Contents

Aninerel Hybrid Solar Inverter/Charger

User Manual for Models ANJ-6200W-48V-WIFI, ANL-4200T-24L-W-PRO, ANL-2000W-12L-W

About This Manual

This manual describes the assembly, installation, operation, and troubleshooting of the Aninerel Hybrid Solar Inverter/Charger. Please read this manual carefully before installations and operations. Keep this manual for future reference.

This manual provides safety and installation guidelines as well as information on tools and wiring.

Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION --To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION - Only qualified personnel can install this device with battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to the Installation section of this manual for details.
  10. Fuse is provided as over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
  12. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
  13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.

Product Overview

The Aninerel Hybrid Solar Inverter/Charger is designed to efficiently manage solar power, utility grid power, and battery power for various applications. It features a user-friendly interface with an LCD display and function buttons for easy operation and monitoring.

Front and rear view of the Aninerel 4.2KVA Hybrid Solar Inverter/Charger, highlighting LCD display, function buttons, RGB indicator, power on/off switch, and various connection ports.
Figure 1: Front and Rear Panel Overview (4.2KVA Model)

Component Identification

  1. LCD display
  2. Function buttons
  3. RGB indicator
  4. Grounding
  5. RS232 communication port
  6. RS485 communication port
  7. AC input
  8. Main out
  9. Second out
  10. Battery input
  11. PV input
  12. Power on/off switch

Product Features

Key features of the 4.2KW 24V inverter, including dual output, lithium battery activation, pure sine wave, power factor 1.0, PV input 60-500Vdc, 120A MPPT, and WiFi remote monitoring.
Figure 2: Product Features (120A MPPT Model)
  • Dual output for smart load management
  • Lithium battery activation function by PV or Utility
  • Colored LCD with RGB lights
  • Compatible work with LiFePO4 battery via RS485
  • PV input 60Vdc~500Vdc Max
  • Built-in MPPT 120A
  • Capable to work without battery
  • Detachable dust cover for harsh environment
  • WiFi remote monitoring
  • Support multiple output priority: UTL, SOL, SBU, SUB
  • EQ function to optimize battery performance and extend lifecycle
Key features of the 4.2KW 24V inverter, including lithium battery activation, WiFi, harsh environment suitability, pure sine wave, power factor 1.0, PV input 30-160Vdc, high efficiency, and 60A MPPT.
Figure 3: Product Features (60A MPPT Model)
  • Lithium battery activation function by PV or Utility
  • Compatible work with LiFePO4 battery via RS485
  • Power factor 1.0
  • PV input Voltage 30Vdc~160Vdc
  • Built-in MPPT 60A
  • Detachable dust cover for harsh environment
  • WiFi remote monitoring optional
  • Support multiple output priority: UTL, SOL, SBU

Installation

Unpacking and Inspection

Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items:

  • The unit x 1
  • User manual x 1

Preparation

Before connecting all wirings, please take off the bottom cover by removing two screws as shown below.

Inverter with bottom cover removed, showing access to wiring terminals.
Figure 4: Removing Bottom Cover for Wiring Access

Mounting the Unit

Consider the following points before selecting where to install:

  1. Do not mount the inverter on flammable construction materials.
  2. Mount on a solid surface.
  3. Install this inverter at eye level in order to allow the LCD display to be read at all times.
  4. The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
  5. The recommended installation position is to be adhered to the wall vertically.
  6. Be sure to keep other objects and surfaces as shown in the right diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.

IMPORTANT: Suitable for mounting on concrete or other non-combustible surface only.

Mounting dimensions and clearances for the inverter, showing 20cm clearance on sides and 50cm on top and bottom.
Figure 5: Recommended Mounting Clearances

Install the unit by screwing two screws. It's recommended to use M4 or M5 screws.

Battery Connection

CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to typical amperage in the table below as required fuse or breaker size.

WARNING! All wiring must be performed by qualified personnel. It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable.

Model Maximum Amperage Battery Capacity Wire Size Cable mm2 Terminal Size (L) Terminal Size (W) Terminal Size (D) Torque Value
4.2KVA 175A 200AH 1AWG 50 37 15.3 6.4 4~6 Nm
6.2KVA 130A 200AH 2AWG 35 37 15.3 6.4 4~6 Nm

Please follow below steps to implement battery connection:

  1. Make positive and negative cables based on recommended terminal size.
  2. Connect all battery packs as units requires. It's suggested to use recommended battery capacity.
  3. Insert battery cable flatly into battery connector of inverter and make sure the bolts are tightened with torque of 4~6Nm. Make sure polarity at both the battery and the inverter/charger is correctly connected and battery cables are tightly screwed to the battery connector.
Diagram showing proper battery cable connection to the inverter terminal.
Figure 6: Battery Cable Connection

AC Input/Output Connection

CAUTION: Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 50A.

CAUTION: There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by qualified personnel. It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.

Suggested Cable Requirement for AC Wires:

Model Gauge Torque Value
4.2KVA 10AWG 1.4~1.6Nm
6.2KVA 10AWG 1.4~1.6Nm

Please follow below steps to implement AC input/output connection:

  1. Before making AC input/output connection, be sure to open DC protector or disconnector first.
  2. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3mm.
  3. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure to connect PE protective conductor (yellow-green) first.
    • Ground (yellow-green)
    • L-LINE (brown or black)
    • N-Neutral (blue)
Diagram showing AC input/output wiring connections to the inverter terminal blocks.
Figure 7: AC Input/Output Wiring

WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.

  1. Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws. Be sure to connect PE protective conductor (yellow-green) first.
    • Ground (yellow-green)
    • L-LINE (brown or black)
    • N-Neutral (blue)
  2. Make sure the wires are securely connected.

CAUTION: Important Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are worked in parallel operation.

CAUTION: Appliances such as air conditioners require at least 2~3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check the manufacturer of the air conditioner if it's equipped with a time-delay function before installation. Otherwise, this inverter/charger will trigger an overload fault and cut off output to protect your appliance, but sometimes it still causes internal damage to the air conditioner.

PV Connection

CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.

WARNING! All wiring must be performed by qualified personnel. It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.

PV Module Wire Connection:

Model Typical Amperage Cable Size Torque
4.2KVA 27A 10 AWG 1.4~1.6 Nm
6.2KVA 27A 10 AWG 1.4~1.6 Nm

Please follow below steps to implement PV module connection:

  1. Remove insulation sleeve 6 mm for positive and negative conductors.
  2. Check correct polarity of connection cable from PV modules and PV input connectors. Then, connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.
Diagram showing PV module wire connection steps, including cable preparation and connection to the inverter's PV input terminals.
Figure 8: PV Module Wire Connection
  1. Make sure the wires are securely connected.

PV Module Selection:

When selecting proper PV modules, please be sure to consider below parameters:

  1. Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
  2. Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.

Solar Charging Mode Specifications:

INVERTER MODEL 4.2KVA / 6.2KVA
Max. PV Array Open Circuit Voltage 500VDC
PV Array MPPT Voltage Range 60VDC~500VDC
Max. PV INPUT CURRENT 27A

Take the 450Wp and 550Wp PV module as an example. After considering above two parameters, the recommended module configurations are listed in the table below.

Solar Panel Spec. (reference) SOLAR INPUT Q'ty of panels Total input power Inverter Model
450Wp
-Vmp: 34.67Vdc
-Imp: 13.82A
-Voc: 41.25Vdc
-Isc: 12.98A
3 pcs in serial 3 pcs 1,350 W 4.2KVA-6.2KVA
4 pcs in serial 4 pcs 1,800 W
5 pcs in serial 5 pcs 2,250 W
6 pcs in serial 6 pcs 2,700 W
7 pcs in serial 7 pcs 3,150 W
8 pcs in serial 8 pcs 3,600 W
9 pcs in serial 9 pcs 4,050 W
10 pcs in serial 10 pcs 4,500 W
11 pcs in serial 11 pcs 4,950 W
12 pcs in serial 12PCS 5,400W
550Wp
-Vmp: 42.48Vdc
-Imp: 12.95A
-Voc: 50.32Vdc
-Isc: 13.70A
3 pcs in serial 3 pcs 1,650 W 4.2KVA-6.2KVA
4 pcs in serial 4 pcs 2,200 W
5 pcs in serial 5 pcs 2,750 W
6 pcs in serial 6 pcs 3,300 W
7 pcs in serial 7 pcs 3,850 W
8 pcs in serial 8 pcs 4,400 W
9 pcs in serial 9 pcs 4,950 W
4 pieces in serial and 2 sets in parallel 8 pcs 4,400 W
5 pieces in serial and 2 sets in parallel 10 pcs 5,500 W
6 pieces in serial and 2 sets in parallel 12 pcs 6,600 W

Final Assembly

After connecting all wirings, please put the bottom cover back by screwing two screws.

Operation

Power ON/OFF

Once the unit has been properly installed and the batteries are connected well, simply press the On/Off switch (located on the side of the case) to turn on the unit.

Diagram showing the location of the Power ON/OFF switch on the side of the inverter.
Figure 9: Power ON/OFF Switch Location

Operation and Display Panel

The operation and display panel, shown below, is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.

Diagram of the inverter's front panel, labeling the LCD display, function buttons, and RGB indicator.
Figure 10: Operation and Display Panel

RGB Indicator Messages:

RGB Indicator Status Messages
Inverter mode (Green) Solid On Output is powered by battery or PV in battery mode. Battery is fully charged or isn't charged.
Flashing Battery is charging with 2s-on and 1s-off.
AC mode (Blue) Solid On Output is powered by AC or PV in AC mode. Battery is fully charged or isn't charged.
Flashing Battery is charging with 2s-on and 1s-off.
Standby mode (Cyan) Solid On Battery is fully charged or isn't charged.
Flashing Battery is charging with 2s-on and 1s-off.
Fault mode (Red) Solid On Fault occurs in the inverter.
Bypass mode (Purple) Solid On Working in AC mode without charging.
Charging mode (Yellow) Solid On Battery is fully charged, when switch is off.
Flashing Battery is charging, when switch is off.

Function Keys:

Function Key Description
ESC To exit setting mode
UP To go to previous selection
DOWN To go to next selection
ENTER To confirm the selection in setting mode or enter setting mode

LCD Display Description

The LCD display information will be switched in turns by pressing keys. All information could be shown in areas 1/2/3/4/5 of the LCD.

LCD display showing various parameters like PV data, battery data, AC output data, AC input data, and setting program code/Eco/buzzer/error/warning.
Figure 11: LCD Display with Data Areas

LCD Display Explanation:

  • Area 1: Shows PV data, such as PV voltage/current/power.
  • Area 2: Shows battery data, such as battery voltage/current/power/SOC.
  • Area 3: Shows AC-output data, such as output voltage/current/power/percentage/frequency.
  • Area 4: Shows AC-input data, such as input voltage/current/power/percentage/frequency.
  • Area 5: Shows setting program code/Eco/buzzer/error/warning.

LCD Data Polling Display Mode:

  • Simultaneously polling data: Press "UP" or "DOWN" button to show all data from area-1 to area-4 simultaneously, and all data will be updated with pressing. Press the ESC key to return to the initial data.
  • Independent polling data: Data of area 1-4 can be polled and displayed independently as follows:
    1. Press "Enter" key, the circle icon of area 1 will be flashing. Press "UP" or "DOWN" to display data of area 1.
    2. Continue to press "Enter" key, the circle icon of area 2 will be flashing. Press "UP" or "DOWN" to display data of area 2.
    3. Continue to press "Enter" key, the circle icon of area 3 will be flashing. Press "UP" or "DOWN" to display data of area 3.
    4. Continue to press "Enter" key, the circle icon of area 4 will be flashing. Press "UP" or "DOWN" to display data of area 4.
    5. Continue to press "Enter" key, the circle icon of area 1 will be flashing, it would come back to area 1.

LCD Setting

After pressing and holding the "Enter" key for 3 seconds, the unit will enter setting mode. Press "UP" or "DOWN" button to select setting programs. And then, press "ENTER" button to confirm the selection or ESC button to exit. When the unit enters setting mode, the LCD display will show:

  • Area 5: Shows setting program code.
  • Area 1: Shows setting minimum value, if the setting program has a minimum value.
  • Area 4: Shows setting maximum value, if the setting program has a maximum value.
  • Area 2: Shows setting program item.
  • Area 3: Shows setting current value which could be set.

Setting Programs:

Remark: Max[A,B] takes the larger value of both A and B and Min[A,B] takes the smaller value of both A and B.

Program Description Selectable Option
01 Output source priority: To configure load power source priority Utility first (default): Utility will provide power to the loads as first priority. Solar and battery energy will provide power to the loads only when utility power is not available.
Solar first: Solar energy provides power to the loads as priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power the loads at the same time. Utility provides power to the loads only when any one condition happens: Solar energy is not available, Battery voltage drops to either low-level warning voltage or the setting point in program 12.
SBU priority: Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power to the loads at the same time. Utility provides power to the loads only when battery voltage drops to either low-level warning voltage or the setting point in program 12.
SUB priority: Solar energy is charged first and then power to the loads. If solar energy is not sufficient to power all connected loads, Utility energy will supply power to the loads at the same time.
SUF priority: If solar energy is sufficient to all connected loads and charge battery, the solar energy could feedback to the grid. If solar energy is not sufficient to power all connected loads, utility energy will supply power to the loads at the same time.
02 Maximum charging current: To configure total charging current for solar and utility chargers. (Max. charging current = utility charging current + solar charging current) 60A (default): If selected, acceptable charging current range will be from Max. AC charging current to Max. charging current of SPEC, but it shouldn't be less than the AC charging current (program 11).
03 AC input voltage range Appliances (default): If selected, acceptable AC input voltage range will be within 90-280VAC.
UPS: If selected, acceptable AC input voltage range will be within 170-280VAC.
Generator: If selected, acceptable AC input voltage range will be within 170-280VAC and compatible with generators. Note: Because generators are unstable, maybe the output of inverter will be unstable too.
05 Battery type AGM (default): Lead acid battery
Flooded: Flooded battery
User-Defined: If "User-Defined" is selected, battery charge voltage and low DC cut-off voltage can be set up in program 26, 27 and 29.
LI2: Support PYLON US2000 Protocol 3.5 Version
06 Auto restart when overload occurs Restart enable (default): Restarts automatically.
07 Auto restart when over temperature occurs Restart enable (default): Restarts automatically.
08 Output voltage 230V (default): Available settings are 220V, 230V, 240V.
09 Output frequency 50Hz (default): Available settings are 50Hz and 60Hz.
10 Auto bypass: When selecting "auto", if the mains power is normal, it will automatically bypass, even if the switch is off. Manual (default)
Auto
11 Maximum utility charging current 30A (default): If selected, acceptable charging current range will be within 5-Max. AC charging current of SPEC.
12 Setting voltage point back to utility source when selecting "SBU priority" or "Solar first" in program 01. 24V models: Default 23.0V (LIB: 26.0V). Range: Max[22V, program31+0.1V]~Min[program13-0.1V,28.6V]. For Lix, default 20%, range Max[5%, program31+1%]~Min[program13-1%,96%].
48V models: Default 46.0V (LIB: 52.0V). Range: Max[44V, program31+0.1V]~Min[program13-0.1V,57.2V]. For Lix, default 20%, range Max[5%, program31+1%]~Min[program13-1%,96%].
13 Setting voltage point back to battery mode when selecting "SBU priority" or "Solar first" in program 01. 24V models: Default battery fully charged (LIB: battery fully charged). Range: Max[24V, program12+0.1V]~Min[program26-0.5V or Full]. For Lix, default 30%, range Max[10%, program12+1%]~100%.
48V models: Default battery fully charged (LIB: battery fully charged). Range: Max[48V, program12+0.1V]~Min[program26-0.5V or Full]. For Lix, default 30%, range Max[10%, program12+1%]~100%.
16 Charger source priority: To configure charger source priority Solar first: Solar energy will charge battery as first priority. Utility will charge battery only when solar energy is not available.
Solar and Utility (default): Solar energy and utility will charge battery at the same time.
Only Solar: Solar energy will be the only charger source no matter utility is available or not.
18 Buzzer mode Mode 1: Buzzer mute.
Mode 2: The buzzer sounds when the input source changes or there is a specific warning or fault.
Mode 3: The buzzer sounds when there is a specific warning or fault.
Mode 4 (default): The buzzer sounds when there is a fault.
19 Auto return to default display screen Return to default display screen (default): If selected, no matter how users switch display screen, it will automatically return to default display screen after no button is pressed for 1 minute.
Stay at latest screen: If selected, the display screen will stay at the latest screen user finally switches.
20 Backlight control Backlight off (default)
Backlight on
23 Overload bypass: When enabled, the unit will transfer to line mode if overload occurs in battery mode. Bypass disable
Bypass enable (default)
25 Modbus ID Setting Modbus ID Setting Range: 001 (default)~247
26 Bulk charging voltage (C.V voltage) If self-defined or "LIB" is selected in program 5, this program can be setup.
24V models: Default 28.2V (LIB: 28.2V). Range: program27 to 31V (LIB: program27 to 29V).
48V models: Default 56.4V (LIB: 56.4V). Range: program27 to 62V (LIB: program27 to 58V).
27 Floating charging voltage If self-defined or "LIB" is selected in program 5, this program can be setup.
24V models: Default 27.0V (LIB: 28.2V). Range: 24.0V to program 26.
48V models: Default 54.0V (LIB: 56.4V). Range: 48.0V to program 26.
29 Setting cut off voltage point or SOC percentage percentage on the second output (OP2) If self-defined or "LIB" is selected in program 5, this program can be setup.
24V models: Default 21.0V (LIB: 25.0V). Range: 20V~Min[program 31,27V]. For Lix, default 10%, range 0% to SOC of program 31.
48V models: Default 42.0V (LIB: 50.0V). Range: 40V~Min[program 31,54V]. For Lix, default 10%, range 0% to SOC of program 31.
31 Setting cut off voltage point or SOC percentage percentage on the Main output (OP1) If self-defined or "LIB" is selected in program 5, this program can be set up, low DC cut-off voltage will be fixed to setting value no matter what percentage of load is connected.
24V models: Default 22.0V (LIB: 25.9V). Range: program29 to Min [program12 - 0.1V, 27V]. For Lix, default 15%, range SOC of program29 to Min[95%, program12 - 1%].
48V models: Default 44.0V (LIB: 51.9V). Range: program29 to Min [program12 - 0.1V, 54V]. For Lix, default 15%, range SOC of program29 to Min[95%, program12 - 1%].
32 Bulk charging time (C.V stage) Automatically (Default): Inverter will judge this charging time automatically.
5 min - 900 min: Setting range is from 5 min to 900 min. Increment of each click is 5 min.
33 Battery equalization Battery equalization disable (default)
34 Battery equalization voltage 24V models: Default 29.2V. Range: floating voltage ~ 31V.
48V models: If program 5 is not LIB, default 58.4V. Range: floating voltage ~ 62V.
35 Battery equalized time 60min (default): Setting range is from 0 min to 900min.
36 Battery equalized timeout 120min (default): Setting range is from 0min to 900 min.
37 Equalization interval 30days (default): Setting range is from 1 to 90 days.
39 Equalization activated immediately Enable: If equalization function is enabled in program 33, this program can be set up. If "Enable" is selected in this program, it's to activate battery equalization immediately and LCD main page will show "EQ".
Disable (default): If "Disable" is selected, it will cancel equalization function until next activated equalization time arrives based on program 37 setting. At this time, "EQ" will not be shown in LCD main page.
41 Automatic activation for lithium battery Disable (default): Disable automatic activation.
Auto: When Program05 is selected as "User-Defined" or "LIB" or "LIx", lithium battery and when the battery is not detected, the unit will activate automatically the lithium battery at a time. If you want to activate automatically the lithium battery, you must restart the unit.
42 Manual activation for lithium battery Default: Disable activation.
Activation: When Program05 is selected "User-Defined" or "LIB" or "LIx" as lithium battery, when the battery is not detected, if you want to activate the lithium battery at a time, you could select it.
43 OP2 Output Enable Enable (default): OP2 output is allowed.
Disable: OP2 output is forbidden.
46 Maximum discharge current protection Default OFF: Disable current discharge current protection function. Only available in Single model. The setting range is from 20A to 500A. When utility is available, it turns to utility model and battery discharge stops after the battery discharge current exceeded the setting value. When utility is unavailable, warning occurs and battery discharge lasts after the battery discharge current exceeded the setting value.
47 Setting the OP2 overload warning point Set the OP2 overload warning point. If the set value is exceeded, 22 warning will be displayed. Setting range is from 10% to 100% and the default setting is 50%.
49 RGB mode - Checking RGB Indicator table Mode 1 (Default): RGB LED is working normally.
Mode 2: RGB LED is working with only the unit in fault mode.
Mode 3: RGB LED is always OFF.
Mode 4: RGB LED shows as mode 1 and whether battery is fully charged or not, RGB LED won't be flashing at any time.
Mode 5: RGB LED shows as mode 1 and whether battery is fully charged or not, RGB LED will be flashing.
50 Lithium battery activation time When lithium battery activation function is available, the activation time could be set, the setting range is 6s~300s, the default time is 6s.

Battery Equalization

Equalization function is added into the charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize battery periodically.

How to Apply Equalization Function:

You must enable battery equalization function in monitoring LCD setting program 33 first. Then, you may apply this function in device by either one of following methods:

  1. Setting equalization interval in program 37.
  2. Active equalization immediately in program 39.

When to Equalize:

In float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter Equalize stage.

Battery equalization voltage and float voltage diagram showing bulk, absorption, float, and equalize stages.
Figure 12: Battery Equalization Stages

Equalize Charging Time and Timeout:

In Equalize stage, the controller will supply power to charge battery as much as possible until battery voltage raises to battery equalization voltage. Then, constant-voltage regulation is applied to maintain battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until setting battery equalized time is arrived.

However, in Equalize stage, when battery equalized time is expired and battery voltage doesn't rise to battery equalization voltage point, the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage. If battery voltage is still lower than battery equalization voltage when battery equalized timeout setting is over, the charge controller will stop equalization and return to float stage.

Setting for Lithium Battery

If choosing a lithium battery for the inverter, you are allowed to use only the lithium battery which we have configured. There are two connectors on the lithium battery: the RS485 port of BMS and the power cable.

Lithium Battery Connection Steps:

  1. Assemble battery terminal based on recommended battery cable and terminal size (same as Lead acid, see section Lead-acid Battery connection for details).
  2. Connect the end of the RS485 port of the battery to the BMS (RS485) communication port of the inverter.
Diagram showing the connection of a lithium battery to the inverter via the RS485 communication port.
Figure 13: Lithium Battery Connection (Fig 1 from manual)

Lithium Battery Communication and Setting:

If choosing a lithium battery, make sure to connect the BMS communication cable between the battery and the inverter. This communication cable delivers information and signals between the lithium battery and the inverter. This information is listed below:

  • Re-configure charging voltage, charging current, and battery discharge cut-off voltage according to the lithium battery parameters.
  • Have the inverter start or stop charging according to the status of the lithium battery.

Connect the end of RS485 of battery to RS485 communication port of inverter:

Make sure the lithium battery RS485 port connects to the inverter is Pin to Pin, the inverter RS485 port pin assignment shown as below:

Pin Number RS485 Port
PIN1 RS485-B
PIN2 RS485-A
PIN7 RS485-A
PIN8 RS485-B

LCD Setting for Lithium Battery:

After connecting, you need to finish and confirm some settings as follows:

  1. Select program 05 as lithium battery type.

LCD Display for Lithium Battery:

If communication between the inverter and battery is successful, there is some information getting from BMS and showing on the LCD as follows:

  1. Communication successful icon: Li will be flashing.
  2. Max lithium battery charging voltage.
  3. Max lithium battery charging current.
  4. Lithium battery discharging is forbidden: Li will flash once every 1 second.
  5. Lithium battery charging is forbidden: Li will flash once every 2 seconds.
  6. Lithium battery SOC (%).

Setting for PYLON US2000 Lithium Battery:

  1. PYLONTECH US2000 lithium battery setting:

    Dip Switch: There are 4 Dip Switches that set different baud rate and battery group address. If switch position is turned to the "OFF" position, it means "0". If switch position is turned to the "ON" position, it means "1".

    • Dip 1 is "ON" to represent the baud rate 9600.
    • Dip 2, 3 and 4 are reserved for battery group address.
    • Dip switch 2, 3 and 4 on master battery (first battery) are to set up or change the group address.

    NOTE: "1" is upper position and "0" is bottom position.

  2. Process of install:
    1. Step 1. Use the RS485 cable to connect inverter and Lithium battery as Fig 1 (Figure 13).
    2. Step 2. Switch on Lithium battery.
    3. Step 3. Press more than three seconds to start Lithium battery, power output ready.
    4. Step 4. Turn on the inverter.
    5. Step 5. Be sure to select battery type as "Li2" in LCD program 5.

    If communication between the inverter and battery is successful, the battery icon LI on the LCD display will light.

Setting for Lithium Battery without Communication:

This suggestion is used for lithium battery application and avoids lithium battery BMS protection without communication. Please finish the setting as follows:

  • A. Recommended method 1: Set battery type as "LIB" in program 05.
  • B. Recommended method 2: Setting as follows:
    1. Before starting setting, you must get the battery BMS specification: Max charging voltage, Max charging current, Discharging protection voltage.
    2. Set battery type as "LIB" in program 05.
    3. Set C.V voltage as Max charging voltage of BMS-0.5V in program 26.
    4. Set floating charging voltage as C.V voltage in program 27.
    5. Set Low DC cut-off voltage discharging protection voltage in program 29.
    6. Set Max charging current in program 02 which must be less than the Max charging current of BMS.
    7. Setting voltage point back to utility source when selecting "SBU priority" in program 12.

    The setting value must be ≥ Low DC cut-off voltage + 2V, or else the inverter will have a warning as battery voltage low.

Remark:

  1. You'd better to finish setting without turning on the inverter (just let the LCD show, no output).
  2. When you finish setting, please restart the inverter.

Troubleshooting

Fault Reference Code

Fault Code Fault Event
01Over temperature of inverter module
02Over temperature of DCDC module
03Battery voltage is too high
04Over temperature of PV module
05Output short circuited.
06Output voltage is too high.
07Overload time out
08Bus voltage is too high
09Bus soft start failed
10PV over current
11PV over voltage
12DCDC over current
13Over current or surge
14Bus voltage is too low
15Inverter failed (Self-checking)
18Op current offset is too high
19Inverter current offset is too high
20DC/DC current offset is too high
21PV current offset is too high
22Output voltage is too low
23Inverter negative power
24Op2 current offset is too high

Warning Indicator

Warning Code Warning Event Audible Alarm
02Temperature is too HighBeep three times every second
04Low batteryBeep once every second
07OverloadBeep once every 0.5 second
10Output power deratingBeep twice every 3 seconds
14Fan blockedNone
15PV energy is lowBeep twice every 3 seconds
19Lithium Battery communication is failedBeep once every 0.5 second
21Lithium Battery over currentNone
22The load exceeds the set value of program program47None
E9Battery equalizationNone
b8Battery is not connectedNone

Troubleshooting Table

Problem LCD/LED/Buzzer Explanation / Possible cause What to do
Unit shuts Down automatically during startup process. LCD/LEDs and buzzer will be active for 3 seconds and then complete off. The battery voltage is too low 1. Re-charge battery.
2. Replace battery.
No response after power on. No indication. 1. The battery voltage is far too low.
2. Battery polarity is connected reversed.
1. Check if batteries and the wiring are connected well.
2. Re-charge battery.
3. Replace battery.
Mains exist but the unit works in battery mode. Input voltage is displayed as 0 on the LCD and green LED is flashing. Input protector is tripped Check if AC breaker is tripped and AC wiring is connected well.
Green LED is flashing. Insufficient quality of AC power. (Shore or Generator) Check if AC wires are too thin and/or too long. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS / Appliance)
When the unit is turned on, internal relay is switched on and off repeatedly. Green LED is flashing. Set "Solar First" as the priority of output source. Change output source priority to Utility first.
LCD display and LEDs are flashing Battery is disconnected. Check if battery wires are connected well.
Fault code 07 Overload error. The inverter is overload 110% and time is up. Reduce the connected load by switching off some equipment.
Fault code 05 Output short circuited. Check if wiring is connected well and remove abnormal load.
Fault code 02 Internal temperature of inverter component is over 100°C. Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.
Fault code 03 Battery is over-charged. Return to repair center.
Fault code 03 The battery voltage is too high. Check if spec and quantity of batteries are meet requirements.
Buzzer beeps continuously and red LED is on. Fault code 06/22 Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) 1. Reduce the connected load.
2. Return to repair center.
Fault code 08/09/15 Internal components failed. Return to repair center.
Fault code 13 Over current or surge. Restart the unit, if the error happens again, please return to repair center.
Fault code 14 Bus voltage is too low. If the wires is connected well, please return to repair center.
Another fault code If the wires is connected well, please return to repair center.

Specifications

Table 1 Line Mode Specifications

INVERTER MODEL 4.2KVA 6.2KVA
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage170Vac±7V (UPS)
90Vac±7V (Appliances)
Low Loss Return Voltage180Vac±7V (UPS);
100Vac±7V (Appliances)
High Loss Voltage280Vac±7V
High Loss Return Voltage270Vac±7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionBattery mode: Electronic Circuits
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)
Output power derating: When AC input voltage drops to 95V or 170V depending on models, the output power will be derated.

Output Power

Rated Power 50% Power

Output power derating curve showing power reduction at lower AC input voltages.
Figure 14: Output Power Derating

Table 2 Inverter Mode Specifications

INVERTER MODEL 4.2KVA 6.2KVA
Rated Output Power4.2KVA
4.2KW
6.2KVA
6.2KW
Dual output functionYesYes
Max.main output power4.2KVA
4.2KW
6.2KVA
6.2KW
Max.second output power4.2KVA
4.2KW
6.2KVA
6.2KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac±5%
Output Frequency50Hz or 60Hz
Peak Efficiency94%
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage24Vdc48Vdc
Cold Start Voltage23.0Vdc46.0Vdc
Low DC Warning Voltage Just for AGM and Flooded @ load < 20%22.0Vdc
21.4Vdc
20.2Vdc
44.0Vdc
42.8Vdc
40.4Vdc
Low DC Warning Return Voltage Just for AGM and Flooded @ load < 20%23.0Vdc
22.4Vdc
21.2Vdc
46.0Vdc
44.8Vdc
42.4Vdc
Low DC Cut-off Voltage Just for AGM and Flooded @ load < 20%21.0Vdc
20.4Vdc
19.2Vdc
42.0Vdc
40.8Vdc
38.4Vdc

Table 3 Charge Mode Specifications

Utility Charging Mode 4.2KVA 6.2KVA
Max Charging Current (PV+AC) (@ VI/P=230Vac)120Amp120Amp
Max Charging Current (AC)(@ VI/P=230Vac)120Amp120Amp
Bulk Charging Voltage (Flooded Battery)29.2Vdc58.4Vdc
Bulk Charging Voltage (AGM / Gel Battery)28.2Vdc56.4Vdc
Floating Charging Voltage27Vdc54Vdc
Overcharge Protection32Vdc63Vdc
Battery reverse connection protectionNoNo
Charging Algorithm3-Step
Charging Curve
Charging curve diagram showing battery voltage and charging current over time through bulk, absorption, and maintenance (floating) stages.
Figure 15: Charging Curve

Solar Input Specifications

INVERTER MODEL 4.2KVA 6.2KVA
Rated Power6200W9000W
Max. PV Array Open Circuit Voltage500Vdc
PV Array MPPT Voltage Range60Vdc~500Vdc
Max. Input Current27A
Max. Charging Current(PV)120A

Table 4 General Specifications

INVERTER MODEL 4.2KVA 6.2KVA
Operating Temperature Range-10°C to 55°C
Storage temperature-15°C ~ 60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm368x328x120
Net Weight, kg7.08.0

User Tips

  • Noise Consideration: The inverter can be noisy during operation due to cooling fans. If noise is a concern, consider installing the unit in a location away from living or sleeping areas.
  • Battery Operation: Some models of this inverter may not operate without a connected battery. Ensure you have a compatible battery connected for full functionality.
  • Power Button Functionality: The physical power button on the unit primarily controls the load output. If the inverter is connected to any power source (solar, utility), it may remain active and its cooling fans may run, even if the load output is turned off. Plan your setup accordingly if you require a complete shutdown.
  • Lithium Battery Settings: When using lithium batteries, it is crucial to correctly configure the battery type and related charging/discharging parameters (programs 05, 26, 27, 29) to ensure optimal performance and prevent damage. Refer to the 'Setting for Lithium Battery' section for detailed instructions.
  • Voltage Accuracy: Some users have noted slight discrepancies in voltmeter readings. While the inverter generally performs well, it's advisable to cross-reference with external measurement tools if precise voltage monitoring is critical for your setup.

Warranty and Support

For detailed warranty information, service, and technical support, please refer to the official product documentation or contact Aninerel customer service. A comprehensive user manual in PDF format is available for download: View User Manual (PDF).

© 2024 Aninerel. All rights reserved.