SWEVY SW300S

Contents

SWEVY SW-300S Clamp Earth Resistance Tester

User Manual

Model: SW-300S | Brand: SWEVY

1. Introduction

The SWEVY SW-300S Clamp Earth Resistance Tester represents a significant advancement in traditional grounding resistance measurement. This device is widely utilized across various sectors including power systems, telecommunications, meteorology, oilfields, construction, and industrial electrical equipment. Its clamp design allows for grounding resistance measurement in systems with loops without the need to disconnect the grounding lead or use auxiliary grounding electrodes, making it a safe, fast, and simple tool to use.

This clamp grounding resistance meter can measure ground faults that traditional methods cannot detect. It is particularly useful in scenarios where conventional measurement techniques are impractical, as it measures the combined resistance of the grounding body and the grounding lead.

For a complete and detailed manual, please refer to the official PDF document: SWEVY SW-300S User Manual (PDF).

2. Safety Precautions

To ensure safe and proper use of the Clamp Earth Resistance Tester, please observe the following precautions:

  • Always pay special attention to safety when using this tester.
  • Adhere to the specified measuring range and usage environment. Do not clamp or test power lines.
  • Observe all labels on the panel and backplane of the meter.
  • Before powering on, operate the trigger one or two times to ensure the jaws are securely closed. Do not hold the trigger or clamp any wires during boot-up.
  • Wait for the auto-inspection to complete and the "OL Ω" symbol to display before clamping and testing any object.
  • Keep the jaw contact surfaces clean. Avoid rubbing them with caustics or coarse materials.
  • Avoid any impact on the meter, especially the jaw contact planes.
  • In hazardous environments, it is strongly recommended to use an explosion-proof type clamp grounding resistance meter.
  • It is strictly forbidden to disassemble or replace batteries in hazardous locations for explosion-proof type products.
  • A slight buzzing sound from the meter clamp during resistance measurement is normal.
  • Ensure the measuring wire current does not exceed the meter's upper range limit.
  • Remove batteries if the meter will not be used for an extended period.
  • Disassembly, calibration, and repair must only be performed by authorized personnel.
  • If the instrument is deemed unsafe for continued use, cease operation immediately and have it handled by an authorized institution.

3. Product Overview

The SWEVY SW-300S is a robust and precise clamp earth resistance tester designed for various electrical measurement tasks.

SWEVY SW-300S Clamp Earth Resistance Tester product shot with key features

Figure 1: SWEVY SW-300S Clamp Earth Resistance Tester highlighting key features like 0.001Ω resolution, 0.01Ω-300Ω resistance range, storable data, alarm setting, 32mm jaw, and double insulation.

3.1. Meter Structure and Dimensions

Dimensions and labeled parts of the SW-300S Clamp Earth Resistance Tester

Figure 2: Diagram showing the dimensions (260mm x 105mm x 60mm) and labeled components of the SW-300S, including the Round Clamp Jaw, HOLD Key, MODE Key, Trigger, Boot Up/Shutdown/Quit button, and Liquid Crystal Display (LCD).

  1. Round Clamp Jaw: Ø32mm
  2. Meter body
  3. Trigger: Controls the clamp opening and closing.
  4. Liquid Crystal Display (LCD)
  5. Power Key: Used for Boot Up, Shutdown, and Quitting operations.
  6. MODE Key: Switches between function modes (resistance measurement / data reading).
  7. HOLD Key: Locks/releases the display and sets alarm values.

3.2. LCD Screen and Symbols

The 4-digital LCD (47mm L x 28.5mm W) provides clear readings and indicators. Key symbols include:

  • Clamp opening symbol: Indicates the clamp is open.
  • Alarm symbol: Flashes when the measured value exceeds the alarm setting.
  • AC symbol
  • Full data storage symbol (MEM): Indicates memory is full.
  • Data reading symbol (MR): Appears during data review.
  • Storage data group number
  • Measurement value display
  • Current unit symbol
  • Measurement value symbol
  • Resistance unit
  • Low battery voltage symbol: Appears when battery voltage drops below 4.8V.
  • Noise signal
  • Data lock symbol (HOLD): Indicates the displayed value is locked.

Special Symbols Description:

  • Clamp Opening Symbol: Appears when the clamp is open, or if the trigger is artificially pressed, or if the clamps are severely polluted, preventing further measurement.
  • "Er" Symbol: Indicates a boot-up error, possibly due to an artificially pressed trigger or an open clamp during startup.
  • Low Battery Voltage Symbol: Displays when the battery voltage is below 4.8V, indicating that measurement accuracy cannot be guaranteed and batteries should be replaced.
  • "OL Ω" Symbol: Indicates that the measured resistance has exceeded the meter's upper limit range.
  • "L0.01Ω" Symbol: Indicates that the measured resistance has fallen below the meter's lower limit range.
  • Alarm Symbol ())) : Flashes when the measured value surpasses the set alarm critical value.
  • MEM Symbol: Flashes when the data memory is full (99 groups), preventing further data storage.
  • MR Symbol: Appears during data reading, along with the storage number of the data.

4. Specifications

4.1. Ranges & Accuracy

Mode Range Resolution Accuracy
Resistance Range 0.010Ω ~ 0.099Ω 0.001Ω ±(1%rdg + 0.01Ω)
0.10Ω ~ 0.99Ω 0.01Ω ±(1%rdg + 0.01Ω)
1.0Ω ~ 49.9Ω 0.1Ω ±(1%rdg + 0.1Ω)
50.0Ω ~ 99.5Ω 0.5Ω ±(1.5%rdg + 0.5Ω)
100Ω ~ 199Ω 1Ω ±(2%rdg + 1Ω)
200Ω ~ 300Ω 5Ω ±(5%rdg + 5Ω)

4.2. Technical Specifications

Attribute Value
Power SourceDC 6V Alkaline dry battery (LR6 1.5V X 4PCS)
LCD4-digital LCD, 47mm (L) X 28.5mm (W)
Structural FeatureClamp and jaw type
Resistance Measurement Range0.010Ω ~ 300Ω
Maximum Resistance Measurement Resolution0.001Ω
Range ShiftAutomatic
Single Measuring Time0.5 second
Measurement Resistance Frequency> 1KHz
Alarm Value SettingResistance: 1Ω ~ 199Ω
Storable Measurement Data99 groups, "MEM" symbol indicates memory full
Data Hold"HOLD" symbol display
Data Review"MR" symbol display
Overflow Display"OL" symbol display
Alarm FunctionAlarm symbol " )))" will flash when measured value exceeds alarm setting.
Battery Voltage IndicatorLow battery symbol displayed when voltage drops to ~4.8V.
Working Current40 mA Max
Meter WeightAbout 820g (include battery); Total weight: about 1.97kg (include battery)
Meter Size260mm × 105mm × 60mm
Operating Temperature-10°C ~ 55°C
Relative Humidity10% ~ 90%
Protection LevelDouble insulation
External Electromagnetic Fields<1V/m, <40A/m
Safety RegulationsIEC61010-1, IEC1010-2-31, IEC61557-1, Pollution Degree 2, CAT III 300V, JJG 1054-2009 Clamp-on Earth Resistance Tester

5. Setup

5.1. Battery Installation

The SW-300S requires four LR6 (1.5V) Alkaline dry batteries. To install or replace batteries, locate the battery compartment on the back of the meter. Ensure correct polarity when inserting the batteries. When the low battery symbol appears on the LCD, replace the batteries promptly to maintain measurement accuracy.

5.2. Initial Checks

Before each use, perform the following checks:

  • Jaw Closure: Before powering on, operate the trigger one or two times to ensure the clamp jaws are well closed.
  • Clean Jaws: Ensure the jaw contact surfaces are clean and free from any debris or corrosive materials.
  • Power On: Press the Power key to switch the meter on. The LCD will perform an automatic test, displaying all symbols (refer to Figure 1 in Product Overview).
  • Auto-Calibration: The meter will then perform an auto-calibration. After successful calibration, it will display "OL Ω" and enter the resistance measurement mode.
  • Error Check: If the meter displays "Er" during boot-up, it indicates an error (e.g., trigger held down, clamp open). Address the issue and reboot.
  • Static State: During auto-inspection, keep the meter in a natural static state. Do not overturn it or apply external force to the clamp, as this can affect measurement accuracy.
  • Conductor Loop: If the jaws are clamped around a conductor loop during auto-inspection, the measurement will be inaccurate. Remove the conductor loop and reboot the meter.

6. Operating Instructions

6.1. Start Up

Before starting, ensure the clamp jaws are closed properly by operating the trigger a couple of times. Press the Power key. The meter will switch on, perform an LCD self-test displaying all symbols, and then auto-calibrate. Upon successful calibration, "OL Ω" will be displayed, and the meter will be ready for resistance measurement. If "Er" is displayed, an error occurred during boot-up (e.g., trigger held, clamp open); resolve the issue and restart.

6.2. Shutdown

To manually shut down the meter, press the Power key. The meter also features an automatic shutdown function: after 5 minutes of inactivity, the LCD screen will flash for 30 seconds before automatically powering off to conserve battery. Pressing the Power key during the flashing state will delay shutdown and keep the meter working.

6.3. Resistance Measurement

After successful boot-up and auto-inspection (displaying "OL Ω"), the meter is ready for resistance measurement. Press the trigger to open the jaws, clamp the measured loop, and then release the trigger. The resistance value will be displayed on the LCD. If the meter displays "OL Ω", the measured resistance exceeds the upper limit. If "L0.01Ω" is displayed, the resistance is below the lower limit. If necessary, a test can be performed with the provided test ring to verify accuracy. If the reading matches the nominal value of the calibration resistor or differs by no more than 0.1Ω, the instrument is functioning correctly. If "OL A" is displayed, the measured current value has exceeded the meter's upper limit range.

6.4. Data Lock/Release/Storage

During measurement, press the HOLD key to lock the current display value. The "HOLD" symbol will appear on the LCD. This locked value is automatically numbered and stored. To release the lock, press the HOLD key or Power key; the "HOLD" symbol will disappear, and the meter will return to measurement mode. The meter can store up to 99 sets of data. If the memory is full, the "MEM" symbol will flash. Saved data is retained even after the meter is shut down.

6.5. Data Access

Press the MODE key to enter the data reading mode. The default display will show the first stored data unit (No. 01). Press the HOLD key to browse through the saved data. After viewing the last data unit, it will loop back to No. 01. If no data is stored, the display will indicate this.

6.6. Alarm Critical Value Setting

Illustration of alarm settings and value alarm prompt for the SW-300S

Figure 3: Visual guide for setting alarm values, showing the process of pressing HOLD for 3 seconds to enter setting mode and adjusting values between 1-199Ω.

In resistance or current measurement mode, press and hold the HOLD key for 3 seconds to enter the alarm critical value setting function. The highest digit will begin to flash. Use the MODE key to switch between digits (from high to low). While a digit is flashing, press the HOLD key to change its value (0-9). After setting all digits, press and hold the HOLD key for 3 seconds or press the Power key to confirm the setting. The set alarm value will flash, and the meter will return to measurement mode. You can also exit the setting function by pressing the Power key at any time.

6.7. Clear Data

To clear all stored data, first press the MODE key to enter the data reading mode. Then, simultaneously press and hold the HOLD key and the MODE key. All stored data will be cleared. If no data is stored, the display will indicate this.

6.8. Measurement Principle

The SW-300S Clamp Earth Resistance Tester measures grounding resistance by determining the loop resistance. The meter's jaw consists of a voltage coil and a current coil. The voltage coil generates a drive signal, inducing an electric potential (E) in the measured loop. This potential causes a current (I) to flow through the loop. The meter measures both E and I, and the resistance (R) is calculated using the formula R = E/I.

6.9. Grounding Resistance Measurement Methods

The SW-300S can be used for various grounding system configurations:

6.9.1. Multi-Point Grounding System

For systems like electricity transmission tower grounding or telecommunications cable grounding, where multiple grounding points are interconnected, the resistance of individual branches can be measured by simply clamping the grounding down lead with the SW-300S.

(Refer to the PDF manual for diagrams illustrating multi-point grounding systems and their equivalent electric circuits.)

6.9.2. Limited Point Grounding System

In situations where grounding bodies are interconnected but not part of an independent grid (e.g., several towers connected via overhead ground wire), the SW-300S can still provide accurate measurements. The parallel equivalent resistance of the grounding resistance is calculated using standard theory, ignoring mutual resistance for practical purposes.

(Refer to the PDF manual for equations related to limited point grounding systems.)

6.9.3. Single-Point Grounding System

While the SW-300S primarily measures loop resistance, single-point grounding can be measured by artificially creating a loop using a test wire and a nearby earth electrode. Two methods are available:

  • Two-Point Method: Connect the measured grounding body (RA) to an independent, better grounding body (RB, e.g., water pipe, fire hydrant) with a test wire. The meter measures the total series resistance (RT = RA + RB + RL, where RL is the test wire resistance). If RT is below the allowable grounding resistance, both RA and RB are qualified.
  • Three-Point Method: Involves three independent grounding bodies (RA, RB, RC). Three separate measurements are taken by connecting two bodies at a time with a test wire. The individual grounding resistance of RA can then be calculated using the formula: RA = (R1 + R2 - R3) / 2, where R1, R2, R3 are the measured resistances of the three combinations.

(Refer to the PDF manual for detailed diagrams of the Two-Point and Three-Point methods.)

6.10. Field Application

The SW-300S is versatile for various field applications:

  • Power System: Measures tower grounding resistance of transmission lines and neutral point grounding resistance of transformers. For transformers with multiple grounding leads, untie all but one for accurate single-point measurement. Also applicable in power stations and substations for testing circuit connections and grounding networks.
  • Telecommunications System: Convenient for measuring machine room grounding resistance, especially in upper floors where traditional megger meters are difficult to use. Connect a fire hydrant or another ground electrode with a test wire to the measured ground electrode. The meter value will be the sum of machine room resistance, test wire resistance, and fire hydrant ground resistance. If the fire hydrant resistance is very small, machine room resistance ≈ meter resistance - test wire resistance. Also used for machine room and launch tower grounding resistance.
  • Lightning Protection System of Building: Measures the grounding resistance of individual grounding poles in buildings where poles are independent of each other.

(Refer to the PDF manual for diagrams illustrating applications in telecommunications and lightning protection systems.)

6.11. Measure Grounding Resistance Notes

When measuring grounding resistance, selecting the correct measurement point is crucial to avoid inaccurate results. For example, in a grounding system with multiple branches:

  • If measuring at point A (where the branch does not form a circuit), the meter will display "OL Ω", indicating an incorrect measurement point.
  • If measuring at point B (where the branch forms a metallic conductor circuit), the meter may display "L 0.01Ω" or a very small resistance value, also indicating an incorrect measurement point.
  • Measuring at point C (where the branch is properly isolated) will yield the correct grounding resistance value for that branch.

(Refer to the PDF manual for a diagram illustrating correct and incorrect measurement points.)

7. Maintenance

  • Cleaning: Keep the jaw contact surfaces clean. Use a soft, dry cloth. Do not use caustic or abrasive materials.
  • Battery Replacement: Replace the four LR6 (1.5V) Alkaline dry batteries when the low battery indicator appears on the LCD (around 4.8V). Remove batteries if the meter will not be used for a long time to prevent leakage.
  • Storage: Store the meter in a dry, clean environment within the specified operating temperature range (-10°C to 55°C) and relative humidity (10%-90%).
  • Servicing: Any disassembly, calibration, or repair of the tester must be performed by authorized service personnel only. Unauthorized modifications will void the warranty and may compromise safety.

8. Troubleshooting

Problem/Display Possible Cause Solution
"Er" symbol on LCD during boot-up Trigger artificially pressed or clamp open during startup. Ensure trigger is released and clamp is closed before pressing Power key. Reboot the meter.
"OL Ω" symbol on LCD Measured resistance exceeds the meter's upper limit range. Verify the circuit being measured is within the meter's range (0.01Ω-300Ω).
"L0.01Ω" symbol on LCD Measured resistance is below the meter's lower limit range. Verify the circuit being measured. This may indicate a short circuit or very low resistance.
Alarm symbol " )))" flashing Measured value exceeds the set alarm critical value. Review the measurement. Adjust the alarm critical value if necessary (refer to section 6.6).
"MEM" symbol flashing Data memory is full (99 groups). Clear stored data if new data needs to be saved (refer to section 6.7).
"OL A" symbol on LCD Measured current value exceeds the meter's upper limit range. Ensure the current in the measured circuit is within safe limits for the device.
Inaccurate measurements Non-static state during auto-inspection, external force on clamp, dirty jaw surfaces, or clamping a conductor loop during auto-inspection. Keep meter static during startup. Avoid external force on clamp. Clean jaw surfaces. Ensure no conductor loop is clamped during auto-inspection.
Low battery symbol displayed Battery voltage is low (around 4.8V). Replace all four LR6 (1.5V) Alkaline dry batteries.

9. User Tips

  • Always ensure the clamp jaws are clean and fully closed before taking any measurements to guarantee accuracy.
  • Regularly check the battery level indicator and replace batteries promptly to avoid interruptions during critical measurements.
  • For multi-point grounding systems, remember that the meter measures the combined resistance of the grounding body and lead.
  • When measuring single-point grounding, ensure your auxiliary grounding body (e.g., water pipe) is truly independent and has a very low resistance for reliable results.
  • Take advantage of the data storage feature for recording multiple measurements, especially when performing sequential tests or monitoring changes over time.

10. Accessories

The following items are included with your SWEVY SW-300S Clamp Earth Resistance Tester:

  • Clamp Grounding Tester: 1 PCS
  • Test Ring: 1 PCS
  • Meter Case: 1 PCS
  • Alkaline dry battery (LR6 1.5V): 4 PCS
  • User's Manual: 1 SET

11. Warranty and Support

SWEVY is committed to providing high-quality products. This user manual contains essential information for the proper operation and maintenance of your SW-300S Clamp Earth Resistance Tester. Please note the following:

  • The manufacturer is not responsible for any losses incurred due to improper use of the product.
  • This manual is intended for informational purposes and should not be used as a basis for special claims.
  • The manufacturer reserves the right to modify the contents of this user manual without prior notice. Please refer to the latest version for any updates.

For technical support or service inquiries, please contact your authorized dealer or the manufacturer directly.