1. Introduction
This PowMr hybrid solar inverter is a multi-function inverter/charger that combines the functionalities of an inverter, solar charger, and battery charger. It is designed to provide uninterruptible power support in a compact size. The comprehensive LCD display allows users to configure settings such as battery charging current, AC/solar charger priority, and acceptable input voltage to suit various applications.
1.1. Key Features
- Pure sine wave output.
- Configurable input voltage range for home appliances and personal computers via LCD settings.
- Adjustable battery charging current based on application requirements via LCD settings.
- Configurable AC/Solar Charger priority via LCD settings.
- Compatible with mains voltage or generator power input.
- Automatic restart function upon AC recovery.
- Built-in protections against overload, over-temperature, and short circuits.
- Smart battery charger design for optimized battery performance.
- Cold start function for system initiation without AC input.
1.2. Basic System Architecture
The inverter integrates with solar panels, a generator or utility power, and a battery bank to supply power to various home appliances. It can power a wide range of devices in home or office environments, including motor-type appliances like tube lights, fans, refrigerators, and air conditioners.

Image: Diagram illustrating the hybrid power system application, showing solar panels, generator, and utility feeding into the inverter, which then connects to a battery and various home appliances.
1.3. Product Overview
The inverter features an LCD display, status indicators, function buttons, and various input/output ports for comprehensive control and connectivity.

Image: Detailed view of the inverter's rear panel with labeled components: 1. LCD display, 2. Status indicator, 3. Charging indicator, 4. Fault indicator, 5. Function buttons, 6. Circuit breaker, 7. AC input, 8. Dry connect, 9. PV input, 10. ON/OFF switch, 11. AC output, 12. RS232 Communication port, 13. DC input/Battery input.
2. Safety Instructions
WARNING: This section contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION: To reduce risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION: Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation, follow required specifications to select appropriate cable sizes.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts, which could cause an explosion.
- Strictly follow installation procedures when disconnecting AC or DC terminals.
- Fuses (4 pieces of 40A, 32VDC for 1KVA/2KVA; 6 pieces of 40A, 32VDC for 3KVA; 1 piece of 200A, 64VDC for 4KVA and 5KVA) are provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Comply with local requirements and regulations.
- NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
- Warning: Only qualified service persons are able to service this device. If errors persist after troubleshooting, send the inverter/charger back to the local dealer or service center for maintenance.
3. Installation and Setup
3.1. Unpacking and Inspection
Before installation, inspect the unit. Ensure nothing inside the package is damaged. The package should contain:
- The inverter unit x 1
- User manual x 1
- Communication cable x 1
- Software CD x 1
3.2. Preparation
Before connecting any wirings, remove the bottom cover by unscrewing two screws.
3.3. Mounting the Unit
Consider the following points for installation:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install at eye level for easy LCD display reading.
- Allow approximately 20 cm clearance to the sides and 50 cm above and below for proper air circulation.
- Ambient temperature should be between 0°C and 55°C for optimal operation.
- Adhere to the wall vertically.
- Ensure enough space for heat dissipation and wiring.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing three screws into the designated mounting holes.
3.4. Battery Connection
CAUTION: For safety and regulation compliance, install a separate DC over-current protector or disconnect device between the battery and inverter.
WARNING: All wiring must be performed by qualified personnel. Use appropriate cable sizes for battery connection to reduce risk of injury.
This model (PS-3K-110V) supports a 24VDC battery system. Connect all battery packs as shown in the manual's diagrams. It is suggested to connect at least a 100Ah capacity battery for 1-3KVA models and at least 200Ah for 4KVA/5KVA models. Only use sealed lead-acid or sealed GEL/AGM lead-acid batteries.
Recommended Battery Cable and Terminal Size for 3KVA Model:
| Typical Amperage | Battery Capacity | Wire Size | Cable mm² | Ring Terminal D (mm) | Ring Terminal L (mm) | Torque Value |
|---|---|---|---|---|---|---|
| 100A | 100AH / 200AH | 1*4AWG / 2*8AWG | 22 / 14 | 6.4 | 33.2 / 29.2 | 2~3 Nm |
Insert the ring terminal of the battery cable flatly into the battery connector of the inverter. Ensure bolts are tightened with a torque of 2-3 Nm. Verify correct polarity at both the battery and inverter/charger. Ring terminals must be tightly screwed to the battery terminals.
WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.
CAUTION: Do not place anything between the flat part of the inverter terminal and the ring terminal. Overheating may occur. Do not apply anti-oxidant substance on the terminals before connecting. Before final DC connection, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).

Image: Inverter showing compatibility with Flooded, AGM, Gel, and Sealed Lead Acid Batteries.
3.5. AC Input/Output Connection
CAUTION: Before connecting to AC input power source, install a separate AC breaker between the inverter and AC input power source. This ensures the inverter can be securely disconnected and protected from overcurrent. The recommended AC breaker for 3KVA is 32A.
CAUTION: There are two terminal blocks labeled "IN" and "OUT". Do NOT mis-connect input and output connectors.
WARNING: All wiring must be performed by qualified personnel. Use appropriate cable for AC input connection.
Suggested Cable Requirement for AC Wires (3KVA Model):
| Model | Gauge | Torque Value |
|---|---|---|
| 3KVA | 12 AWG | 1.2~1.6 Nm |
Before making AC input/output connections, ensure the DC protector or disconnector is open. Remove insulation sleeve 10mm for conductors. Insert AC input wires according to polarities (Ground: yellow-green, Line: brown or black, Neutral: blue) and tighten terminal screws. Ensure PE protective conductor is connected first. Then, insert AC output wires similarly.
WARNING: Ensure AC power source is disconnected before hardwiring to the unit.
CAUTION: Important. Connect AC wires with correct polarity. Reversed L and N wires can cause utility short-circuiting in parallel operation.
CAUTION: Appliances like air conditioners require 2-3 minutes to restart. Check if your air conditioner has a time-delay function to prevent damage from short power interruptions.
3.6. PV Connection (For models with solar charger)
CAUTION: Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.
WARNING: All wiring must be performed by qualified personnel. Use appropriate cable for PV module connection.
Suggested Cable Requirement for PV Wires:
| Typical Amperage | Gauge | Torque Value |
|---|---|---|
| 50A | 8 AWG | 1.4~1.6 Nm |
PV Module Selection (3KVA Model):
- Open circuit Voltage (Voc) of PV modules must not exceed 60Vdc.
- Max. Power Voltage (Vmpp) of PV modules should be close to 30Vdc or within 30Vdc~32Vdc for best performance.
Remove insulation sleeve 10mm for positive and negative conductors. Check correct polarity of connection cable from PV modules and PV input connectors. Connect positive pole (+) of connection cable to positive pole (+) of PV input connector, and negative pole (-) to negative pole (-).
3.7. Final Assembly
After connecting all wirings, replace the bottom cover by screwing the two screws back in.
3.8. Communication Connection
Use the supplied communication cable to connect the inverter to a computer. Insert the bundled CD and follow on-screen instructions to install the monitoring software. Refer to the software user manual on the CD for detailed operation.
3.9. Dry Contact Signal
A dry contact (3A/250VAC) is available on the rear panel. It can deliver a signal to an external device when the battery voltage reaches a warning level.
4. Operation
4.1. Power ON/OFF
Once the unit is properly installed and batteries are connected, press the On/Off switch (located on the bottom of the case) to turn on the unit.
4.2. Operation and Display Panel
The front panel features an LCD display, three indicators (AC/INV, CHG, FAULT), and four function keys (ESC, UP, DOWN, ENTER) to show operating status and input/output power information.
LED Indicator Meanings:
| Indicator | Color | State | Message |
|---|---|---|---|
| AC/INV | Green | Solid On | Output powered by utility (Line mode) |
| Flashing | Output powered by battery or PV (Battery mode) | ||
| CHG | Green | Solid On | Battery fully charged |
| Flashing | Battery is charging | ||
| FAULT | Red | Solid On | Fault occurs in the inverter |
| Flashing | Warning condition occurs in the inverter |
Function Key Descriptions:
- ESC: To exit setting mode.
- UP: To go to previous selection.
- DOWN: To go to next selection.
- ENTER: To confirm selection in setting mode or enter setting mode.
4.3. LCD Display Icons
The LCD displays various icons indicating input source (AC, PV), input/battery voltage, charger current, setting programs, warning/fault codes, output load information (voltage, frequency, load percent, VA, Watt), and battery information (level, charging status).
4.4. LCD Setting
Press and hold the ENTER button for 3 seconds to enter setting mode. Use UP/DOWN to select programs, then ENTER to confirm or ESC to exit. Key settings include:
- Program 01: Output source priority (Solar First, Utility First, SBU Priority).
- Program 02: Maximum charging current (10A to 50A, depending on model).
- Program 03: AC input voltage range (Appliances or UPS).
- Program 04: Power saving mode enable/disable.
- Program 05: Battery type (AGM, Flooded, User-Defined).
- Program 06/07: Auto restart when overload or over-temperature occurs.
- Program 09: Output frequency (50Hz/60Hz).
- Program 11: Maximum utility charging current.
- Program 12/13: Setting voltage point back to utility/battery source.
- Program 16: Charger source priority (Solar First, Utility First, Solar and Utility, Only Solar).
- Program 18: Alarm control.
- Program 19: Auto return to default display screen.
- Program 20: Backlight control.
- Program 22: Beeps while primary source is interrupted.
- Program 23: Overload bypass enable/disable.
- Program 25: Record Fault code enable/disable.
- Program 26: Bulk charging voltage (C.V voltage) for User-Defined battery type.
- Program 27: Floating charging voltage for User-Defined battery type.
- Program 29: Low DC cut-off voltage for User-Defined battery type.
4.5. Display Setting
Pressing the UP or DOWN key cycles through various display information: input voltage, input frequency, PV voltage, charging current, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, DC discharging current, main CPU Version, and second CPU Version.
4.6. Operating Mode Description
The inverter operates in several modes:
- Standby Mode / Power Saving Mode: No output is supplied, but the unit can still charge batteries.
- Fault Mode: Errors are caused by internal circuit issues or external reasons (over-temperature, output short circuit). PV energy and utility can charge batteries.
- Line Mode: The unit provides output power from the mains and charges the battery.
- Battery Mode: The unit provides output power from the battery and PV power.

Image: Diagram illustrating the four charging modes (Solar First, Utility First, Solar and Utility, Only Solar) and three load output working modes (Utility First, Solar First, SBU First).
5. Specifications
5.1. Table 1 Line Mode Specifications
| Parameter | Specification (3KVA) |
|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) |
| Nominal Input Voltage | 230Vac |
| Low Loss Voltage (UPS/Appliances) | 170Vac±7V / 90Vac±7V |
| Low Loss Return Voltage (UPS/Appliances) | 180Vac±7V / 100Vac±7V |
| High Loss Voltage | 280Vac±7V |
| High Loss Return Voltage | 270Vac±7V |
| Max AC Input Voltage | 300Vac |
| Nominal Input Frequency | 50Hz / 60Hz (Auto detection) |
| Low Loss Frequency | 40±1Hz |
| Low Loss Return Frequency | 42±1Hz |
| High Loss Frequency | 65±1Hz |
| High Loss Return Frequency | 63±1Hz |
| Output Short Circuit Protection | Circuit Breaker |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) |
| Transfer Time (UPS/Appliances) | 10ms typical / 20ms typical |
5.2. Table 2 Inverter Mode Specifications
| Parameter | Specification (3KVA) |
|---|---|
| Rated Output Power | 3KVA/2.4KW |
| Output Voltage Waveform | Pure Sine Wave |
| Output Voltage Regulation | 230Vac±5% |
| Output Frequency | 50Hz |
| Peak Efficiency | 90% |
| Overload Protection | 5s@≥150% load; 10s@110%~150% load |
| Surge Capacity | 2* rated power for 5 seconds |
| Nominal DC Input Voltage | 24Vdc |
| Cold Start Voltage | 23.0Vdc |
| Low DC Warning Voltage (@load < 20% / 20%≤load<50% / load≥50%) | 22.0Vdc / 21.4Vdc / 20.2Vdc |
| Low DC Warning Return Voltage (@load < 20% / 20%≤load<50% / load≥50%) | 23.0Vdc / 22.4Vdc / 21.2Vdc |
| Low DC Cut-off Voltage (@load < 20% / 20%≤load<50% / load≥50%) | 21.0Vdc / 20.4Vdc / 19.2Vdc |
| High DC Recovery Voltage | 29Vdc |
| High DC Cut-off Voltage | 31Vdc |
| No Load Power Consumption | <20W |
| Saving Mode Power Consumption | <10W |
5.3. Table 3 Charge Mode Specifications
| Parameter | Specification (3KVA) |
|---|---|
| Charging Algorithm | 3-Step |
| Utility Charging Mode AC Charging Current | 20/30Amp (@VI/P=230Vac) |
| Bulk Charging Voltage (Flooded/AGM/Gel) | 29.2V / 28.2V |
| Floating Charging Voltage | 27Vdc |
| Solar Charging Mode Charging Current (PWM) | 50Amp |
| System DC Voltage | 24Vdc |
| Operating Voltage Range | 30~32Vdc |
| Max. PV Array Open Circuit Voltage | 60Vdc |
| Standby Power Consumption | 1W |
| DC Voltage Accuracy | +/-0.3% |
| Joint Utility and Solar Charging Max Charging Current | 50Amp |
| Default Charging Current | 50Amp |
5.4. Table 4 General Specifications
| Parameter | Specification (3KVA) |
|---|---|
| Safety Certification | CE |
| Operating Temperature Range | 0°C to 55°C |
| Storage temperature | -15°C~60°C |
| Dimension (D*W*H), mm | 100 x 272 x 355 |
| Net Weight, kg | 6.9 |
6. Troubleshooting
This section provides common issues, their possible causes, and recommended solutions.
| Problem | LCD/LED/Buzzer | Explanation / Possible Cause | What to do |
|---|---|---|---|
| Unit shuts down automatically during startup | LCD/LEDs and buzzer active for 3s then off | Battery voltage too low (<1.91V/Cell) | 1. Re-charge battery. 2. Replace battery. |
| No response after power on | No indication | 1. Battery voltage too low (<1.4V/Cell). 2. Battery polarity reversed. | 1. Check battery/wiring. 2. Re-charge battery. 3. Replace battery. |
| Input voltage 0, green LED flashing | Input protector tripped | Check AC breaker/wiring. | |
| Mains exist but unit works in battery mode | Green LED flashing | Insufficient quality of AC power | 1. Check AC wires. 2. Check generator/input voltage range. |
| Green LED flashing |