ANERN Hybrid Solar Inverter User Manual

Model: FGI-S12000 Series

This manual is valid for 5KW, 6.5KW, and 12KW models.

1. Introduction

This manual provides comprehensive instructions for the assembly, installation, operation, and maintenance of the ANERN Hybrid Solar Inverter. Please read this manual carefully before proceeding with any installations or operations to ensure proper functioning and safety.

1.1 Product Overview

The ANERN Hybrid Solar Inverter is a multifunctional device integrating an MPPT solar charge controller, a high-frequency pure sine wave inverter, and a UPS function module. It is designed for off-grid backup power and self-consumption applications and can operate with or without batteries. The system requires additional components such as PV modules, a generator, or a utility grid for complete functionality. Some models include a built-in or plug-and-play WiFi module for remote monitoring via mobile app or website.

ANERN Hybrid Solar Inverter main unit with specifications: 6500W/12000W, 6.5KW/12KW Rated Output Power, 48Vdc Nominal DC Input Voltage, 120A/160A Max Charging Current, Model AN-FGI-S6500/S12000, 2 Year Warranty.

Figure 1: ANERN Hybrid Solar Inverter (FGI-S6500/S12000) with key specifications.

System Diagram showing connections: Solar Panel, Generator, Utility, Inverter (FGI-S12000), External Battery packs, and Home Appliances. Also shows Cube WIFI/GPRS for internet, PVguarder APP, and PVguarder Web monitoring.

Figure 2: Typical Solar Energy Storage System Diagram.

1.2 Target Group

This document is intended for qualified persons and end-users. Tasks not requiring specific qualifications can be performed by end-users. Qualified persons should possess knowledge of inverter operation, risks associated with electrical devices, installation and commissioning of electrical systems, applicable standards, and safety information.

1.3 Safety Instructions

Adherence to safety instructions is crucial for personal safety and proper product function. Please observe all warnings and cautions.

  • WARNING! A high level of potential danger, which, if not avoided, could result in death or serious injury to personnel.
  • CAUTION! A moderate or low level of potential danger, which, if not avoided, could result in moderate or minor injuries to personnel. In some bad situations, it could result in death or serious injury to personnel.

General Safety Guidelines:

  • Ensure correct battery system type (lithium or lead-acid) is selected to prevent system malfunction.
  • Read all instructions and cautionary markings on the unit and batteries before use.
  • All electrical installations must comply with local electrical safety standards.
  • When installing PV modules during the daytime, cover them with opaque materials to avoid high terminal voltage.
  • Only charge deep-cycle lead-acid or lithium rechargeable batteries. Other battery types may burst.
  • Do not disassemble the unit. Refer servicing to qualified personnel.
  • Disconnect all wiring before maintenance or cleaning. Turning off the unit alone does not eliminate electrical shock risk.
  • NEVER charge a frozen battery.
  • Follow recommended cable sizes for optimal operation.
  • Exercise caution with metal tools near batteries to prevent short circuits or explosions.
  • Strictly follow installation procedures for disconnecting AC or DC terminals.
  • The inverter must be connected to a permanent grounded wiring system, complying with local regulations.
  • NEVER short circuit AC output and DC input. Do NOT connect to mains with DC input short circuits.
  • Ensure the inverter is completely assembled before operation.

Labels on Inverter:

SymbolDescription
⚠ CAUTIONDo not disconnect under load!
⚠ Danger: High Voltage!Danger: Electrical Hazard!
⏱ 5minStart maintaining the INVERTER at least 5 minutes after the INVERTER disconnected from all external power supplies.
📖Read instructions carefully before performing any operation on the INVERTER.
␣Grounding: The system must be firmly grounded for operator safety.

2. Setup (Installation)

2.1 Unpacking and Inspection

Upon receiving the product, inspect the outer packaging for any damage. Open the box and check if the internal equipment is intact. If any damage is found, contact your local distributor. Products are strictly tested before leaving the factory.

Installation Tools:

  • Multi-meter
  • Protective gloves
  • Insulated anti-smashing shoes
  • Safety glasses
  • ESD wrist strap
  • Hammer drill
  • Electric screwdriver
  • Cross screwdriver
  • Rubber mallet
  • Spirit level
  • Wire cutter / stripper
  • Terminal crimping tool

2.2 Mounting Unit

Consider the following points for installation location:

  • Do not mount on flammable construction materials.
  • Mount on a solid, non-combustible surface (e.g., concrete).
  • Install at eye level for easy LCD display reading.
  • Ambient temperature should be between -10°C and 60°C.
  • Mount vertically on the wall.
  • Ensure sufficient space (at least 30cm clearance on top, bottom, and sides) for heat dissipation and wiring access.

Figure 3: Inverter Mounting Clearance (Refer to manual for diagram).

Mounting Steps:

  1. Use an ⌀8 drilling bit to drill holes on the mounting surface, 110mm apart. Insert expansion screw tubes (M6 expansion screws suggested).
  2. Align the inverter's top screw holes with the installed expansion screw tubes and fix the inverter to the wall.
  3. Before connecting wiring, remove the bottom cover by unscrewing four screws.

2.3 AC Input / Output Connection

CAUTION! Install a separate AC breaker (recommended 80A) between the inverter and the AC input power source. Do not mis-connect input and output connectors. Ensure correct AC cable polarity (L and N) to prevent short circuits.

WARNING! All wiring must be performed by qualified personnel. Use appropriate cable sizes to ensure system safety and efficient operation.

GaugeCable (mm²)
6 AWG13.3
TerminalGaugeCable (mm²)
AC OUT1 (Max current is 70A)6 AWG13.3
AC OUT2 (Max current is 40A)10 AWG5.26

WARNING! AC OUT2 terminal cannot be connected with a load current > 40A, or an error will occur. Ensure AC power is disconnected before connecting to the unit.

AC Input Connection Steps:

  1. Open the AC circuit breaker before making connections.
  2. Remove 12mm insulation from cable ends, shorten conductor to 10mm. Insert into tubular terminal and crimp tightly.
  3. Insert AC input cables according to polarities (PE: yellow-green, L: brown/black, N: blue) and tighten terminal screws. Connect PE protective cable first.
  4. Ensure cables are securely connected.

Figure 4: AC Input/Output Terminal Connections (Refer to manual for diagram).

CAUTION! Appliances like air conditioners require a 2-3 minute restart delay to balance refrigerant gas. Ensure your air conditioner has a time-delay function or this inverter may trigger overload faults.

2.4 PV Connection

CAUTION! Install a separate DC circuit breaker between the inverter and PV modules. Do not ground positive or negative PV module terminals, as this can severely damage the inverter.

WARNING! Exposure to sunlight can generate lethal high voltages. Connect PV terminals to corresponding ports; reversing polarity can damage the inverter. All wiring must be performed by qualified personnel. Use appropriate cable sizes.

GaugeCable (mm²)
10 AWG5.26

PV Module Selection Parameters:

  • Open circuit Voltage (Voc) of PV modules must not exceed max. PV array open circuit voltage of inverter (500Vdc).
  • Open circuit Voltage (Voc) of PV modules should be higher than start-up voltage (80Vdc).
  • PV Array MPPT Voltage Range: 60Vdc~450Vdc.

PV Module Connection Steps:

  1. Open the DC circuit breaker before making PV connections.
  2. Remove 12mm insulation from cable ends, shorten conductor to 10mm. Insert into tubular terminal and crimp tightly.
  3. Use a multi-meter to check polarities (+ → PV+ (red), - → PV- (black)).
  4. Insert PV cables according to polarities and tighten terminal screws.
  5. Ensure cables are securely connected.
  6. PV1 and PV2 can be connected to different panel strings. If connected to the same string, set program 62 to enable PV parallel mode.

Figure 5: PV Terminal Connections (Refer to manual for diagram).

2.5 Battery Connection

The inverter supports 48V nominal voltage lead-acid (AGM or FLD) and lithium batteries.

CAUTION! Install a separate DC over-current protector or disconnect device (recommended 250A) between the battery and inverter.

WARNING! All wiring must be performed by qualified personnel. Use appropriate cable sizes. Ensure AC power is disconnected before connecting batteries. Observe correct polarity. Installation requires care due to high battery voltage.

GaugeCable (mm²)
000 AWG85

Note: For lead-acid batteries, the recommended charge current is 0.3C (C ≤ battery capacity).

Lead-acid Battery Connection Steps:

  1. Unscrew pre-fixed screws on battery poles. Prepare 2 DT terminals.
  2. Remove 12mm insulation from cable ends, shorten conductor to 10mm. Insert into DT terminal and crimp tightly.
  3. Pass battery cable through the bottom shell's installation hole and tighten terminal screws. Ensure correct polarity (BAT+ and BAT-) at both the battery and inverter.
  4. Connect all battery packs as required. A minimum 200Ah capacity battery is suggested.

CAUTION! Do not place anything between the flat part of the inverter terminal and the DT terminal to prevent overheating. Do not apply anti-oxidant substance on terminals before connection. Ensure positive (+) is connected to positive (+) and negative (-) to negative (-) before final DC connection.

Lithium Battery Connection Steps:

Check battery protocol compatibility first. The inverter has two connectors for lithium batteries: an RJ45 port for BMS and a power cable.

  1. Follow the power cable connection steps for lead-acid batteries (Section 2.5.1).
  2. Connect the RJ45 terminal of the battery communication cable to the BMS communication port of the inverter. The communication protocol should be RS485 or CAN.
  3. Insert the other end of the RJ45 cable to the battery's communication port.

Note: If using lithium batteries, ensure the BMS communication cable is connected between the battery and the inverter. For parallel systems, connect the BMS communication cable between the battery and one inverter.

Lithium Battery Communication and Setting:

Set battery type to 'Llb' or 'FEL' in Program 17 (Section 3.3.2). Ensure the lithium battery BMS port connects to the inverter is Pin to Pin. The inverter BMS port pin assignment is as follows:

Pin numberBMS port
1RS485B
2RS485A
3-
4CANH
5CANL
6-
7-
8-

2.6 Meter Connection

The inverter can connect to an external meter at the grid side for accurate grid power and grid-tied function. The inverter's RS485A and RS485B interfaces (part of the BMS interface) are used for meter connection. Ensure the meter model supports the inverter's communication protocol.

2.7 Final Assembly

After connecting all wiring, replace the bottom cover and secure it with the four screws removed earlier.

2.8 Smart Communication Stick Connection (Optional)

The smart communication stick (WiFi) connects to the cloud platform. Insert the stick directly into the COM port. Some models have built-in WiFi monitoring; refer to the solar APP quick configuration guide for setup.

Diagram showing the ANERN FGI-S12000 inverter with WiFi signals connecting to two mobile phones displaying monitoring apps.

Figure 6: Wi-Fi Monitoring Feature.

3. Operation

3.1 Power ON/OFF

Once the unit is properly installed and batteries are connected, press the ON/OFF switch (located on the bottom of the case) to turn on the unit.

3.2 Operation and Display Panel

The front panel features four indicators, four function keys, and an LCD display for operating status and input/output power information.

Close-up of the inverter's LCD display and control buttons. Labels include AC Indicator, Invert Indicator, Charging Indicator, Fault Indicator, LCD Display, ESC Button, Down Button, Enter Button, RGB Light.

Figure 7: Operation and Display Panel.

LED Indicators:

IndicatorStateMessage
AC (Green)Solid OnMains power is normal and in operation.
FlashingMains power is normal but not yet in operation.
OffMains power is abnormal.
Invert (Yellow)Solid OnOutput powered by battery or PV in battery mode.
OffOther states.
Charging (Yellow)Solid OnBattery is in float charging.
FlashingBattery is in constant voltage charging.
OffOther states.
Fault (Red)Solid OnFault occurs in the inverter.
FlashingWarning condition occurs in the inverter.
OffInverter is working properly.

Function Buttons:

ButtonDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

3.3 LCD Display Icons and Information

The LCD displays various icons and information related to battery, AC input, PV input, output, and system parameters. The display cycles through information by pressing UP or DOWN. If no operation for a long time, it defaults to daily PV power generation.

Close-up of the inverter's LCD display showing operational data including battery voltage, AC input/output, PV power, and frequency.

Figure 8: Detailed LCD Display.

Key Display Areas:

  • Battery Information: Battery icon, type (AGM, FLD, USER, Li-ion), charging period (CC, CV, FLOAT), voltage, charging/discharging current.
  • AC Input Information: UPS/APP input mode, AC input voltage and frequency.
  • PV Input Information: PV input icon, PV power, voltage, current (PV1 and PV2 rotate).
  • Output Information: Output voltage (V), apparent power (VA/kVA), active power (W/kW), output frequency.
  • Battery Capacity: Bar graph indicating charge level.
  • Load Capacity: Bar graph indicating load level, overload icon.
  • AC OUTPUT2 Information: Second AC output icon, AC output 2 voltage.
  • Parameter Query, Function Setting or Fault/Alarm Information: System information, function settings, fault/alarm indicators.

Battery Icon Display in Battery Mode (Lead-acid):

Load PercentageBattery VoltageDisplay
Load >50%< 44.584V[25%]
44.584 ~ 46.74V[25%, 50%]
46.74 ~ 48.896V[25%, 50%, 75%]
> 48.896V[25%, 50%, 75%, 100%]
50% > Load > 20%< 47.18V[25%]
47.18 ~ 49.336V[25%, 50%]
49.336 ~ 51.492V[25%, 50%, 75%]
> 51.492V[25%, 50%, 75%, 100%]
Load < 20%< 48.48V[25%]
48.48 ~ 50.636V[25%, 50%]
50.636 ~ 52.792V[25%, 50%, 75%]
> 52.792V[25%, 50%, 75%, 100%]

3.4 LCD Settings (Program List)

Press and hold the ENTER button for 2 seconds to enter setting mode. Use UP/DOWN to select programs, then ENTER to confirm or ESC to exit.

ProgramDescriptionSetting Option
01Output voltage230V (default), adjustable: 220V, 230V, 240V
02Output frequency50Hz (default), adjustable: 50Hz, 60Hz. Takes effect immediately in standby or grid mode.
03Output source priorityGrid first (default), Solar first, MKS (Generator priority)
04Input modeAPP (Appliance, default), UPS (Computer/devices), GEN (Generator)
05Charger source priorityPNG (PV and Grid, default), OPV (Only PV), PVF (PV first)
06Grid charging current60A (default), adjustable: 2-160A in steps.
07Maximum charging current100A (default), adjustable: 2-160A in steps. Follows BMS data if connected.
08Menu DefaultON (default): Returns to first page after 1 min inactivity. OFF: Stays on current page.
09Auto restart when overload occursON (default)
10Auto restart when over temperature occursON (default)
11Main input cut warningON (default): Buzzer sounds for 5s if grid input lost. OFF: No sound.
12Energy-saving modeOFF (default). ON: In battery mode, if load < 25W/100VA, output stops then resumes. If load > 35W/120VA, continuous output.
13Overload transfer to bypassOFF (default). ON: In PBG/MKS mode, overload immediately transfers to bypass (grid power output).
14Silent mode settingOFF (default). ON: Buzzer silent for alarms/faults. Button sound not affected.
15Battery return to grid voltage pointDefault 46V (AGM/FLD), 47.6V (LIB/CUS), 48V (FEL). Adjustable range varies by battery type.
16Switching back to battery mode voltage pointsDefault 52V (AGM/FLD), 54.4V (LIB/CUS), 53.2V (FEL). Adjustable range varies by battery type.
17Battery typeAGM (default), Flooded, Lithium (Ternary Lithium Battery), FEL (Lithium iron), User-Defined.
18Battery low voltage pointDefault 44V (AGM/FLD), 47.6V (LIB/CUS), 48V (FEL). Adjustable range varies by battery type. Follows BMS data if connected.
19Battery shutdown voltage pointDefault 42V (AGM/FLD), 46V (LIB/CUS), 42V (FEL). Adjustable range varies by battery type. Follows BMS data if connected.
20Constant voltage mode voltage point settingDefault 56.4V (AGM), 58V (FLD), 56.4V (LIB/CUS), 55.2V (FEL). Adjustable range varies. Must be higher than float charge set point. Follows BMS data if connected.
21Floating charge mode voltage point settingDefault 54V (AGM/FLD), 55.2V (CUS/LIB), 54.4V (FEL). Adjustable range varies. Must be lower than constant voltage point. Follows BMS data if connected.
22Grid low voltage point settingAPP/GEN mode: 154V (default), range 90-154V. UPS mode: 185V (default), range 170-200V.
23Grid high voltage point settingAPP/GEN mode: 264V (default), range 264-280V. UPS mode: Cannot be changed.
24Automatic turn off backlightON (default): Backlight turns off after 1 min inactivity.
25Inverter soft start settingOFF (default). ON: Output gradually increases. OFF: Output increases directly. Only in single-machine operation mode.
26Reset factory settingRestores all settings to factory defaults. Applied in mains and standby modes.
29Battery Disconnection AlarmOFF (default): No alarm when battery disconnected.
31Equalization Voltage Point Setting58.4V (default), range [48, 60V].
32Equalization Charging Time SettingOFF (default). Range [5, 900] minutes, 5 min step. Charges until voltage rises to equalization voltage, then constant voltage.
33Equalization Delay Time Setting120 minutes (default), range [5, 900] minutes, 5 min step. Extends equalization if voltage not reached.
34Equalization Interval Time Setting30 days (default), range [1, 90] days, 1 day step. Starts equalization when interval reached during float phase.
35Enable Equalization ImmediatelyOFF (default). ON: Activates equalization immediately during float charging if battery connected.
36Grid-tie inverter functionSet whether inverter feeds to grid (INT) or controls feeding power based on meter data (MET). Behavior varies by PGB/GPB/MKS modes.
37Max Grid Tie Power12.0kW (default), range [0, 12.0]kW, 0.5kW step. Uses electricity meter data if GTI is 'MET'.
38Battery dual output low voltage shutdown point48V (default), range [44, 60]V. Secondary output turns off if battery voltage drops below set point, turns on if voltage rises +2V per cell.
39Battery dual output durationOFF (default). Range [5, 900] minutes. Secondary output turns off if discharge time reaches set point. FUL for unlimited.
40Dual output battery mode cut-off SOC20 (default), range [5, 90] and OFF. Secondary output turns off if battery SOC is lower than set value, turns on if SOC is 5% higher.
44BMS Communication FunctionOFF (default). Set to specific BMS protocol (CVT, PYL, GRO, VOL, IRO, PAC) to communicate with lithium battery BMS. Alarm 56 if abnormal.
45BMS IDAuto (AtO) (default), or numerical [0, 15] (A-F for 10-15). System polls IDs until correct response, then locks.
46Low SOC Shutdown20 (default), range [5, 50]. Inverter shuts down if lithium battery SOC is low (Alarm 68). Can be set to OFF.
47High SOC to Battery90 (default), range [10, 100]. In PBG mode, inverter switches to battery mode when lithium battery SOC reaches set value. Can be set to OFF.
48Low SOC to Grid50 (default), range [10, 90]. In PBG mode, inverter switches to grid mode when lithium battery SOC is low. Can be set to OFF.
61Battery Max. Discharge CurrentOFF (default). Range [10, 220A], 5A step. Limits discharge current. Fault 14 if overcurrent for 5s.
62PV Parallel ModeOFF (default): PV1/2 connected to different PV strings. ON: PV1/2 connected to same PV string.

4. Maintenance

Regular maintenance ensures the longevity and optimal performance of your ANERN Hybrid Solar Inverter. Always disconnect all power sources (AC, PV, and Battery) and wait at least 5 minutes before performing any maintenance to avoid electrical hazards.

4.1 General Checks

  • Periodically inspect all wiring connections for tightness and signs of corrosion.
  • Ensure the inverter's ventilation openings are clear of dust and debris to maintain proper heat dissipation.
  • Check the battery terminals for corrosion and clean if necessary.
  • Monitor the LCD display for any fault or alarm codes and address them promptly.

4.2 Battery Equalization

The equalization function helps reverse negative chemical effects like stratification and removes sulfate crystals in lead-acid batteries, which can reduce overall capacity. This mode should NOT be activated when using lithium batteries.

How to Apply Equalization Function (Lead-acid batteries only):

You can enable battery equalization via LCD setting Program 32 (setting time) or Program 35 (immediate equalization). Configure the following programs:

  • Program 31: Equalization Voltage Point Setting
  • Program 32: Equalization Charging Time Setting
  • Program 33: Equalization Delay Time Setting
  • Program 34: Equalization Interval Time Setting
  • Program 35: Immediate Equalization Mode Activation

When to Equalize:

In the float stage, when the set equalization interval is reached, or if immediate equalization is activated, the controller will enter the Equalize stage.

Figure 9: Battery Equalization Charging Cycle (Refer to manual for diagram).

During equalization, the controller charges the battery until it reaches the equalization voltage, then maintains constant voltage. The battery remains in this stage until the set equalization time is reached. If the voltage doesn't rise to the equalization point within the set time, the controller extends the equalization time. If the voltage is still below the equalization voltage after the extended time, the controller stops equalization and returns to the float stage.

5. Troubleshooting

This section provides guidance for identifying and resolving common issues. The inverter indicates problems via fault codes (constant red LED, LCD display code) or alarm codes (flashing red LED, LCD display code).

5.1 Fault Reference Code

If a fault occurs, the fault indicator (red LED) is always on, and the buzzer sounds for 10 seconds then stops. The system attempts to restart automatically. If it fails after six restarts, the machine remains in fault status. Power off the unit completely (off the screen) or wait 15 minutes to restart. Contact the manufacturer for abnormal situations.

LCD display showing 'FAULT 18' with a warning triangle icon.

Figure 10: Example Fault Display.

Fault Code Sheet:

Fault CodeMeaningRelevant ActionTrigger ConditionsResume Conditions
1Bus boost failTurn fault modeGrid soft start process starts but bus voltage does not reach set valueRestore after reaching the set voltage for 15 seconds
2Bus over voltageTurn fault modeBus voltage is higher than set valueRestore after reaching the set voltage for 15 seconds
3Bus below voltageTurn fault modeBus voltage is lower than set valueRestore after 15 seconds
4Battery over currentTurn fault modeBattery current is higher than set valueCannot restore
5System over temperatureTurn fault modeTemperature is higher than set value or fan is not connectedRestore after temperature lower than set value and fan connected for 15 minutes
6Battery over voltageTurn fault modeBattery voltage is higher than set valueRestore after reaching the set voltage for 15 seconds
7Bus soft start failedTurn fault modeBattery soft start process starts but the bus voltage has not reached set valueRestore after reaching the set voltage for 15 seconds
8Bus short circuitTurn fault modeBus voltage is lower than set valueCannot restore
9Inverter soft start failedTurn fault modeInverter soft start process starts but the inverter voltage has not reached set valueRestore after reaching the set voltage for 15 seconds
11Inverter under voltageTurn fault modeThe inverter voltage is lower than the set value in battery modeRestore after reaching the set voltage for 15 seconds
12Inverter short circuitTurn fault modeInverter voltage is less than the set value and current is higher than the set valueRestore after reaching the set voltage for 15 seconds
13Inverter negative powerTurn fault modeThe inverter power is negative and exceeds the set value for a period of timeRestore after reaching the set voltage for 15 seconds
14Over loadTurn fault modeThe load current is higher than the set valueRestore after reaching the set voltage for 15 seconds
17Program updatingTurn fault modeInverter updating or OTARestore after updating
18PV reverse connectionTurn fault modePV reverse connectionRestore after connecting correctly for 15 seconds
26BMS faultTurn fault modeError code in BMS message.Restore after BMS fault resolved
29Inverter load abnormalTurn fault modeAbnormal inverter load leads to abnormal voltageRestore after voltage returning normal for 15 seconds

5.2 Alarm Reference Code

If an alarm occurs, the inverter does not enter fault mode. The red LED flashes, and the LCD displays the alarm code. The buzzer sounds every second for 1 minute, then stops.

LCD display showing 'ALA 52' with a warning triangle icon.

Figure 11: Example Alarm Display.

Alarm Code Sheet:

Alarm CodeMeaningRelevant ActionTrigger ConditionsResume Conditions
50Battery openAlarmBattery disconnected for no more than 10 minutesRestore after battery connected for 2 minutes
51Battery under voltageAlarm, battery low voltage shutdown or cannot power onBattery voltage is lower than BAU set valueRestore after the battery voltage exceeding the BAU set value by 2V
52Battery low voltageAlarmBattery voltage is lower than BAL set valueRestore after the battery voltage exceeding the BAL set value by 2V
53Battery charge short circuitAlarm, battery does not chargeBattery voltage is less than 24V and the charging current exists.Restore after the short circuit is eliminated.
56BMS lossAlarmCommunication failure after BMS communication function is enabledRestore after communication function disabled or communication success
58Fan errorAlarm, fan operation in full speedNo fan speed signal detectedRestore after fan speed signal detected
59EEPROM errorAlarmEEPROM read/write exceptionCannot restore
60OverloadAlarmThe mains current/battery discharge current/load power is higher than the rated value.Restore after the mains current/battery discharge current/load power is less than the rated value.
62PV energy weakAlarm, Turn off the PV output to the load, but keep the PV charging the batteryWhen the battery is not connected, the bus voltage is lower than the set valueRestore after battery connected or grid connected, or 10 minutes later.
68Battery under SOC shutdownAlarm, turn to standby modeBMS reports SOC lower than BSU set valueDisable low SOC shutdown function, disable BMS communication, or SOC is higher than set value by 5%.
69Battery below SOC warningAlarm, if it is in standby mode, it will remain in standby mode.Lithium battery SOC is lower than set value+5% (grid mode or battery mode), lower than set value+10% (standby mode)Disable low SOC shutdown function, disable BMS communication, or SOC is higher than set value by 10%.
72Battery can not startupAlarmDuring standby, battery voltage is lower than the allowed startup voltageRestore after the battery voltage is higher than the allowed startup voltage
77Grid power is unstableAlarmLost of grid power three times within 5 minutesRestore after 5 mins
78Meter LossAlarmWhen the grid power is connected and the grid connected inverter function is set to Meter, the meter communication is disconnectedRestore after grid is disconnected, or detection device is not set to Meter, or meter communication restore

5.3 General Troubleshooting

ProblemFault EventTrigger ConditionsWhat to do
LED screen display fault code 5Over temperaturePFC temperature exceeds protection threshold for >20s, or Alarm 58 lasts for >5s.Check if fan is connected or wiring is loose. If fan not connected for >5 mins, machine reports fault code 5.
LED screen display fault code 12Inverter short circuitIn battery/standby mode, inverter voltage < 80V and current > 30A, response within 100-120ms.Check for short circuit at output terminals. Verify inverter voltage and current meet triggering conditions.
LED screen display fault code 58Fan malfunctionAny fan rotating < 8 times within 2 seconds.Check fan connection/loose wires. If connected, check fan detection circuit (soldering) or fan itself.
Unable to startBatteryRequires voltage ≥11.5V/N to start in battery mode. Common reasons: improper calibration or insufficient battery voltage.Check battery voltage sampling and calibration. Use multimeter to measure battery terminals. Configure battery voltage according to model to prevent capacitor explosion.
Utility powerCheck for short circuits at mains terminal. Check for wiring errors (e.g., mains input to output terminals).
PVCheck if PV input voltage is too close to critical threshold. For low voltage versions, check main control software compatibility.
PV not chargingConnecting wrong battery voltage can damage auxiliary power supply on PV side, causing power loss and inability to communicate with main control.

6. Specifications

The following table outlines the technical specifications for the ANERN Hybrid Solar Inverter.

Comparison table for FGI-S6500 and ECO-6200 models, showing Rated Output Power, Max PV Output Power, Number of MPPTs, IGBT, Electrolysis, Capacitor.

Figure 12: Model Comparison (FGI-S6500 vs ECO-6200).

CategoryParameterValue
AC InputRated Input Voltage (VAC)220/230/240; L+N+PE
Voltage Range (VAC)90~280 (APP mode); 170~280 (UPS mode)
Frequency (Hz)50/60 (Auto Adaptive)
AC OutputRated Capacity (kW)12 (Max current of AC output 1 is 70A. Max current of AC output 2 is 40A)
Surge Power (kVA)24
Voltage (VAC)220/230/240
Power Factor (PF)1
Frequency (Hz)50/60±0.1%
Switch Time (ms)10 (APP/UPS mode) / 20 (GEN mode)
WaveFormPure Sine Wave
Overload Capacity (Battery Mode)1min@ 102%~125% load; 10s@ >125% load
Max. Efficiency (Battery Mode)94%@48V
Charger (PV/AC)Solar Charger TypeMPPT
Max PV Input Current/PowerSingle PV Input: 27A/9000W; Dual PV Input: 22.5*2A/15000W
MPPT Range@Operating Voltage (VDC)60~450
PV Start-up Voltage80Vdc
Max PV Open Circuit Voltage (VDC)500
Max PV Charge Current (A)160
Max AC Charge Current (A)160
Max. Charge Current (PV+AC) (A)160
BatteryNormal Voltage (VDC)48
Battery TypeLithium and Lead-acid
General DataHMILCD
InterfaceRS232/RS485/CAN
MonitoringWiFi(Optional)
Ingress ProtectionIP21
Operating Temperature-10°C~60°C
Relative Humidity5%~95% (Non-condensing)
Storage Temperature-15°C~60°C
Max. Operating Altitude4000m (Derating above 1000m)

Note: Updates to the content and version of this manual will not be notified separately.

7. User Tips

  • Battery Charging Algorithm: When using the 'CUS' battery type, carefully review and potentially adjust the charging algorithm settings. Some users have reported discrepancies where the main charging voltage (CV mode) might be set to a point typically used for the next stage (Float mode). Ensure your settings align with your battery manufacturer's recommendations to prevent issues.
  • System Monitoring: Utilize the optional WiFi module and mobile app/website monitoring to keep track of your PV system's status, performance, and any alerts in real-time.
  • Cable Sizing: Always adhere to the recommended cable sizes for AC input/output, PV, and battery connections to ensure safety and optimal performance. Incorrect cable sizing can lead to inefficiencies or hazards.
  • Appliance Compatibility: Be aware that appliances like air conditioners may require a time-delay function for safe operation with the inverter, especially after power interruptions. Consult appliance manufacturers if unsure.

8. Warranty and Support

The ANERN Hybrid Solar Inverter comes with a 2-year warranty.

For technical support, warranty claims, or any questions not covered in this manual, please contact ANERN customer service or your local distributor. When contacting support, please have your product model (FGI-S12000 Series) and any relevant fault/alarm codes ready.

A detailed user manual in PDF format is available for download: ANERN MPPT Solar Inverter User Manual (PDF).

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.