ECGSOLAX iXCEED 3K24-S120, 3.6K24-S120, 5K48-S120

Contents

ECGSOLAX Hybrid Solar Inverter User Manual

Models: iXCEED 3K24-S120, iXCEED 3.6K24-S120, iXCEED 5K48-S120

Brand: ECGSOLAX

1. Safety Instructions

This section contains important safety and operating instructions. Read and keep this manual for future reference.

  • Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  • CAUTION: To reduce risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  • Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  • To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  • CAUTION: Only qualified personnel can install this device with battery.
  • NEVER charge a frozen battery.
  • For optimum operation, follow required specifications to select appropriate cable size.
  • Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  • Strictly follow installation procedure when disconnecting AC or DC terminals.
  • One piece of 150A fuse is provided as over-current protection for the battery supply.
  • GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Comply with local requirements and regulations.
  • NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
  • Warning: Only qualified service persons are able to service this device. If errors persist after troubleshooting, send this inverter/charger back to local dealer or service center.

2. Product Overview

This multi-function inverter/charger combines inverter, solar charger, and battery charger functions to provide uninterruptible power support. It features a comprehensive LCD display for user-configurable settings.

ECGSOLAX Hybrid Solar Inverter with key specifications

Figure 1: ECGSOLAX Hybrid Solar Inverter - Key Features

2.1 Features

  • Capable to operate without Battery
  • Wider PV input voltage range: 60V~300Vdc
  • Excellent solar MPPT performance, efficiency up to 99%
  • PV generated energy Total and Daily information
  • Battery wake-up function
  • Capable to communicate with battery BMS by RS-485 interface
  • Pure sine wave inverter
  • Configurable battery charging or discharging current based on applications via LCD setting
  • Configurable AC/Solar Charger priority via LCD setting
  • Overload/ Over temperature/ short circuit protection
Inverter with 360 degree protection and list of protection features

Figure 2: Comprehensive Protection Features

  • Short Circuit Protection
  • Over-Load Protection
  • Over Current Protection
  • Backfill Protection
  • Over Voltage Protection
  • Over-Temperature Protection
  • Under Voltage Protection
  • Over Charge Protection

2.2 Product Components

The following diagram illustrates the main components of the Hybrid Solar Inverter.

Diagram of Hybrid Solar Inverter with labeled parts

Figure 3: Hybrid Solar Inverter Components

  • 1. LCD display
  • 2. Status indicator
  • 3. Bypass indicator
  • 4. Fault indicator
  • 5. Function buttons
  • 6. Power on/off switch
  • 7. AC input
  • 8. AC output
  • 9. PV input
  • 10. Battery input
  • 11. Circuit breaker
  • 12. BMS RS485 communication port
  • 13. USB communication port
  • 14. Dust proof components
Bottom and back view of the Hybrid Solar Inverter

Figure 4: Inverter Bottom and Back Panel Connections

3. Setup (Installation)

3.1 Unpacking and Inspection

Before installation, inspect the unit for any damage. The package should contain:

  • The inverter unit x 1
  • User manual x 1
  • Screws x 2

3.2 Preparation

Before connecting all wirings, remove the bottom cover by unscrewing the two screws.

3.3 Mounting the Unit

Consider the following points when selecting the installation location:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install at eye level for easy LCD display reading.
  • Allow approximately 20 cm clearance to the sides and 50 cm above and below for proper air circulation.
  • Ambient temperature should be between 0°C and 55°C.
  • Mount vertically on the wall.
  • Ensure sufficient space for heat dissipation and wiring.

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Mounting dimensions and clearances for the inverter

Figure 5: Recommended Mounting Clearances

Install the unit by screwing two M6x50 screws into the wall.

3.4 Battery Connection

CAUTION: Install a separate DC over-current protector or disconnect device between the battery and inverter. Refer to the table below for required fuse or breaker size.

WARNING: All wiring must be performed by qualified personnel. Use appropriate cable sizes for battery connection.

ModelWire SizeCable (mm²)Torque value (max)
3KW/3.6KW1x 3 AWG256 N·m
5KW1x 3 AWG256 N·m

Steps for battery connection:

  1. Remove 18 mm insulation sleeve for positive and negative conductors.
  2. Use bootlace ferrules on wire ends with a proper crimping tool.
  3. Connect all battery packs as shown in the diagram.
  4. Insert battery wires flatly into inverter battery connectors and tighten bolts to 6 N·m. Ensure correct polarity.

WARNING: Shock Hazard! Installation must be performed with care due to high battery voltage.

CAUTION: Before final DC connection, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).

3.5 AC Input/Output Connection

CAUTION: Install a separate AC breaker between the inverter and AC input power source. Recommended AC breaker specs: 32A for 3KW/3.6KW, 50A for 5KW.

WARNING: All wiring must be performed by qualified personnel. Use appropriate cable sizes for AC input connection.

ModelGaugeCable (mm²)Torque Value
3KW/3.6KW10 AWG62 N·m
5KW8 AWG102 N·m

Steps for AC input/output connection:

  1. Before connection, open DC protector or disconnector.
  2. Remove 10mm insulation sleeve for conductors. Shorten phase L and neutral N by 3mm.
  3. Insert AC input wires according to polarities (L, N, PE) and tighten screws. Connect PE first.
  4. Insert AC output wires according to polarities and tighten screws. Connect PE first.
  5. Ensure all wires are securely connected.

WARNING: Ensure AC power source is disconnected before hardwiring.

3.6 PV Connection

CAUTION: Install a DC circuit breaker between PV modules and the inverter.

WARNING: Use appropriate cable sizes for PV module connection.

ModelWire SizeCable (mm²)Torque value (max)
3kW/3.6kW/5KW1x 12 AWG41.2 N·m

PV Module Selection Parameters:

  • Open circuit Voltage (Voc) of PV modules must not exceed max. PV array open circuit voltage of inverter (300Vdc).
  • Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
  • MPPT Operating Voltage Range: 70-280Vdc.

Steps for PV module connection:

  1. Remove 10 mm insulation sleeve for positive and negative conductors.
  2. Use bootlace ferrules on wire ends with a proper crimping tool.
  3. Check correct polarity of wire connection from PV modules and PV input connectors. Connect positive to positive, negative to negative. Tighten screws.

3.7 Final Assembly

After connecting all wiring, replace the bottom cover by screwing the four screws.

3.8 Communication Connection

BMS RS-485 Communication: Use the supplied cable to connect to the inverter and Lithium battery pack's BMS RS-485. Select PYLON communication protocol. The battery icon "Li" will blink when communication is OK. Reconfigure charging voltage, current, discharge cut-off voltage, and SOC according to BMS parameters.

USB Communication: Use the supplied cable to connect to the inverter and PC to view inverter information via upper computer software.

Wi-Fi Cloud Communication (Optional): Use the supplied cable to connect to the inverter and Wi-Fi module. Download the APP, install it, and follow the "WiFi Plug Quick Installation Guideline" to set up the network. Inverter status will be shown on the mobile phone APP or webpage.

4. Operating Instructions

4.1 Power ON/OFF

Once the unit is properly installed and batteries are connected, press the On/Off switch (located on the bottom of the case) to turn on the unit.

4.2 Operation and Display Panel

The front panel includes three indicators, four function keys, and an LCD display showing operating status and input/output power information.

LCD display screen with real-time monitoring data

Figure 6: LCD Display Screen and Internal Features

LED Indicators

IndicatorColorStatusMessages
INVGreenSolid On
Flashing
Output powered by PV(main) or Bat in Inverter mode.
Output powered by bat(main) or PV in Inverter mode.
BYPASSYellowSolid On
Flashing
Output powered by utility in Line mode.
Output powered by utility and PV/Bat in Hybrid mode.
FAULTRedSolid On
Flashing
Fault condition occurs in the inverter.
Warning condition occurs in the inverter.

Function Keys

Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or display in-turns

4.3 LCD Display Icons

The LCD displays various icons to indicate input source, configuration, fault information, output, and battery status. Refer to the manual for a detailed description of each icon.

4.4 LCD Settings

Press and hold "ESC" and "ENTER" buttons together for >10 seconds to enter setting mode. Use "UP" or "DOWN" to select programs, and "ENTER" to confirm. "ESC" exits the mode.

Configurable settings include: Output voltage, Output frequency, Output source priority (Solar first, SBU priority, Utility first), Battery type, Maximum/Minimum Battery Charging/Discharging Voltage, Battery SOC Reserved for backup, Maximum battery charging/discharging current, Under voltage SOC value, Grid connection function, Alarm control, Restore factory setting, and Calendar Clock settings.

4.5 Display Information

The LCD display information can be switched using "UP" or "DOWN" keys, or by pressing "ENTER". Information displayed includes: Output voltage/load power, Output frequency/load current, PV voltage/PV current, PV generated energy Today/PV power, Battery voltage/Battery SOC, Battery Charging current/Battery power, Unit temperature/Battery Discharging current, Input AC voltage/Input AC frequency, Unit firmware Version, and calendar clock.

4.6 PV Generated Energy Information Display

Press and hold "ESC" and "UP" buttons together for >10 seconds to display PV generated energy information. Use "UP" or "DOWN" to show PV generated energy Total or Daily for nearly 10 days. "ENTER" exits.

4.7 Operating Mode Description

The inverter operates in various modes: Standby, Fault, Bypass, and Hybrid. Each mode has specific conditions and behaviors related to power source (utility, PV, battery) and charging status.

5. Maintenance

Regular maintenance ensures optimal performance and longevity of your inverter. While specific maintenance steps are not detailed, general best practices include:

  • Keep the inverter area clean and free from dust and debris to ensure proper ventilation.
  • Periodically check all wiring connections for tightness and signs of corrosion.
  • Ensure the cooling fans are operating correctly and are not obstructed.
  • Monitor the LCD display for any warning or fault codes and address them promptly.
  • If the unit requires internal servicing, always refer to qualified personnel.

6. Troubleshooting

Refer to the following table for common issues and their solutions. If problems persist, contact customer support.

6.1 Fault Reference Code

Fault CodeFault Event
01Overload time out
02Over temperature
03INV Over current
04Invert Short
05Output voltage is too high
06Output voltage is too low
07Bus voltage is abnormal
08Bus voltage is too high
09Bus voltage is too low
10PV Over current
11Fan Fail
12Battery voltage is too high
13Battery voltage is too low
14Battery disconnected
15Temperature sensor wire disconnected

6.2 Troubleshooting Table

ProblemLCD/LED/BuzzerExplanation / Possible CauseWhat to do
Mains power often outages, battery backup time is insufficientThe inverter works properly.Poor battery performance or small capacity; Battery SOC is low during power outage.Increase battery capacity; Select "SBU" priority and set "Battery SOC Reserved" High (SoH), or select "UTL" mains priority.
Electricity supply is stable, but electricity bill has not decreased significantlyThe inverter works properly.Insufficient use of solar energy or batteries.If mains is stable, select SBU and set Battery SOC Reserved Low (SoL) to reduce mains power supply.
No reaction after battery is connectedNo displayBattery voltage is too low; Battery polarity is reversed; Battery input is damaged.1. Check battery connection. 2. Charge or replace battery. 3. Replace inverter.
After battery is connected, it automatically shuts down during startupLCD/LEDs and buzzer work for 3S and then turn offBattery voltage is too low1. Re-charge battery. 2. Replace battery.
When mains is connected, LCD voltage of inverter is 0Green LED is flashing.Input protector is tripped; Insufficient quality of AC power.Check if AC breaker is tripped and AC wiring is connected well; Check if AC wires are too thin/long; Check mains voltage.
When unit is turned on, internal relay is switched on and off repeatedlyLCD display and LEDs are flashingBattery is disconnected.Check if battery wires are connected well.
Buzzer beeps continuously and red LED is onFault code 01Overload error.Reduce the connected load by switching off some equipment.
Buzzer beeps continuously and red LED is onFault code 02Over temperature fault: Radiator temperature exceeds 80°C.Check if inlet/outlet are blocked or ambient temperature is too high.
Buzzer beeps continuously and red LED is onFault code 03Inverter overflows and internal components fail.Restart inverter. If not working, return to repair center.
Buzzer beeps continuously and red LED is onFault code 04Output short circuit.Check if wiring is connected well and remove abnormal load.
Buzzer beeps continuously and red LED is onFault code 05/06High/Low output voltage.Restart inverter. If not working, return to repair center.
Buzzer beeps continuously and red LED is onFault code 07/08/09Bus voltage is abnormal/too high/too low.Restart inverter. If not working, return to repair center.
Buzzer beeps continuously and red LED is onFault code 10PV over current.Check if wiring is connected well or replace the fan.
Buzzer beeps continuously and red LED is onFault code 11Fan error.Check if wiring is connected well or replace the fan.
Buzzer beeps continuously and red LED is onFault code 12/13Battery voltage is too high/too low.1. Check if wiring is connected well. 2. Check if spec and quality of batteries are met.
Buzzer beeps continuously and red LED is onFault code 14Battery not connected.1. Check if wiring is connected well. 2. Check if spec and quality of batteries are met.

7. Specifications

ParameteriXCEED 3K-24S120iXCEED 3.6K24-S120iXCEED 5K48-S120
PV Array
Max. PV Array Power3600W4200W6000W
Max. PV Array Open-Circuit Voltage300Vdc
Start-up Voltage60Vdc
MPPT Operating Voltage Range70-280Vdc
MPPT Efficiency99%
Nominal Input Voltage250Vdc
Max. Input Current MPPT30A
Battery
Battery TypeLead-acid/Li-ion
Nominal Battery Voltage24V48V
Battery Voltage Range21-29V42-58V
Max. AC Charging Current40A50A50A
Max. PV Charging Current80A100A100A
Max. Continuous Discharging Current100A100A120A
AC Input
Nominal Voltage120Vac
Voltage Range90-140Vac
Frequency50/60Hz (Auto sensing)
Max. Input Current40A50A
AC Output
Nominal Voltage120Vac±5%
Output Voltage WaveformPure Sine Wave
Rated Output Power3000VA/3000W4200VA/4200W5000VA/5000W
Peak Output Power4500VA5400VA7500VA
Nominal Output Frequency50/60Hz
Transfer Time10ms
Max. PV to AC Efficiency96.50%96.50%
Max. Battery to AC Efficiency91.00%93.00%
Protection
Over Temperature ProtectionYes
Overload Protection3s@≥150% load; 10s@110%~150% load
General Data
Operating Temperature Range-10 ~ +50°C
Safety CertificationCE
Relative Humidity0~95% Relative Humidity (Non-condensing)
Max. Operating Altitude< 4000m
Cooling MethodIntelligent Fan cooling
DisplayLED + LCD
Communication with BMSRS-485
Communication with CloudWiFi/4G
Degree of ProtectionIP21
Weight6.5kg8.4kg
Dimension (W*H*D)348*95mm*290370*107*320
Mounting MethodWall Mounted

8. User Tips

  • The 48V model of this inverter can be used as an Uninterruptible Power Supply (UPS) for critical loads.
  • The 48V model is compatible with lithium batteries, offering flexibility in battery choice.
  • Ensure proper battery configuration (e.g., two lithium batteries) to match the inverter's voltage requirements.

9. Warranty and Support

For warranty information, technical support, or service inquiries, please contact your authorized ECGSOLAX dealer or the point of purchase. Keep your purchase receipt as proof of purchase.