1. Product Overview
The ELECTESLA ZQ-D12 Series Variable Frequency Drive (VFD) is a high-tech industrial automation solution designed to regulate the speed of induction motors. It supports both 220V and 380V input/output configurations and is available in power ratings from 0.4KW to 2.2KW. This VFD offers precise motor control, energy saving features, and robust protection functions.

Key Features:
- Wide Voltage Compatibility: Supports 220V and 380V input/output.
- Power Range: Available for motors from 0.4KW to 2.2KW.
- Control Modes: V/F control, Sensorless Vector Control, Built-in PID control.
- Communication: Built-in RS485 for remote control and monitoring.
- Protection Functions: Comprehensive protection against overcurrent, overvoltage, overheat, undervoltage, module fault, short circuit, and more.
- User-Friendly Interface: Intuitive control panel with digital display and speed knob.
2. Safety Precautions
WARNING: Read the user manual before operation. Risk of electrical shock. Wait 10 minutes after removing power before servicing.
- For single-phase motors, it is recommended to remove the capacitor on the motor.
- Ensure the selected power supply voltage matches the VFD input voltage specification.
- Always disconnect the input power before performing any wiring.
- Wiring should only be performed by a professional electrical engineer.
- Ensure proper grounding of the VFD. For 400V level, grounding resistance should be 4Ω or below.
- Disconnect the main circuit power before any inspection or maintenance.
- Connect the braking resistor strictly according to the wiring diagram provided.
- Do not touch VFD terminals during operation due to high voltage hazards.
- Never change wiring or disassemble terminals while the VFD is powered on.
- Do not modify the inverter without authorization.
3. Product Specifications
3.1. General Specifications
| Attribute | Value |
|---|---|
| Brand Name | ELECTESLA |
| Model Number | ZQ-D12 |
| Type | DC/AC Inverters |
| Output Type | SINGLE |
| Output Frequency | 0-999HZ |
| Output Current | 2.5A-10A |
| Overload Capability | 150%/1min |
| Protection Class | IP20 |
| Operating Temperature | -10℃-65℃ |
| Certification | CE, FCC, RoHS |
| Weight | 1.5kgs |
3.2. Model-Specific Power and Current

| Model | Power (KW) | Output Current (A) |
|---|---|---|
| Three phase 380V input, Three phase 380V output | ||
| D12-T3-0R7G | 0.75 | 3 |
| D12-T3-1R5G | 1.5 | 4 |
| D12-T3-2R2G | 2.2 | 5 |
| Single phase 220V input, Three phase 220V output | ||
| D12-S2-0R4G | 0.4 | 2.5 |
| D12-S2-0R7G | 0.75 | 5 |
| D12-S2-1R5G | 1.5 | 7 |
| D12-S2-2R2G | 2.2 | 10 |
3.3. Dimensions

| Input Voltage | Output Voltage | Power | Rated Current | Size (L*W*H) |
|---|---|---|---|---|
| Input 1ph AC 220V 50/60Hz | Output 1ph AC 220V 0-999.9Hz | 0.4KW | 2.5A | 86*116*143mm |
| 0.75KW | 5A | |||
| Output 3ph AC 220V 0-999.9Hz | 1.5KW | 7A | 100*120*151mm | |
| 2.2KW | 10A | |||
| Input 3ph AC 380V 50/60Hz | Output 3ph AC 380V 0-999.9Hz | 0.4KW | 2A | 100*120*151mm |
| 0.75KW | 3A | |||
| 1.5KW | 4A | |||
| 2.2KW | 5A | |||
| Input 1ph AC 220V 50/60Hz | Output 3ph AC380V 0-999.9Hz | 0.4KW | 2A | 100*120*151mm |
| 0.75KW | 3A | |||
| 1.5KW | 4A | |||
| 2.2KW | 5A |
4. Installation and Wiring
4.1. Control Panel Layout

4.2. Main Circuit Wiring
The VFD supports both 220V and 380V connections for induction motors. Ensure correct phase connections as shown in the diagram below.

Main Circuit Terminals Function:
| Terminal | Function |
|---|---|
| R, S/L1, T/L2 | Power input for main circuit (R/S/T for 3-phase 380V, L1/L2 for 220V models) |
| U, V, W | Output of frequency inverter, terminal for connection to motor |
| P, PB | Connection of braking resistor |
| Grounding | Terminal for grounding |
4.3. Control Circuit Wiring
The VFD offers various control input and output terminals for flexible operation.



Control Circuit Terminals Function:
| Terminal | Function |
|---|---|
| GND | Public terminal of the control circuit |
| 10V | 10V output voltage (Max 10mA), commonly used as working voltage for external potentiometer |
| 12V | 12V output voltage (Max 10mA), commonly used as working voltage for logic input terminal |
| AVI | Voltage Analog input (0-10V) or Current Analog input (0/4-20mA) |
| X1-X5 | Digital inputs (FWD, REV, IDLE, Pulse Frequency Input, etc. configurable via parameters) |
| TA-TB-TC | Relay output (AC 250V/5A, DC 24V/2.5A) |
| Y1 | Open-collector output (Default running indication) |
| AO | Analog output (0-10V or 0/4-20mA) |
5. Operation
5.1. Basic Control Panel Operation
The VFD features a digital display and several keys for programming and control:
- **PRG (Program) Key**: Enters/exits parameter programming mode.
- **MF (Multi-function) Key**: Used for various functions, including reversing direction.
- **Up/Down Arrows**: Navigate through parameters and adjust values.
- **Shift Key**: Moves cursor during parameter editing.
- **ENTER Key**: Confirms parameter settings.
- **RUN Key (Green)**: Starts motor operation.
- **STOP/RESET Key (Red)**: Stops motor operation and resets faults.
- **Speed Knob**: Adjusts motor speed.
5.2. Changing Motor Rotation Direction
This video demonstrates how to change the motor's rotation direction (forward/reverse) using the VFD's control panel by adjusting parameter P8.04.
5.3. Parameter Settings (Overview)
The VFD has extensive programmable parameters organized into groups (P0, P1, P2, etc.) to customize its operation. Refer to the detailed parameter tables in the full PDF manual for specific settings.
- **Group P0 - Basic Operating Parameters**: Includes power specification, software version, run command channel selection, frequency setting selection, maximum output frequency, upper/lower limit frequency, and digital frequency control.
- **Group P1 - Auxiliary Operating Parameters**: Covers start mode, start/stop DC braking, jog acceleration/deceleration, hopping frequency, and combination of frequency setting methods.
- **Group P2 - Analog and Digital Input and Output Parameters**: Configures AO output limits, input terminal functions (FWD/STOP, REV/STOP, Multi-Speed, etc.), and FWD/REV terminal control mode.
- **Group P3 - PID Parameters**: Settings for PID function, gain, integration time, derivative time, sampling period, and sleep/awakening thresholds.
- **Group P4 - Advanced Function Parameters**: Motor rated parameters, AVR function, cooling fan control, automatic resets, energy consumption brake, PWM mode, slip compensation, and motor parameter self-learning.
- **Group P5 - Protection Function Parameters**: Motor overload protection, undervoltage/overvoltage levels, current limiting, feedback disconnection detection, and inverter overload settings.
- **Group P6 - Communication Parameters**: Native address, MODBUS communication configuration, timeout, and proportional linkage coefficient.
- **Group P7 - Supplementary Function Parameters**: Counting and timing mode, swing frequency control, and sudden jump frequency settings.
6. Troubleshooting
This section provides common fault codes and their possible causes and countermeasures.
| Fault Code | Name | Possible Cause | Countermeasures |
|---|---|---|---|
| E0C1 | Overcurrent during acceleration | Acceleration time too short, inverter power too small, improper V/F curve or torque boost | Extend acceleration time, choose larger power inverter, adjust V/F curve or torque boost |
| E0C2 | Overcurrent during deceleration | Deceleration time too short, inverter power too small | Extend deceleration time, choose larger power inverter |
| E0C3 | Overcurrent during uniform speed running | Load mutation or abnormality | Check the load or reduce load mutation |
| EHU1 | Overvoltage during acceleration | Abnormal input voltage | Check input power |
| ELU0 | Undervoltage during running | Input voltage abnormal or relay not drawn | Check power supply voltage or seek service |
| ESC1 | Power module fault | Inverter output short circuit or ground, control board abnormal, power device damage | Check motor wiring, refer to overcurrent, seek service |
| E-OH | Radiator overheating | Ambient temperature too high, fan damage, air duct blocked | Reduce ambient temperature, replace fan, dredge air duct |
| E485 | RS485 communication fault | RS485 channel interference, communication timeout | Check wiring, consider filter capacitor, retry |
7. User Tips
- **Parameter P0.02**: If using external control terminals for RUN/STOP, ensure P0.02 is set correctly (e.g., 1 for terminal control).
- **Motor Direction**: If the motor spins in the wrong direction, adjust parameter P8.04 as shown in the operation video.
- **Noise Reduction**: For silent operation, consider increasing the carrier frequency (P0.16), but be aware this may increase VFD heat.
- **Analog Input Stability**: If analog input signals (AVI) are unstable, adjust parameter P2.08 (Time constant of analog input signal filtering) to filter interference.
- **Remote Operation**: The VFD can be connected to an extension cable for remote operation, providing a clear and intuitive digital display.
8. Warranty and Support
The ELECTESLA ZQ-D12 Series VFD comes with an 18-month warranty from the date of purchase. ELECTESLA is committed to providing technical guidance and support for the lifetime of the product. For any technical inquiries or support needs, please contact ELECTESLA Official Store.