About This Manual
This manual describes the assembly, installation, operation, and troubleshooting of the Aninerel Hybrid Solar Inverter/Charger. Please read this manual carefully before installations and operations. Keep this manual for future reference.
This manual provides safety and installation guidelines as well as information on tools and wiring.
Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION --To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION - Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to the Installation section of this manual for details.
- Fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
Product Overview
The Aninerel Hybrid Solar Inverter/Charger is designed to efficiently manage solar power, utility grid power, and battery power for various applications. It features a user-friendly interface with an LCD display and function buttons for easy operation and monitoring.
Component Identification
- LCD display
- Function buttons
- RGB indicator
- Grounding
- RS232 communication port
- RS485 communication port
- AC input
- Main out
- Second out
- Battery input
- PV input
- Power on/off switch
Product Features
- Dual output for smart load management
- Lithium battery activation function by PV or Utility
- Colored LCD with RGB lights
- Compatible work with LiFePO4 battery via RS485
- PV input 60Vdc~500Vdc Max
- Built-in MPPT 120A
- Capable to work without battery
- Detachable dust cover for harsh environment
- WiFi remote monitoring
- Support multiple output priority: UTL, SOL, SBU, SUB
- EQ function to optimize battery performance and extend lifecycle
- Lithium battery activation function by PV or Utility
- Compatible work with LiFePO4 battery via RS485
- Power factor 1.0
- PV input Voltage 30Vdc~160Vdc
- Built-in MPPT 60A
- Detachable dust cover for harsh environment
- WiFi remote monitoring optional
- Support multiple output priority: UTL, SOL, SBU
Installation
Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items:
- The unit x 1
- User manual x 1
Preparation
Before connecting all wirings, please take off the bottom cover by removing two screws as shown below.
Mounting the Unit
Consider the following points before selecting where to install:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level in order to allow the LCD display to be read at all times.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Be sure to keep other objects and surfaces as shown in the right diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.
IMPORTANT: Suitable for mounting on concrete or other non-combustible surface only.
Install the unit by screwing two screws. It's recommended to use M4 or M5 screws.
Battery Connection
CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to typical amperage in the table below as required fuse or breaker size.
WARNING! All wiring must be performed by qualified personnel. It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable.
Recommended Battery Cable & Terminal Size:
| Model | Maximum Amperage | Battery Capacity | Wire Size | Cable mm2 | Terminal Size (L) | Terminal Size (W) | Terminal Size (D) | Torque Value |
|---|---|---|---|---|---|---|---|---|
| 4.2KVA | 175A | 200AH | 1AWG | 50 | 37 | 15.3 | 6.4 | 4~6 Nm |
| 6.2KVA | 130A | 200AH | 2AWG | 35 | 37 | 15.3 | 6.4 | 4~6 Nm |
Please follow below steps to implement battery connection:
- Make positive and negative cables based on recommended terminal size.
- Connect all battery packs as units requires. It's suggested to use recommended battery capacity.
- Insert battery cable flatly into battery connector of inverter and make sure the bolts are tightened with torque of 4~6Nm. Make sure polarity at both the battery and the inverter/charger is correctly connected and battery cables are tightly screwed to the battery connector.
AC Input/Output Connection
CAUTION: Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 50A.
CAUTION: There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by qualified personnel. It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested Cable Requirement for AC Wires:
| Model | Gauge | Torque Value |
|---|---|---|
| 4.2KVA | 10AWG | 1.4~1.6Nm |
| 6.2KVA | 10AWG | 1.4~1.6Nm |
Please follow below steps to implement AC input/output connection:
- Before making AC input/output connection, be sure to open DC protector or disconnector first.
- Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3mm.
- Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure to connect PE protective conductor (yellow-green) first.
- Ground (yellow-green)
- L-LINE (brown or black)
- N-Neutral (blue)
WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
- Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws. Be sure to connect PE protective conductor (yellow-green) first.
- Ground (yellow-green)
- L-LINE (brown or black)
- N-Neutral (blue)
- Make sure the wires are securely connected.
CAUTION: Important Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are worked in parallel operation.
CAUTION: Appliances such as air conditioners require at least 2~3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check the manufacturer of the air conditioner if it's equipped with a time-delay function before installation. Otherwise, this inverter/charger will trigger an overload fault and cut off output to protect your appliance, but sometimes it still causes internal damage to the air conditioner.
PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.
WARNING! All wiring must be performed by qualified personnel. It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.
PV Module Wire Connection:
| Model | Typical Amperage | Cable Size | Torque |
|---|---|---|---|
| 4.2KVA | 27A | 10 AWG | 1.4~1.6 Nm |
| 6.2KVA | 27A | 10 AWG | 1.4~1.6 Nm |
Please follow below steps to implement PV module connection:
- Remove insulation sleeve 6 mm for positive and negative conductors.
- Check correct polarity of connection cable from PV modules and PV input connectors. Then, connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.
- Make sure the wires are securely connected.
PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:
- Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
Solar Charging Mode Specifications:
| INVERTER MODEL | 4.2KVA / 6.2KVA | |
|---|---|---|
| Max. PV Array Open Circuit Voltage | 500VDC | |
| PV Array MPPT Voltage Range | 60VDC~500VDC | |
| Max. PV INPUT CURRENT | 27A |
Take the 450Wp and 550Wp PV module as an example. After considering above two parameters, the recommended module configurations are listed in the table below.
Recommended PV Module Configurations:
| Solar Panel Spec. (reference) | SOLAR INPUT | Q'ty of panels | Total input power | Inverter Model |
|---|---|---|---|---|
| 450Wp -Vmp: 34.67Vdc -Imp: 13.82A -Voc: 41.25Vdc -Isc: 12.98A |
3 pcs in serial | 3 pcs | 1,350 W | 4.2KVA-6.2KVA |
| 4 pcs in serial | 4 pcs | 1,800 W | ||
| 5 pcs in serial | 5 pcs | 2,250 W | ||
| 6 pcs in serial | 6 pcs | 2,700 W | ||
| 7 pcs in serial | 7 pcs | 3,150 W | ||
| 8 pcs in serial | 8 pcs | 3,600 W | ||
| 9 pcs in serial | 9 pcs | 4,050 W | ||
| 10 pcs in serial | 10 pcs | 4,500 W | ||
| 11 pcs in serial | 11 pcs | 4,950 W | ||
| 12 pcs in serial | 12PCS | 5,400W | ||
| 550Wp -Vmp: 42.48Vdc -Imp: 12.95A -Voc: 50.32Vdc -Isc: 13.70A |
3 pcs in serial | 3 pcs | 1,650 W | 4.2KVA-6.2KVA |
| 4 pcs in serial | 4 pcs | 2,200 W | ||
| 5 pcs in serial | 5 pcs | 2,750 W | ||
| 6 pcs in serial | 6 pcs | 3,300 W | ||
| 7 pcs in serial | 7 pcs | 3,850 W | ||
| 8 pcs in serial | 8 pcs | 4,400 W | ||
| 9 pcs in serial | 9 pcs | 4,950 W | ||
| 4 pieces in serial and 2 sets in parallel | 8 pcs | 4,400 W | ||
| 5 pieces in serial and 2 sets in parallel | 10 pcs | 5,500 W | ||
| 6 pieces in serial and 2 sets in parallel | 12 pcs | 6,600 W |
Final Assembly
After connecting all wirings, please put the bottom cover back by screwing two screws.
Operation
Power ON/OFF
Once the unit has been properly installed and the batteries are connected well, simply press the On/Off switch (located on the side of the case) to turn on the unit.
Operation and Display Panel
The operation and display panel, shown below, is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.
RGB Indicator Messages:
| RGB Indicator | Status | Messages |
|---|---|---|
| Inverter mode (Green) | Solid On | Output is powered by battery or PV in battery mode. Battery is fully charged or isn't charged. |
| Flashing | Battery is charging with 2s-on and 1s-off. | |
| AC mode (Blue) | Solid On | Output is powered by AC or PV in AC mode. Battery is fully charged or isn't charged. |
| Flashing | Battery is charging with 2s-on and 1s-off. | |
| Standby mode (Cyan) | Solid On | Battery is fully charged or isn't charged. |
| Flashing | Battery is charging with 2s-on and 1s-off. | |
| Fault mode (Red) | Solid On | Fault occurs in the inverter. |
| Bypass mode (Purple) | Solid On | Working in AC mode without charging. |
| Charging mode (Yellow) | Solid On | Battery is fully charged, when switch is off. |
| Flashing | Battery is charging, when switch is off. |
Function Keys:
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
LCD Display Description
The LCD display information will be switched in turns by pressing keys. All information could be shown in areas 1/2/3/4/5 of the LCD.
LCD Display Explanation:
- Area 1: Shows PV data, such as PV voltage/current/power.
- Area 2: Shows battery data, such as battery voltage/current/power/SOC.
- Area 3: Shows AC-output data, such as output voltage/current/power/percentage/frequency.
- Area 4: Shows AC-input data, such as input voltage/current/power/percentage/frequency.
- Area 5: Shows setting program code/Eco/buzzer/error/warning.
LCD Data Polling Display Mode:
- Simultaneously polling data: Press "UP" or "DOWN" button to show all data from area-1 to area-4 simultaneously, and all data will be updated with pressing. Press the ESC key to return to the initial data.
- Independent polling data: Data of area 1-4 can be polled and displayed independently as follows:
- Press "Enter" key, the circle icon of area 1 will be flashing. Press "UP" or "DOWN" to display data of area 1.
- Continue to press "Enter" key, the circle icon of area 2 will be flashing. Press "UP" or "DOWN" to display data of area 2.
- Continue to press "Enter" key, the circle icon of area 3 will be flashing. Press "UP" or "DOWN" to display data of area 3.
- Continue to press "Enter" key, the circle icon of area 4 will be flashing. Press "UP" or "DOWN" to display data of area 4.
- Continue to press "Enter" key, the circle icon of area 1 will be flashing, it would come back to area 1.
LCD Setting
After pressing and holding the "Enter" key for 3 seconds, the unit will enter setting mode. Press "UP" or "DOWN" button to select setting programs. And then, press "ENTER" button to confirm the selection or ESC button to exit. When the unit enters setting mode, the LCD display will show:
- Area 5: Shows setting program code.
- Area 1: Shows setting minimum value, if the setting program has a minimum value.
- Area 4: Shows setting maximum value, if the setting program has a maximum value.
- Area 2: Shows setting program item.
- Area 3: Shows setting current value which could be set.
Setting Programs:
Remark: Max[A,B] takes the larger value of both A and B and Min[A,B] takes the smaller value of both A and B.
| Program | Description | Selectable Option |
|---|---|---|
| 01 | Output source priority: To configure load power source priority | Utility first (default): Utility will provide power to the loads as first priority. Solar and battery energy will provide power to the loads only when utility power is not available. |
| Solar first: Solar energy provides power to the loads as priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power the loads at the same time. Utility provides power to the loads only when any one condition happens: Solar energy is not available, Battery voltage drops to either low-level warning voltage or the setting point in program 12. | ||
| SBU priority: Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power to the loads at the same time. Utility provides power to the loads only when battery voltage drops to either low-level warning voltage or the setting point in program 12. | ||
| SUB priority: Solar energy is charged first and then power to the loads. If solar energy is not sufficient to power all connected loads, Utility energy will supply power to the loads at the same time. | ||
| SUF priority: If solar energy is sufficient to all connected loads and charge battery, the solar energy could feedback to the grid. If solar energy is not sufficient to power all connected loads, utility energy will supply power to the loads at the same time. | ||
| 02 | Maximum charging current: To configure total charging current for solar and utility chargers. (Max. charging current = utility charging current + solar charging current) | 60A (default): If selected, acceptable charging current range will be from Max. AC charging current to Max. charging current of SPEC, but it shouldn't be less than the AC charging current (program 11). |
| 03 | AC input voltage range | Appliances (default): If selected, acceptable AC input voltage range will be within 90-280VAC. |
| UPS: If selected, acceptable AC input voltage range will be within 170-280VAC. | ||
| Generator: If selected, acceptable AC input voltage range will be within 170-280VAC and compatible with generators. Note: Because generators are unstable, maybe the output of inverter will be unstable too. | ||
| 05 | Battery type | AGM (default): Lead acid battery |
| Flooded: Flooded battery | ||
| User-Defined: If "User-Defined" is selected, battery charge voltage and low DC cut-off voltage can be set up in program 26, 27 and 29. | ||
| LI2: Support PYLON US2000 Protocol 3.5 Version | ||
| 06 | Auto restart when overload occurs | Restart enable (default): Restarts automatically. |
| 07 | Auto restart when over temperature occurs | Restart enable (default): Restarts automatically. |
| 08 | Output voltage | 230V (default): Available settings are 220V, 230V, 240V. |
| 09 | Output frequency | 50Hz (default): Available settings are 50Hz and 60Hz. |
| 10 | Auto bypass: When selecting "auto", if the mains power is normal, it will automatically bypass, even if the switch is off. | Manual (default) |
| Auto | ||
| 11 | Maximum utility charging current | 30A (default): If selected, acceptable charging current range will be within 5-Max. AC charging current of SPEC. |
| 12 | Setting voltage point back to utility source when selecting "SBU priority" or "Solar first" in program 01. | 24V models: Default 23.0V (LIB: 26.0V). Range: Max[22V, program31+0.1V]~Min[program13-0.1V,28.6V]. For Lix, default 20%, range Max[5%, program31+1%]~Min[program13-1%,96%]. 48V models: Default 46.0V (LIB: 52.0V). Range: Max[44V, program31+0.1V]~Min[program13-0.1V,57.2V]. For Lix, default 20%, range Max[5%, program31+1%]~Min[program13-1%,96%]. |
| 13 | Setting voltage point back to battery mode when selecting "SBU priority" or "Solar first" in program 01. | 24V models: Default battery fully charged (LIB: battery fully charged). Range: Max[24V, program12+0.1V]~Min[program26-0.5V or Full]. For Lix, default 30%, range Max[10%, program12+1%]~100%. 48V models: Default battery fully charged (LIB: battery fully charged). Range: Max[48V, program12+0.1V]~Min[program26-0.5V or Full]. For Lix, default 30%, range Max[10%, program12+1%]~100%. |
| 16 | Charger source priority: To configure charger source priority | Solar first: Solar energy will charge battery as first priority. Utility will charge battery only when solar energy is not available. |
| Solar and Utility (default): Solar energy and utility will charge battery at the same time. | ||
| Only Solar: Solar energy will be the only charger source no matter utility is available or not. | ||
| 18 | Buzzer mode | Mode 1: Buzzer mute. |
| Mode 2: The buzzer sounds when the input source changes or there is a specific warning or fault. | ||
| Mode 3: The buzzer sounds when there is a specific warning or fault. | ||
| Mode 4 (default): The buzzer sounds when there is a fault. | ||
| 19 | Auto return to default display screen | Return to default display screen (default): If selected, no matter how users switch display screen, it will automatically return to default display screen after no button is pressed for 1 minute. |
| Stay at latest screen: If selected, the display screen will stay at the latest screen user finally switches. | ||
| 20 | Backlight control | Backlight off (default) |
| Backlight on | ||
| 23 | Overload bypass: When enabled, the unit will transfer to line mode if overload occurs in battery mode. | Bypass disable |
| Bypass enable (default) | ||
| 25 | Modbus ID Setting | Modbus ID Setting Range: 001 (default)~247 |
| 26 | Bulk charging voltage (C.V voltage) | If self-defined or "LIB" is selected in program 5, this program can be setup. 24V models: Default 28.2V (LIB: 28.2V). Range: program27 to 31V (LIB: program27 to 29V). 48V models: Default 56.4V (LIB: 56.4V). Range: program27 to 62V (LIB: program27 to 58V). |
| 27 | Floating charging voltage | If self-defined or "LIB" is selected in program 5, this program can be setup. 24V models: Default 27.0V (LIB: 28.2V). Range: 24.0V to program 26. 48V models: Default 54.0V (LIB: 56.4V). Range: 48.0V to program 26. |
| 29 | Setting cut off voltage point or SOC percentage percentage on the second output (OP2) | If self-defined or "LIB" is selected in program 5, this program can be setup. 24V models: Default 21.0V (LIB: 25.0V). Range: 20V~Min[program 31,27V]. For Lix, default 10%, range 0% to SOC of program 31. 48V models: Default 42.0V (LIB: 50.0V). Range: 40V~Min[program 31,54V]. For Lix, default 10%, range 0% to SOC of program 31. |
| 31 | Setting cut off voltage point or SOC percentage percentage on the Main output (OP1) | If self-defined or "LIB" is selected in program 5, this program can be set up, low DC cut-off voltage will be fixed to setting value no matter what percentage of load is connected. 24V models: Default 22.0V (LIB: 25.9V). Range: program29 to Min [program12 - 0.1V, 27V]. For Lix, default 15%, range SOC of program29 to Min[95%, program12 - 1%]. 48V models: Default 44.0V (LIB: 51.9V). Range: program29 to Min [program12 - 0.1V, 54V]. For Lix, default 15%, range SOC of program29 to Min[95%, program12 - 1%]. |
| 32 | Bulk charging time (C.V stage) | Automatically (Default): Inverter will judge this charging time automatically. 5 min - 900 min: Setting range is from 5 min to 900 min. Increment of each click is 5 min. |
| 33 | Battery equalization | Battery equalization disable (default) |
| 34 | Battery equalization voltage | 24V models: Default 29.2V. Range: floating voltage ~ 31V. 48V models: If program 5 is not LIB, default 58.4V. Range: floating voltage ~ 62V. |
| 35 | Battery equalized time | 60min (default): Setting range is from 0 min to 900min. |
| 36 | Battery equalized timeout | 120min (default): Setting range is from 0min to 900 min. |
| 37 | Equalization interval | 30days (default): Setting range is from 1 to 90 days. |
| 39 | Equalization activated immediately | Enable: If equalization function is enabled in program 33, this program can be set up. If "Enable" is selected in this program, it's to activate battery equalization immediately and LCD main page will show "EQ". |
| Disable (default): If "Disable" is selected, it will cancel equalization function until next activated equalization time arrives based on program 37 setting. At this time, "EQ" will not be shown in LCD main page. | ||
| 41 | Automatic activation for lithium battery | Disable (default): Disable automatic activation. |
| Auto: When Program05 is selected as "User-Defined" or "LIB" or "LIx", lithium battery and when the battery is not detected, the unit will activate automatically the lithium battery at a time. If you want to activate automatically the lithium battery, you must restart the unit. | ||
| 42 | Manual activation for lithium battery | Default: Disable activation. |
| Activation: When Program05 is selected "User-Defined" or "LIB" or "LIx" as lithium battery, when the battery is not detected, if you want to activate the lithium battery at a time, you could select it. | ||
| 43 | OP2 Output Enable | Enable (default): OP2 output is allowed. |
| Disable: OP2 output is forbidden. | ||
| 46 | Maximum discharge current protection | Default OFF: Disable current discharge current protection function. Only available in Single model. The setting range is from 20A to 500A. When utility is available, it turns to utility model and battery discharge stops after the battery discharge current exceeded the setting value. When utility is unavailable, warning occurs and battery discharge lasts after the battery discharge current exceeded the setting value. |
| 47 | Setting the OP2 overload warning point | Set the OP2 overload warning point. If the set value is exceeded, 22 warning will be displayed. Setting range is from 10% to 100% and the default setting is 50%. |
| 49 | RGB mode - Checking RGB Indicator table | Mode 1 (Default): RGB LED is working normally. |
| Mode 2: RGB LED is working with only the unit in fault mode. | ||
| Mode 3: RGB LED is always OFF. | ||
| Mode 4: RGB LED shows as mode 1 and whether battery is fully charged or not, RGB LED won't be flashing at any time. | ||
| Mode 5: RGB LED shows as mode 1 and whether battery is fully charged or not, RGB LED will be flashing. | ||
| 50 | Lithium battery activation time | When lithium battery activation function is available, the activation time could be set, the setting range is 6s~300s, the default time is 6s. |
Battery Equalization
Equalization function is added into the charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize battery periodically.
How to Apply Equalization Function:
You must enable battery equalization function in monitoring LCD setting program 33 first. Then, you may apply this function in device by either one of following methods:
- Setting equalization interval in program 37.
- Active equalization immediately in program 39.
When to Equalize:
In float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter Equalize stage.
Equalize Charging Time and Timeout:
In Equalize stage, the controller will supply power to charge battery as much as possible until battery voltage raises to battery equalization voltage. Then, constant-voltage regulation is applied to maintain battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until setting battery equalized time is arrived.
However, in Equalize stage, when battery equalized time is expired and battery voltage doesn't rise to battery equalization voltage point, the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage. If battery voltage is still lower than battery equalization voltage when battery equalized timeout setting is over, the charge controller will stop equalization and return to float stage.
Setting for Lithium Battery
If choosing a lithium battery for the inverter, you are allowed to use only the lithium battery which we have configured. There are two connectors on the lithium battery: the RS485 port of BMS and the power cable.
Lithium Battery Connection Steps:
- Assemble battery terminal based on recommended battery cable and terminal size (same as Lead acid, see section Lead-acid Battery connection for details).
- Connect the end of the RS485 port of the battery to the BMS (RS485) communication port of the inverter.
Lithium Battery Communication and Setting:
If choosing a lithium battery, make sure to connect the BMS communication cable between the battery and the inverter. This communication cable delivers information and signals between the lithium battery and the inverter. This information is listed below:
- Re-configure charging voltage, charging current, and battery discharge cut-off voltage according to the lithium battery parameters.
- Have the inverter start or stop charging according to the status of the lithium battery.
Connect the end of RS485 of battery to RS485 communication port of inverter:
Make sure the lithium battery RS485 port connects to the inverter is Pin to Pin, the inverter RS485 port pin assignment shown as below:
| Pin Number | RS485 Port |
|---|---|
| PIN1 | RS485-B |
| PIN2 | RS485-A |
| PIN7 | RS485-A |
| PIN8 | RS485-B |
LCD Setting for Lithium Battery:
After connecting, you need to finish and confirm some settings as follows:
- Select program 05 as lithium battery type.
LCD Display for Lithium Battery:
If communication between the inverter and battery is successful, there is some information getting from BMS and showing on the LCD as follows:
- Communication successful icon: Li will be flashing.
- Max lithium battery charging voltage.
- Max lithium battery charging current.
- Lithium battery discharging is forbidden: Li will flash once every 1 second.
- Lithium battery charging is forbidden: Li will flash once every 2 seconds.
- Lithium battery SOC (%).
Setting for PYLON US2000 Lithium Battery:
- PYLONTECH US2000 lithium battery setting:
Dip Switch: There are 4 Dip Switches that set different baud rate and battery group address. If switch position is turned to the "OFF" position, it means "0". If switch position is turned to the "ON" position, it means "1".
- Dip 1 is "ON" to represent the baud rate 9600.
- Dip 2, 3 and 4 are reserved for battery group address.
- Dip switch 2, 3 and 4 on master battery (first battery) are to set up or change the group address.
NOTE: "1" is upper position and "0" is bottom position.
- Process of install:
- Step 1. Use the RS485 cable to connect inverter and Lithium battery as Fig 1 (Figure 13).
- Step 2. Switch on Lithium battery.
- Step 3. Press more than three seconds to start Lithium battery, power output ready.
- Step 4. Turn on the inverter.
- Step 5. Be sure to select battery type as "Li2" in LCD program 5.
If communication between the inverter and battery is successful, the battery icon LI on the LCD display will light.
Setting for Lithium Battery without Communication:
This suggestion is used for lithium battery application and avoids lithium battery BMS protection without communication. Please finish the setting as follows:
- A. Recommended method 1: Set battery type as "LIB" in program 05.
- B. Recommended method 2: Setting as follows:
- Before starting setting, you must get the battery BMS specification: Max charging voltage, Max charging current, Discharging protection voltage.
- Set battery type as "LIB" in program 05.
- Set C.V voltage as Max charging voltage of BMS-0.5V in program 26.
- Set floating charging voltage as C.V voltage in program 27.
- Set Low DC cut-off voltage discharging protection voltage in program 29.
- Set Max charging current in program 02 which must be less than the Max charging current of BMS.
- Setting voltage point back to utility source when selecting "SBU priority" in program 12.
The setting value must be ≥ Low DC cut-off voltage + 2V, or else the inverter will have a warning as battery voltage low.
Remark:
- You'd better to finish setting without turning on the inverter (just let the LCD show, no output).
- When you finish setting, please restart the inverter.
Troubleshooting
Fault Reference Code
| Fault Code | Fault Event |
|---|---|
| 01 | Over temperature of inverter module |
| 02 | Over temperature of DCDC module |
| 03 | Battery voltage is too high |
| 04 | Over temperature of PV module |
| 05 | Output short circuited. |
| 06 | Output voltage is too high. |
| 07 | Overload time out |
| 08 | Bus voltage is too high |
| 09 | Bus soft start failed |
| 10 | PV over current |
| 11 | PV over voltage |
| 12 | DCDC over current |
| 13 | Over current or surge |
| 14 | Bus voltage is too low |
| 15 | Inverter failed (Self-checking) |
| 18 | Op current offset is too high |
| 19 | Inverter current offset is too high |
| 20 | DC/DC current offset is too high |
| 21 | PV current offset is too high |
| 22 | Output voltage is too low |
| 23 | Inverter negative power |
| 24 | Op2 current offset is too high |
Warning Indicator
| Warning Code | Warning Event | Audible Alarm |
|---|---|---|
| 02 | Temperature is too High | Beep three times every second |
| 04 | Low battery | Beep once every second |
| 07 | Overload | Beep once every 0.5 second |
| 10 | Output power derating | Beep twice every 3 seconds |
| 14 | Fan blocked | None |
| 15 | PV energy is low | Beep twice every 3 seconds |
| 19 | Lithium Battery communication is failed | Beep once every 0.5 second |
| 21 | Lithium Battery over current | None |
| 22 | The load exceeds the set value of program program47 | None |
| E9 | Battery equalization | None |
| b8 | Battery is not connected | None |
Troubleshooting Table
| Problem | LCD/LED/Buzzer | Explanation / Possible cause | What to do |
|---|---|---|---|
| Unit shuts Down automatically during startup process. | LCD/LEDs and buzzer will be active for 3 seconds and then complete off. | The battery voltage is too low | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | No indication. | 1. The battery voltage is far too low. 2. Battery polarity is connected reversed. |
1. Check if batteries and the wiring are connected well. 2. Re-charge battery. 3. Replace battery. |
| Mains exist but the unit works in battery mode. | Input voltage is displayed as 0 on the LCD and green LED is flashing. | Input protector is tripped | Check if AC breaker is tripped and AC wiring is connected well. |
| Green LED is flashing. | Insufficient quality of AC power. (Shore or Generator) | Check if AC wires are too thin and/or too long. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS / Appliance) | |
| When the unit is turned on, internal relay is switched on and off repeatedly. | Green LED is flashing. | Set "Solar First" as the priority of output source. | Change output source priority to Utility first. |
| LCD display and LEDs are flashing | Battery is disconnected. | Check if battery wires are connected well. | |
| Fault code 07 | Overload error. The inverter is overload 110% and time is up. | Reduce the connected load by switching off some equipment. | |
| Fault code 05 | Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
| Fault code 02 | Internal temperature of inverter component is over 100°C. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
| Fault code 03 | Battery is over-charged. | Return to repair center. | |
| Fault code 03 | The battery voltage is too high. | Check if spec and quantity of batteries are meet requirements. | |
| Buzzer beeps continuously and red LED is on. | Fault code 06/22 | Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) | 1. Reduce the connected load. 2. Return to repair center. |
| Fault code 08/09/15 | Internal components failed. | Return to repair center. | |
| Fault code 13 | Over current or surge. | Restart the unit, if the error happens again, please return to repair center. | |
| Fault code 14 | Bus voltage is too low. | If the wires is connected well, please return to repair center. | |
| Another fault code | If the wires is connected well, please return to repair center. |
Specifications
Table 1 Line Mode Specifications
| INVERTER MODEL | 4.2KVA | 6.2KVA |
|---|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) | |
| Nominal Input Voltage | 230Vac | |
| Low Loss Voltage | 170Vac±7V (UPS) 90Vac±7V (Appliances) | |
| Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) | |
| High Loss Voltage | 280Vac±7V | |
| High Loss Return Voltage | 270Vac±7V | |
| Max AC Input Voltage | 300Vac | |
| Nominal Input Frequency | 50Hz / 60Hz (Auto detection) | |
| Low Loss Frequency | 40±1Hz | |
| Low Loss Return Frequency | 42±1Hz | |
| High Loss Frequency | 65±1Hz | |
| High Loss Return Frequency | 63±1Hz | |
| Output Short Circuit Protection | Battery mode: Electronic Circuits | |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) | |
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) | |
| Output power derating: When AC input voltage drops to 95V or 170V depending on models, the output power will be derated. |
Output Power Rated Power 50% Power
|
|
Table 2 Inverter Mode Specifications
| INVERTER MODEL | 4.2KVA | 6.2KVA |
|---|---|---|
| Rated Output Power | 4.2KVA 4.2KW | 6.2KVA 6.2KW |
| Dual output function | Yes | Yes |
| Max.main output power | 4.2KVA 4.2KW | 6.2KVA 6.2KW |
| Max.second output power | 4.2KVA 4.2KW | 6.2KVA 6.2KW |
| Output Voltage Waveform | Pure Sine Wave | |
| Output Voltage Regulation | 230Vac±5% | |
| Output Frequency | 50Hz or 60Hz | |
| Peak Efficiency | 94% | |
| Surge Capacity | 2* rated power for 5 seconds | |
| Nominal DC Input Voltage | 24Vdc | 48Vdc |
| Cold Start Voltage | 23.0Vdc | 46.0Vdc |
| Low DC Warning Voltage Just for AGM and Flooded @ load < 20% | 22.0Vdc 21.4Vdc 20.2Vdc | 44.0Vdc 42.8Vdc 40.4Vdc |
| Low DC Warning Return Voltage Just for AGM and Flooded @ load < 20% | 23.0Vdc 22.4Vdc 21.2Vdc | 46.0Vdc 44.8Vdc 42.4Vdc |
| Low DC Cut-off Voltage Just for AGM and Flooded @ load < 20% | 21.0Vdc 20.4Vdc 19.2Vdc | 42.0Vdc 40.8Vdc 38.4Vdc |
Table 3 Charge Mode Specifications
| Utility Charging Mode | 4.2KVA | 6.2KVA |
|---|---|---|
| Max Charging Current (PV+AC) (@ VI/P=230Vac) | 120Amp | 120Amp |
| Max Charging Current (AC)(@ VI/P=230Vac) | 120Amp | 120Amp |
| Bulk Charging Voltage (Flooded Battery) | 29.2Vdc | 58.4Vdc |
| Bulk Charging Voltage (AGM / Gel Battery) | 28.2Vdc | 56.4Vdc |
| Floating Charging Voltage | 27Vdc | 54Vdc |
| Overcharge Protection | 32Vdc | 63Vdc |
| Battery reverse connection protection | No | No |
| Charging Algorithm | 3-Step | |
| Charging Curve |
|
|
Solar Input Specifications
| INVERTER MODEL | 4.2KVA | 6.2KVA |
|---|---|---|
| Rated Power | 6200W | 9000W |
| Max. PV Array Open Circuit Voltage | 500Vdc | |
| PV Array MPPT Voltage Range | 60Vdc~500Vdc | |
| Max. Input Current | 27A | |
| Max. Charging Current(PV) | 120A | |
Table 4 General Specifications
| INVERTER MODEL | 4.2KVA | 6.2KVA |
|---|---|---|
| Operating Temperature Range | -10°C to 55°C | |
| Storage temperature | -15°C ~ 60°C | |
| Humidity | 5% to 95% Relative Humidity (Non-condensing) | |
| Dimension (D*W*H), mm | 368x328x120 | |
| Net Weight, kg | 7.0 | 8.0 |
User Tips
- Noise Consideration: The inverter can be noisy during operation due to cooling fans. If noise is a concern, consider installing the unit in a location away from living or sleeping areas.
- Battery Operation: Some models of this inverter may not operate without a connected battery. Ensure you have a compatible battery connected for full functionality.
- Power Button Functionality: The physical power button on the unit primarily controls the load output. If the inverter is connected to any power source (solar, utility), it may remain active and its cooling fans may run, even if the load output is turned off. Plan your setup accordingly if you require a complete shutdown.
- Lithium Battery Settings: When using lithium batteries, it is crucial to correctly configure the battery type and related charging/discharging parameters (programs 05, 26, 27, 29) to ensure optimal performance and prevent damage. Refer to the 'Setting for Lithium Battery' section for detailed instructions.
- Voltage Accuracy: Some users have noted slight discrepancies in voltmeter readings. While the inverter generally performs well, it's advisable to cross-reference with external measurement tools if precise voltage monitoring is critical for your setup.
Warranty and Support
For detailed warranty information, service, and technical support, please refer to the official product documentation or contact Aninerel customer service. A comprehensive user manual in PDF format is available for download: View User Manual (PDF).