Key Features
- Pure sine wave inverter.
- Configurable input voltage range for home appliances and personal computers via LCD setting.
- Configurable battery charging current based on applications via LCD setting.
- Configurable AC/Solar Charger priority via LCD setting.
- Compatible with mains voltage or generator power.
- Auto restart while AC is recovering.
- Overload/Over temperature/short circuit protection.
- Smart battery charger design for optimized battery performance.
- Cold start function.
- Supports parallel operation of up to 9 units.
1.2 Basic System Architecture
The inverter can power various appliances in home or industrial environments, including motor-type appliances such as tube lights, fans, refrigerators, and air conditioners. A complete system typically includes the inverter/charger, a generator or utility power source, and PV modules.
2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION: To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION: Only qualified personnel can install this device with a battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow the required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts, which could cause an explosion.
- Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Refer to the INSTALLATION section of this manual for details.
- One piece of 150A fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input to be short-circuited. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to a local dealer or service center for maintenance.
WARNING: Shock Hazard
- Installation must be performed with care due to high battery voltage in series.
CAUTION
- Before making the final DC connection or closing the DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
3. Setup (Installation)
3.1 Unpacking and Inspection
Before installation, please inspect the unit to ensure nothing inside the package is damaged. The package should contain:
- The inverter unit x 1
- User manual x 1
- Parallel communication cable x 1
- Share current wires x 1
- Expansion screw (M6*80mm) x 2
- Battery fuse x 1
3.2 Preparation
Before connecting any wiring, remove the bottom cover by unscrewing the four screws.
3.3 Mounting the Unit
Consider the following points when selecting an installation location:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level to allow the LCD display to be read at all times.
- For proper air circulation to dissipate heat, allow a clearance of approximately 20 cm to the sides and approximately 50 cm above and below the unit.
- The ambient temperature should be between 20°C and 35°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Be sure to keep other objects and surfaces as shown in the diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing three screws. Use M6*80mm expansion bolts for suspending and securing the equipment from above. Use M4 or M5 screws in the 3 holes to secure the equipment, as shown in the figure.
NOTICE
- To avoid potential damage to the terminal base and internal electronic components, it is recommended not to install screws in the mounting hole located at the lower left corner.
3.4 Grounding
Please make sure to connect the equipment grounding first, ensuring the device enclosure is reliably grounded before the system is powered on to effectively prevent personal injury caused by accidental leakage.
3.5 Battery Connection
The 6.2KW model supports 48VDC battery systems. Connect all battery banks as shown in the diagram below. It is recommended to install a separate DC over-current protector or disconnect device between the battery and inverter.
Insert the battery wires flatly into the battery connectors of the inverter and make sure the bolts are tightened with a torque of 2 Nm in a clockwise direction. Ensure correct polarity at both the battery and the inverter/charger terminals.
3.6 AC Input/Output Connection
Before connecting to the AC input power source, install a separate AC breaker between the inverter and the AC input power source. This ensures the inverter can be disconnected during maintenance and is fully protected from overcurrent. The recommended breaker specification is 63A for a 48V system.
There are two terminal blocks with "IN" and "OUT" markings. Do NOT mis-connect input and output connectors.
Follow these steps for AC input/output connection:
- Before making AC input/output connections, ensure the DC protector or disconnector is open.
- Remove 10mm of insulation sleeve for six conductors. Shorten phase L and N by 3mm.
- Insert AC main output wires according to polarities indicated on the terminal block and tighten terminal screws. Be sure to connect the PE protective conductor (Ground) first.
- Insert AC second output wires according to polarities indicated on the terminal block and tighten terminal screws. Be sure to connect the PE protective conductor (Ground) first.
- Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor (Ground) first.
WARNING
- Be sure that the AC power source is disconnected before attempting to hardwire it to the unit.
CAUTION
- Appliances such as air conditioners require at least 2-3 minutes to restart to balance refrigerant gas. If a power shortage occurs and recovers quickly, it can damage connected appliances. Check if your air conditioner has a time-delay function before installation. Otherwise, the inverter/charger may trigger an overload fault to protect the appliance, but internal damage to the air conditioner may still occur.
3.7 PV Connection
Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.
WARNING
- All wiring must be performed by qualified personnel.
- It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce the risk of injury, use the proper recommended cable size.
When choosing the right PV module, consider the following:
- The open circuit voltage (Voc) of the PV modules must not exceed the maximum PV array open circuit voltage of the inverter.
- The maximum supply voltage of the PV modules should be close to the optimal PV access voltage range of the inverter for best performance. If one PV module cannot meet this requirement, connect multiple PV modules in series.
Follow these steps to implement PV modules connection:
- Remove 10mm of insulation sleeve for positive and negative conductors.
- It is suggested to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Insert PV input wires according to polarities indicated on the terminal block and tighten the terminal screws.
- Check the correct polarity of the wire from PV modules and PV input connectors. Then, connect the positive pole (+) of the connection wire to the positive pole (+) of the PV input connector. Connect the negative pole (-) of the connection wire to the negative pole (-) of the PV input connector.
3.8 Final Assembly
After connecting all wirings, please install the bottom cover back by screwing the four screws.
4. Operation
4.1 Power ON/OFF
Once the unit has been properly installed and the batteries are connected, follow the power-on sequence below to start the inverter safely:
- Close the battery circuit breaker.
- Press the On/Off switch (located on the bottom of the case) to turn on the unit. Wait until the inverter starts up and enters normal operation (inverting).
- Close the PV and AC input circuit breakers.
- Finally, close the AC output circuit breaker.
To shut down the system, turn off the circuit breakers in the reverse order.
4.1.1 Steps to Start Up
Connect the battery that meets the requirements (battery voltage needs to be beyond 46V) or AC (AC needs to confirm the suitable input range depending on the output mode), then you can start up the inverter.
- Mains power on: Connect to normal AC power, press the switch, the system will automatically turn on. If you set AC output power priority, after waiting for a period of time, the panel will display AC mode, indicating successful startup, then it will enter AC mode.
- Battery boot: Connect to battery, press the power-on button to establish a working power source. The system will automatically turn on. After waiting for a period of time, the panel will display battery mode, indicating successful startup, then it will enter battery mode.
4.1.2 Shutdown Steps
When the system is in battery mode or AC mode output, press the switch again, then the system will be turned off.
4.2 Operation and Display Panel
The operation and display panel, located on the front of the inverter, includes three indicators, four function keys, and an LCD display, showing the operating status and input/output power information.
4.2.1 Function Keys
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
4.2.2 LED Indicators
| LED Indicator | Color | Status | Messages |
|---|---|---|---|
| AC/INV | Green | Solid On | Output is powered by utility in Line mode. |
| Flashing | Output is powered by battery or PV in battery mode. | ||
| CHG | Yellow | Solid On | Battery is fully charged. |
| Flashing | Battery is charging. | ||
| FAULT | Red | Solid On | Fault occurs in the inverter. |
| Flashing | Warning condition occurs in the inverter. |
4.2.3 LCD Display Icons
The LCD display information switches between input voltage, input frequency, PV voltage, charging current, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, DC discharging current, main board firmware version, and SCC firmware version.
4.3 Operating Mode Description
The inverter operates in various modes depending on the power sources and load conditions. These modes are visually represented on the LCD display.
5. Maintenance
5.1 Battery Equalization Description
The equalization function in the charge controller reverses the buildup of negative chemical effects like stratification and helps remove sulfate crystals that might reduce battery capacity. It is recommended to equalize the battery periodically.
5.1.1 How to Apply Equalization Function
Enable the battery equalization function in LCD setting program 30. Then, you may apply this function by either:
- Setting the equalization interval in program 35.
- Activating equalization immediately in program 36.
5.1.2 When to Equalize
When the setting equalization interval (battery equalization cycle) is reached, or equalization is active immediately, the controller will start to enter the Equalize stage.
5.1.3 Equalize Charging Time and Timeout
In the Equalize stage, the controller will supply power to charge the battery as much as possible until the battery voltage reaches the battery equalization voltage. Then, constant-voltage regulation is applied to maintain the battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until the set battery equalized time is reached.
If the battery equalized time expires and the battery voltage doesn't rise to the battery equalization voltage point, the charge controller will extend the battery equalized time until the battery voltage achieves the battery equalization voltage. If the battery voltage is still lower than the battery equalization voltage when the battery equalized timeout setting is over, the charge controller will stop equalization and return to the float stage.
6. Troubleshooting
6.1 Faults Descriptions
When a fault occurs, the inverter enters fault mode, the red LED light is always on, and the LCD displays a fault code.
6.1.1 Fault Reference Code
| Fault Code | Fault Event | What to do |
|---|---|---|
| 01 | Fan is locked when inverter is off. | Replace the fan. |
| 02 | Over temperature or NTC is not connected well. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. |
| 03 | Battery voltage is too high. | Return to repair center. Check if spec and quantity of batteries are meet requirements. |
| 04 | Battery voltage is too low. | Return to repair center. Check if spec and quantity of batteries are meet requirements. |
| 05 | Output short circuited or over temperature is detected by internal converter components. | Check if wiring is connected well and remove abnormal load. |
| 06/58 | Output abnormal (Inverter voltage below 190Vac or higher than 260Vac). | 1. Reduce the connected load. 2. Return to repair center. |
| 07 | Overload time out. | Reduce the connected load by switching off some equipment. |
| 08/09/53/57 | Internal components failed. | Return to repair center. |
| 51 | Over currents or surge. | Restart the unit, if the error happens again, please return to repair center. |
| 52 | Bus voltage is too low. | Restart the unit, if the error happens again, please return to repair center. |
| 55 | Output voltage is unbalanced. | Restart the unit, if the error happens again, please return to repair center. |
| 59 | PV input voltage is beyond these specification. | Reduce the number of PV modules in series. |
| 60 | Power feedback protection. | |
| 71 | Firmware version inconsistent. | |
| 72 | Current sharing fault. | |
| 80 | CAN fault. | |
| 81 | Host loss. | |
| 82 | Synchronization loss. | |
| 83 | Battery voltage detected different. | |
| 84 | AC input voltage and frequency detected different. | |
| 85 | AC output current unbalance. | |
| 86 | AC output mode setting is different. |
6.2 Warning Descriptions
When an alarm occurs, the red LED flashes, and the LCD displays an alarm code. The inverter does not enter failure mode.
6.2.1 Warning Indicator
| Warning Code | Warning Event | Audible Alarm | Icon flashing |
|---|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep three times every second | |
| 02 | Over temperature | None | |
| 03 | Battery is over-charged | Beep once every second | |
| 04 | Low battery | Beep once every second | |
| 07 | Overload | Beep once every 0.5 second | |
| 10 | Output power derating | Beep twice every 3 seconds | |
| 15 | PV energy is low. | Beep twice every 3 seconds | |
| 16 | High AC input (>280VAC) during BUS soft start | None | |
| E9 | Battery equalization | None | |
| 6P | Battery is not connected | None |
6.3 Code Reference
Related information codes will be displayed on the LCD screen. Check the inverter LCD screen for the operation.
| Code | Description |
|---|---|
| 60 | If battery status is not allowed to charge and discharge after successful communication between the inverter and battery, it will show code 60 to stop charging and discharging battery. |
| 61 | Communication lost. After battery is connected, if the communication signal is not detected for 1 minute, the buzzer will beep. Communication lost occurs after the inverter and battery are successfully connected, the buzzer beeps immediately. |
| 69 | If battery status is not allowed to charge after successful communication between the inverter and battery, it will show code 69 to stop charging battery. |
| 70 | If battery status must charge after successful communication between the inverter and battery, it will show code 70 to charge battery. |
| 71 | If battery status is not allowed to discharge after successful communication between the inverter and battery, it will show code 71 to stop discharge battery. |
7. Specifications
| Category | Specification | Value |
|---|---|---|
| AC Input | Input Sources | L+N+PE |
| Rated Input Voltage | 220/230/240VAC | |
| Voltage Range | 90-280VAC±3V (APL Mode); 170-280VAC±3V (UPS Mode) | |
| Frequency | 50Hz/60Hz (Auto Adaptive) | |
| Inverter Output | Rated Power (Battery Inverter) | 6200W |
| Rated Power (Photovoltaic Inverter) | 6500W | |
| Output Voltage | 220/230/240VAC±5% | |
| Output Frequency | 50Hz/60Hz±0.1% | |
| Waveform | Pure Sine Wave | |
| Transfer Time (Adjustable) | Computers (UPS Mode) 10ms, Appliance (APL Mode) 20ms | |
| Peak Power | 12400VA | |
| Grid-Connected Operation | Output Voltage | 220/230/240VAC±5% |
| Feed Into the Grid Voltage Range | 170-265VA | |
| Feed Into the Grid Frequency Range | 49-51±1Hz/59-61±1Hz | |
| Nominal Output Current | 26.9A | |
| Power Factor Range | >0.99 | |
| Battery | Battery Voltage | 48Vdc |
| Constant Charging Voltage (Adjustable) | 56.4Vdc | |
| Float Charging Voltage (Adjustable) | 54Vdc | |
| PV Input | PV Charging Mode | MPPT |
| MAX. PV Input Power | 8500W | |
| MPPT Tracking Range | 60~500Vdc | |
| Operating Voltage | 360~430V | |
| MAX. PV Input Voltage | 500Vdc | |
| PV Max Input Current | 27A | |
| MAX. PV Charging Current | 120A | |
| General Specifications | Operating Temperature | -10℃~50℃ |
| Humidity | 20%~95% (Non-condensing) | |
| Storage Temperature | -15℃~60℃ | |
| Altitude | Not Over 1000m, Derating over 1000m, Max 4000m, Refer to IEC62040 | |
| Noise | ≤50db | |
| Standards and Certification | EN-IEC 60335-1, EN IEC 60335-2-29, IEC 62109-1 |
8. Parallel Function (Appendix I)
The PowMr Hybrid Solar Inverter supports parallel operation of up to 9 units to create a high-power energy system, allowing for single-phase 230V or three-phase 400V configurations with a maximum output power of 55.8kW.
8.1 Mounting the Unit (Parallel)
When installing multiple units, follow the same mounting guidelines as for a single unit, ensuring proper air circulation and clearances.
8.2 Wiring Connection (Parallel)
NOTICE: It's required to connect to battery for parallel operation.
WARNING: Do not connect the current sharing cable between inverters which are in different phases. Otherwise, it may damage the inverters.
The cable size of each inverter is shown in the specifications table. Ensure all output N wires of each inverter are connected all the time. Otherwise, it will cause inverter fault (error code #72).
WARNING
- Be sure the length of all battery cables is the same. Otherwise, there will be a voltage difference between the inverter and battery, causing parallel inverters not to work.
8.2.1 Parallel Operation in Single Phase
Two inverters in parallel: Each photovoltaic panel needs to be connected to an independent system.
Communication Connection:
Similar diagrams for three, four, five, six, seven, eight, and nine inverters in parallel, as well as various three-phase configurations, are available in the full user manual (PDF).
8.3 PV Connection (Parallel)
NOTE
- Each inverter should be connected to an independent photovoltaic array. Multiple inverters must not share the same photovoltaic array, as this may cause irreversible damage to the inverters.
Refer to the schematic diagram below and combine it with the photovoltaic wiring guidelines in the wiring section to complete the connection of the photovoltaic array in parallel operation mode.
8.4 Commissioning (Parallel)
Parallel in single phase:
Step 1: Check the following requirements before commissioning:
- Correct wire connection.
- Ensure all breakers in Line wires of the load side are open, and all Neutral wires of each unit are connected together.
Step 2: Turn on each unit and set "PAL" in LCD setting program 4 of each unit. Then shut down all units.
NOTE: It's necessary to turn off the switch when setting the LCD program. Otherwise, the setting cannot be programmed.
Step 3: Turn on each unit.
NOTE: Master and slave units are randomly defined.
9. User Tips
- Voltage Compatibility: The PowMr Hybrid Solar Inverter is designed for 220/230/240VAC input and output. If your region uses 110V or 120V systems, this inverter may not be directly compatible without additional voltage conversion equipment. Always verify your local grid voltage requirements before installation.
- Battery Type Selection: Ensure you correctly set the battery type (AGM, GEL, FLD, LI, SLD, USER) in the LCD settings to optimize charging and prolong battery life. For lithium batteries, setting the battery type to LIB will activate the battery via solar energy after 3 seconds.
- Proper Ventilation: Always maintain the recommended clearances around the inverter (20cm sides, 50cm top/bottom) to ensure adequate airflow and prevent overheating, which can lead to reduced performance or faults.
- Cable Sizing: Use appropriate cable sizes for battery and AC connections as specified in the manual to ensure system safety and efficient operation. Incorrect cable sizing can lead to power loss and potential hazards.
10. Warranty and Support
The PowMr Hybrid Solar Inverter (POW-HVM6.2KP) comes with a 1-year warranty.
For technical support, inquiries, or service, please contact:
- Company: SHENZHEN HEHEJIN INDUSTRIAL CO.,LTD
- Email: support@powmr.com
- Website: www.powmr.com
- Tel/Fax: +86755-28219903
- Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China 55304-200-931
For the complete and most up-to-date user manual, please refer to the official PDF document available at: PowMr Hybrid Solar Inverter User Manual (PDF)