1. Important Safety Instructions
Warning: It is essential to read, understand, and adhere to all safety instructions provided in this document. Failure to comply with safety regulations may result in property damage or personal injury.
Basic Guidelines
- Before using the equipment, carefully review all relevant sections of the device, battery, and instruction manual for all guidance and warning signs.
- Caution: To reduce the risk of injury, if you choose to use lead-acid batteries, please charge only deep cycle lead-acid batteries. Other types of lead-acid batteries may rupture, causing personal injury.
- This product does not contain user-serviceable parts. Do not disassemble the equipment. When maintenance or cleaning is required, take it to a qualified service center. Improper reassembly may pose risks of short-circuiting and fire. If any panel displays a malfunction, do not remove the front panel or operate the product. All operating procedures must be performed by trained professionals.
- To reduce the risk of electric shock, disconnect all wiring before performing any maintenance and cleaning. Switching off the main unit alone does not eliminate the risk of electric shock.
- Caution: Only qualified personnel should assemble the equipment with the battery.
- Charging frozen batteries is prohibited.
- Exercise extreme caution when using metal tools or placing them around the battery. Dropping tools can generate sparks or cause unpredictable risks such as short-circuiting the battery or other electronic components, potentially leading to explosions.
- When disconnecting AC or DC terminals, strictly follow the installation steps as outlined in the instruction manual's installation section.
- Before using this product, read the provided instructions to familiarize yourself with safety features and operating instructions. This product is designed and tested according to international standards. The equipment must be used exclusively for its intended purpose.
Installation Safety
- Do not use this product in areas where there is a risk of gas or dust explosions.
- Consult with the battery manufacturer's relevant literature to ascertain the compatibility of this product with the battery. Always adhere to the safety instructions provided by the battery manufacturer.
- This is a safety-class product equipped with a protective grounding terminal. Continuous protective grounding must be provided by the AC input/output terminals.
- Grounding Instructions: The inverter/charger should be connected to a permanent grounding wire system to ensure full compliance with local requirements and regulations for installing the inverter. When grounding protection may have been compromised, the product must be shut down to prevent accidental electric shock.
- To ensure optimal operation of the inverter/charger, adhere to the required specifications and select appropriate cable sizes, which are crucial for the correct operation of the inverter/charger.
- Before connecting to the mains power, ensure that the available power supply meets the parameters specified in the product manual.
- Do not short-circuit the AC output and DC input. Do not connect the mains power when the DC output is short-circuited.
- Ensure that the equipment is used in conditions compliant with standards. Do not operate the product in moist or dusty environments. Ensure there is sufficient clearance space around the product and check that ventilation holes are not blocked.
- Ensure that the required system voltage does not exceed the capacity of the product.
Transportation and Storage
- Ensure that the power and battery cables are disconnected before storing or transporting the product.
- If the equipment is not in its original packaging during transportation, any transport damage is not the responsibility of the manufacturer.
- Store the product in a dry environment, with storage temperature between -25°C to 60°C.
- Refer to the battery manufacturer's manual for information on battery transportation, storage, charging, recharging, and disposal.
Please follow these instructions diligently to ensure safe installation, operation, transportation, and storage of the product.
2. Product Overview
The POW-SunSmart series is a new type of solar energy storage inverter. It integrates solar charging, utility charging and energy storage with AC sine wave output. It adopts DSP control and utilizes advanced algorithms to deliver fast response, high reliability, and industrial-grade performance. This series is ideal for demanding industrial applications.
2.1 Features
- Supports lead acid battery and li-ion battery connections.
- With a dual activation function when the li-ion battery is dormant; either mains/photovoltaic power supply access can trigger the activation of the li-ion battery.
- Support single-phase pure sine wave output.
- Supports six different voltage levels of 100/105/110/115/120/127Vac per phase.
- Supports two solar inputs and simultaneous tracking of two solar maximum power charging/loading capacity functions.
- Dual MPPT with 99.9% efficiency and maximum 25A current in a single circuit, perfectly adapted to high power modules.
- 2 charging modes are available: solar only, grid/solar hybrid charging.
- With the time-slot charging and discharging setting function, you can set the time period for cutting in/out of mains charging and switch the time period between battery discharging and mains bypass power supply mode.
- Energy saving mode function to reduce no-load energy losses.
- With two output modes of utility bypass and inverter output, with uninterrupted power supply function.
- LCD large screen dynamic flow diagram design, easy to understand the system data and operation status.
- 360° protection with complete short circuit protection, over current protection, over under voltage protection, overload protection, backfill protection, etc.
- Support CAN, USB, and RS485 communication.
2.2 System Connection Diagram
The diagram below shows the system application scenario of this product. A complete system consists of the following components:
- PV modules: converts light energy into DC energy, which can be used to charge the battery via an inverter or directly inverted into AC power to supply the load.
- Utility grid or generator: connected to the AC input, it can supply the load and charge the battery at the same time. The system can also operate generally without the mains or generator when the battery and the PV module power the load.
- Battery: The role of the battery is to ensure the regular power supply of the system load when the solar energy is insufficient and there is no mains power.
- Home load: Various household and office loads can be connected, including refrigerators, lamps, televisions, fans, air conditioners, and other AC loads.
- Inverter: The energy conversion device of the whole system.
The actual application scenario determines the specific system wiring method.

2.3 Production Overview

The inverter features various terminals and indicators for comprehensive system management:
| No. | Item | No. | Item |
|---|---|---|---|
| 1 | LED Indicators | 14 | Load Ground Terminal |
| 2 | LCD Screen | 15 | Grid Input Ground Terminal |
| 3 | Touchable Keys | 16 | Transmitter-PLC |
| 4 | WIFI Port | 17 | AFCI |
| 5 | RS485 Port | 18 | Parallel Port A |
| 6 | External CT Port | 19 | Parallel Port B |
| 7 | CAN Port | 20 | Dry Contact |
| 8 | PV1 Terminals | 21 | USB-B Port |
| 9 | PV2 Terminals | 22 | Battery Terminal |
| 10 | Utility Terminals (L1+L2+N)+Breaker | 23 | Battery Circuit Breaker |
| 11 | Load Terminals (L1+L2+N)+Breaker | 24 | PV Circuit Breaker |
| 12 | Generator Terminals (L1+L2+N)+Breaker | 25 | ON/OFF Switch |
| 13 | Generator Ground Terminal | 26 | USB-A Port |
2.4 Dimension Drawing




3. Installation
3.1 Select the Mount Location
POW-SunSmart series can be used outdoors (protection class IP65). Please consider the followings before selecting the location:
- Choose a solid wall to install the inverter.
- Mount the inverter at eye level.
- Adequate heat dissipation space must be provided for the inverter.
- Installation location should be a cool and ventilated place, under a photovoltaic panel or under the eaves, to avoid direct sunlight exposure.
- The ambient temperature should be kept between -25°C and 60°C (-13°F and 140°F) to ensure optimal operation.
DANGER
- Do not install the inverter where highly flammable materials are nearby.
- Do not install the inverter in potential explosive areas.
- Do not install the inverter with lead-acid batteries in a confined space.
CAUTION
- Do not install the inverter in direct sunlight.
3.2 Mount the Inverter
Drill four mounting holes in the wall with an electric drill according to the specified dimensions. Then insert four M8*60 expansion bolts into the holes.
3.3 Remove the Terminal Cover & Anti Insect Net
Using a screwdriver, remove the fan shroud and open the cover.
NOTICE
- When using the device in areas with poor air quality, the fan cover is easily blocked by air particles. Please disassemble and clean the fan regularly to avoid affecting the inverter's internal air flow rate, which may trigger the device over-temperature protection fault (19/20 faults) affecting the power supply and the service life of the inverter.
4. Connection
4.1 Split-Phase Mode
The inverter supports split-phase output, providing 120V (L-N) and 240V (L1-L2) AC output. The default L-N voltage is 120Vac, and the default L1-L2 voltage is 240Vac.
4.2 Cable & Circuit Breaker Requirement
PV Input
| Model | Cable Diameter | Max. PV Input Current | Circuit Breaker Spec |
|---|---|---|---|
| 8KW Model | 6mm²/10AWG | 25A | 2P-25A |
| 10KW Model | 6mm²/10AWG | 25A | 2P-25A |
| 12KW Model | 6mm²/10AWG | 25A | 2P-25A |
Battery
| Model | Cable Diameter | Max. Battery Current | Circuit Breaker Spec |
|---|---|---|---|
| 8KW Model | 53mm²/0AWG | 200A | 2P-250A |
| 10KW Model | 67mm²/00AWG | 230A | 2P-250A |
| 12KW Model | 67mm²/00AWG | 270A | 2P-250A |
AC Input
| Model | Cable Diameter | Circuit Breaker Spec |
|---|---|---|
| 8KW Model | 13mm²/6AWG (L1/L2/N) | 3P-63A |
| 10KW Model | 13mm²/6AWG (L1/L2/N) | 3P-63A |
| 12KW Model | 13mm²/6AWG (L1/L2/N) | 3P-63A |
Generator Input
| Model | Cable Diameter | Circuit Breaker Spec |
|---|---|---|
| 8KW Model | 13mm²/6AWG (L1/L2/N) | 3P-63A |
| 10KW Model | 13mm²/6AWG (L1/L2/N) | 3P-63A |
| 12KW Model | 13mm²/6AWG (L1/L2/N) | 3P-63A |
AC Output
| Model | Cable Diameter | Circuit Breaker Spec |
|---|---|---|
| 8KW Model | 13mm²/6AWG (L1/L2/N) | 3P-63A |
| 10KW Model | 13mm²/6AWG (L1/L2/N) | 3P-63A |
| 12KW Model | 13mm²/6AWG (L1/L2/N) | 3P-63A |
NOTICE
The wire diameter is for reference only. If the distance between the PV array and the inverter or between the inverter and the battery is long, using a thicker wire will reduce the voltage drop and improve the performance of the system.
4.3 GRID & LOAD & GEN Connection
Connect the live, neutral and ground wires according to the cables' position and order shown in the diagram below.
4.4 Battery Connection
Connect the positive and negative cable of the battery according to the diagram below.
DANGER
- Before connecting battery, the circuit breaker must be opened to avoid the risk of electric shock and must not be operated with electricity.
- Make sure that the positive and negative terminals of the battery are connected correctly and not reversed, otherwise the inverter may be damaged.
- Please check that the cable used is sufficient for the requirements, too thin, poor quality cables are a serious safety hazard.
4.5 PV Connection
Connect the positive and negative wires of both PVs in the cable locations and sequence shown in the diagram below. The positive wire runs through the AFCI unit.
DANGER
- Before connecting PV, the circuit breaker must be opened to avoid the risk of electric shock and must not be operated with electricity.
- Please make sure that the open circuit voltage of the PV modules in series does not exceed the maximum open-circuit voltage of the inverter (the value is 550V), otherwise the inverter may be damaged.
Transmitter-PLC Device
The APsmart Rapid Shutdown System Transmitter-PLC is part of a rapid shutdown solution when paired with APsmart RSD-D, a PV module rapid shutdown unit. While powered on, the Transmitter-PLC sends a signal to the RSD-D units to keep their PV modules connected and supplying energy. RSD-D units automatically enter rapid shutdown mode when the Transmitter-PLC is switched off and resume energy production when power is restored to the Transmitter-PLC.
4.6 Dry Contact Connection
Use a small screwdriver to push back the direction indicated by the arrow, then insert the communication cable into the dry contact port. (Communication cable diameter 0.2~1.5mm²)
Dry contact port with 3 functions:
- RSD power supply
- Temperature sampling (reserved)
- Generator remote start/stop
4.7 Grounding Connection
Please make sure the grounding terminal connects to the Grounding Busbar.
NOTICE
- The grounding cable should have a diameter of not less than 4mm² and be as close as possible to the grounding point.
4.8 Inverter Start
After ensuring that the wiring is reliable and the wire sequence is correct, follow the power-on sequence below to start the inverter safely:
- Close the circuit breaker of the battery.
- Press the rocker switch on the bottom of inverter, the screen and indicators light up to indicate that the inverter has been activated.
- Sequential close of the circuit breakers for PV, AC input and AC output.
- Install the terminal protection cover in place.
- Start the loads one by one in order of power from small to large.
5. Operation
5.1 Operation and Display Panel
The operation and display panel includes 1 LCD screen, 3 indicators, and 4 touchable keys.
| Touchable Keys | Description |
|---|---|
| Enter/exit the setting menu | |
| Go to the next selection | |
| Go to the previous selection | |
| Confirm/Enter the selection in setting menu |
| Indicators | Color | Description |
|---|---|---|
| AC/INV | Yellow | Steady on: The grid output with load Flash: The inverter output with load |
| CHARGE | Green | Steady on: Charging is complete Flash: Charging is underway |
| FAULT | Red | Flash: An alarm or fault event occurred |
5.2 Display Panel
The display panel provides real-time information through various icons:
| Icon | Description | Icon | Description |
|---|---|---|---|
| Solar panel | Load | ||
| Battery | Grid or Generator | ||
| Home | Home page button | INVERTER | Inverter is working |
| History | History data | Setting | Setting |
| 0:0:0 | Local time | The buzzer On/Off | |
| Indicators that machine is currently in energy-saving mode. | The energy direction | ||
| UPS | UPS load (connected to inverter load port) | HOME | Home load (connected to grid port) |
5.3 View Real-Time Data
On the LCD home screen, click the inverter icon, battery icon, mains icon, load icon and photovoltaic icon to view the real-time data of the machine.
System Data
| NO. | Item | NO. | Item |
|---|---|---|---|
| 1 | Machine state | 11 | SN code |
| 2 | MCU1 version | 12 | Minor version |
| 3 | LCD version | 13 | Rated power |
| 4 | MCU2 version | 14 | RS485 Address |
| 5 | Customer ID | 15 | External Temperature |
| 6 | Inverter Temperature | 16 | PV Temperature |
| 7 | Transformer temperature | 17 | L1 Voltage |
| 8 | L1 Current | 18 | L2 Voltage |
| 9 | L2 Current | 19 | Positive busbar voltage |
| 10 | Negative busbar voltage | 20 | Total busbar voltage |
Battery Data
| NO. | Item | NO. | Item |
|---|---|---|---|
| 1 | SOH | 6 | Discharge current |
| 2 | SOC (Percentage of remaining battery capacity) | 7 | BMS protocol |
| 3 | Battery voltage | 8 | Battery type |
| 4 | Charge current | 9 | Battery Charge Status |
| 5 | Battery power (Battery charging and discharging power) |
Grid Data
| NO. | Item | NO. | Item |
|---|---|---|---|
| 1 | L1 Voltage V | 7 | L2 Voltage |
| 2 | L1 Current A | 8 | L2 Current |
| 3 | L1 active power | 9 | L2 active power |
| 4 | L1 apparent power | 10 | L2 apparent power |
| 5 | Frequency | 11 | Grid charging current |
| 6 | Today's on-grid energy |
Click on the history button in the menu bar below to access the historical data and view various types of historical data.
Today Data
| NO. | Item | NO. | Item |
|---|---|---|---|
| 1 | Battery charging energy | 5 | Grid charging energy |
| 2 | Battery discharging energy | 6 | Load consumption energy from grid |
| 3 | Solar generated energy | 7 | On Grid Energy |
| 4 | Load consumption energy |
History
| NO. | Item | NO. | Item |
|---|---|---|---|
| 1 | PV generation last seven days history | 4 | Mains charge energy for last 7 days |
| 2 | Battery charging energy for last 7 days | 5 | Load consumption energy for last 7 days |
| 3 | Battery discharge for last 7 days | 6 | Load consumption from the grid for last 7 days |
Energy Statistics
| NO. | Item | NO. | Item |
|---|---|---|---|
| 1 | Total battery charging energy | 5 | Total battery discharging energy |
| 2 | Total solar generated energy | 6 | Total load consumption energy |
| 3 | Total grid charging energy | 7 | Total load consumption energy from grid |
| 4 | Total on grid energy |
Historical Faults
This section would display historical fault information if available.
5.4 Setting
Operating instructions: Click on the settings in the menu bar at the bottom of the screen to enter the setup interface, including the basic settings, work mode settings, battery settings, grid settings, advanced settings of the five major setup items.
5.4.1 Basic Setup - Display Setup
| Parameter Meaning | Description |
|---|---|
| Language | Currently supported languages include English, Italian, German, Spanish, and Chinese. |
| RS485 Address | Display and current inverter RS485 address, range 1-255 |
| Screen always on | Selectable whether the screen is always on or not |
| Beep | You can choose whether to enable the Beep alarm |
| Screen brightening time | Setting range 0-60S |
| Backlight brightness | 0-100% |
5.4.1 Basic Setup - Time Setup
Set the current Year, Month, Day, Hour, Minute, and Second.
5.4.1 Basic Setup - Password Setting
Password is required to access the Grid Settings and Advanced Settings. Default password is "00000". Password setting value range: 0-65535.
5.4.2 Work Mode Setup
| Parameter Meaning | Option | Description |
|---|---|---|
| Hybrid grid mode | On grid | Direct grid connection of excess PV energy. |
| Limit power to ups | UPS load backflow prevention, photovoltaic or battery energy is only for the ups load, excess energy will not be connected to the grid. | |
| PV energy manage | Limit power to home | Home load anti-backflow, solar or battery energy is only supplied to the home load, excess energy will not be connected to the grid. |
| AC Coupling | On-grid inverter connect to the hybrid inverter "GEN port" or Grid side. | |
| First to load | PV power supply logic: load-charge-grid connection | |
| First to charging | PV power supply logic: charge-load-grid connection | |
| First to grid | PV power supply logic: load-grid connection-charge | |
| Grid charging enable | Selectable grid participation in battery charging | |
| Battery energy manage | Standby | The battery does not discharge, and the battery is discharged only when the working state is off the grid. |
| Battery to ups load | When the PV power is less than the UPS load power, the battery discharge is added. | |
| Battery to home load | The battery can supply the power to Home load. | |
| Battery to grid sell | The battery can supply the power to grid. | |
| Parallel mode | Stand-alone | Single inverter |
| Parallel | The grid type setting is effective when set to split-phase. | |
| Grid type | Single Phase | When the grid type is single-phase, L1-L2 is Europe voltage, L1-L2 is 230V. Note 1: Parallel operation is not supported when single-phase mode is selected. Note 2: In single-phase mode (230V), it is recommended to connect L1 to the live wire and L2 to the neutral wire for standard wiring practice. |
| Three Phase | When the grid type is three-phase, the phase difference between L1 and L2 is 120° and the output voltage is 120V/208V. | |
| Split Phase | When the grid type is split-phase, the phase difference between L1 and L2 is 180°, and the grid voltage is 120V/240V. Please select according to the actual grid type. | |
| Output phase voltage | Settable: 100V,105V,110V,115,120V,127V |
5.4.2 Work Mode Setup - Peak Shaving
| Parameter Meaning | Description |
|---|---|
| Time charging/discharging enable | Select whether to turn on timed charging and discharging |
| Start/End Time | Setting the time period for timed charging and discharging |
| Stop SOC | Setting the battery charging cut-off SOC value and the cut-off SOC value for discharging during the timed charging and discharging time period (during BMS communication) |
| Stop Volt | Setting the battery charging cut-off voltage value and discharging cut-off voltage value during the timed charging and discharging time period (when the BMS is not communicating) |
| Max Power | Setting the battery charging power and discharging power during the timed charging and discharging time period |
5.4.3 Battery Setup - Battery Type
| Parameter Meaning | Option | Description |
|---|---|---|
| Battery chg. curr. limit (Valid for BMS communication) | HMI | Maximum battery charging current is limited according to the inverter battery charging current setting value. |
| BMS | Maximum battery charging current is limited by the current limit value of the BMS. | |
| Inverter | Maximum battery charging current is limited by the machine's derating logic. | |
| BMS comm. interface | Disable | BMS does not communicate |
| RS485 | BMS RS485 communication function | |
| CAN | BMS CAN communication function | |
| Battery Temperature Compensation | Select whether to turn on temperature compensation | |
| Battery Type | USER | User customizable to set all battery parameters |
| SLD | Sealed Lead Acid Battery | |
| FLD | Open-ended lead-acid batteries | |
| GEL | Gel lead-acid battery |
5.4.3 Battery Setup - BMS Communication Protocol
When the BMS port selection setting item = 485 or CAN, you need to select the corresponding lithium battery manufacturer brand for communication:
- 1:PACE-PACEEX; 2:RUDA-Ritar; 3:AOGUAN-ALLGRAND BATTERY
- 4:OULITE-OLITER; 5:CEF-CHANGFENG TECHNOLOGY;
- 6:XINWANGDA-SUNWODA; 7:DAQIN-DAKING; 8:WOW-SRNE
- 9:PYL-PYLONTECH; 10:MIT-FOXESS; 11:XIX-XYE;
- 12:POL-POWMR; 13:GUOX-Gotion; 14:SMK-SMK;
- 15:VOL-WEILAN; 16:UZE-YUZE
5.4.3 Battery Setup - Battery Parameters
| Parameter | Sealed lead acid battery (SLd) | Gel lead acid battery (GEL) | Flooded lead acid battery (FLd) | User-defined (USER) |
|---|---|---|---|---|
| Overdisconnect Voltage | 60V | 60V | 60V | 60V |
| Boost charging voltage | 57.6V | 56.8V | 57.6V | 40~60V (can be set) |
| Undervoltage alarm voltage | 44V | 44V | 44V | 40~60V (can be set) |
| Undervoltage disconnect voltage | 42V | 42V | 42V | 40~60V (can be set) |
| Discharge limiting voltage | 40V | 40V | 40V | 40~60V (can be set) |
| Overdischarge delay time | 5s | 5s | 5s | 1~30s (can be set) |
| Enhanced Charge Cycle | 120min | 120min | 120min | 10~900min (can be set) |
5.4.3 Battery Setup - Li-ion Battery Parameters
| Parameter | Ternary | LFP | User-defined (USER) | |||
|---|---|---|---|---|---|---|
| N13 | N14 | L16 | L15 | L14 | ||
| Overdisconnect Voltage | 60V | 60V | 60V | 60V | 60V | 60V |
| Boost charging voltage | 53.2V | 57.6V | 56.8V | 53.2V | 49.2V | 40~60V (can be set) |
| Undervoltage alarm voltage | 43.6V | 46.8V | 49.6V | 46.4V | 43.2V | 40~60V (can be set) |
| Undervoltage disconnect voltage | 38.8V | 42V | 48.8V | 45.6V | 42V | 40~60V (can be set) |
| Discharge limiting voltage | 36.4V | 39.2V | 46.4V | 43.6V | 40.8V | 40~60V (can be set) |
| Overdischarge delay time | 30s | 30s | 30s | 30s | 30s | 1~30s (can be set) |
| Enhanced Charge Cycle | 120min (can be set) | 120min (can be set) | 120min (can be set) | 120min (can be set) | 120min (can be set) | 10~900min (can be set) |
5.4.4 On Grid Setup
To enter this setting, you need to enter the password set by the user, the default password is "00000".
| Parameter Meaning | Description |
|---|---|
| Grid Standard | America: UL1741&IEEE1547.1-2020, California: RULE21, Hawaii: HECO, Puerto Rico, Columbia: UL1741, Other regions: GNL, Not Initialized |
| Grid Frequency | Selection of local grid frequency, 50Hz/60Hz |
| CT ratio | When connecting an external CT, enter the ratio on the CT specification |
| Sell power Max | On grid power |
| Buy power Max | Maximum power drawn from the grid. If the grid charging power + load power exceeds this setting, the machine reduces the charging power. (Setting range: 0 to rated power) |
| Zero-export power | Error calibration power in the case of backflow prevention, recommended setting 20-100W. |
| On-Grid Reactive Power | Setting range 0-100%, % of reactive power |
| Reactive power over/under excited | Over indicates 0%-100% / Under indicates -100%-0% |
| On Grid PF | Setting range 0.8-1 |
| Power factor over/under excited | Over indicates 0.8-1 / Under indicates -0.8--1 |
5.4.4 On Grid Setup - Enter Service (Not recommended to be changed by the customer)
| Parameter Meaning | Description |
|---|---|
| Enter service enable | Grid-connect enable setting (on by default) |
| Connect Voltage Low | Grid-connected low voltage protection voltage |
| Connect Frequency Low | Grid-connected low-frequency protection points |
| Connect Voltage High | Grid-connected high-voltage protection voltage |
| Connect Frequency High | Grid-connected high-frequency protection points |
| Normal connect delay time | Grid normal connection, grid connection delay time |
| Normal Connect Power Ramp Rate | Normal grid connection, rate of rise of grid-connected power |
| Reconnect delay time | Grid down reconnection, grid connection delay time |
| Reconnect Power Ramp Rate | Grid disconnection and reconnection, rate of rise of grid-connected power |
5.4.4 On Grid Setup - Grid Protection (Not recommended to be changed by the customer)
| Parameter Meaning | Description |
|---|---|
| LV1 | Class 1 undervoltage protection point |
| LF1 | Class 1 underfrequency protection point |
| LV2 | Class 2 undervoltage protection point |
| LF2 | Class 2 underfrequency protection point |
| LV3 | Class 3 undervoltage protection point |
| HV1 | Class 1 overvoltage protection point |
| HF1 | Class 1 overfrequency protection point |
| HV2 | Class 2 overvoltage protection point |
| HF2 | Class 2 overfrequency protection point |
| Time | Protection Response Time |
5.4.4 On Grid Setup - Other
| Parameter Meaning | Description |
|---|---|
| Frequency Droop (F-P) enable | Adjustment of inverter output power according to grid frequency |
| Volt -Watt (V-P) curve enable | Adjustment of the inverter active power according to the set grid voltage |
| Volt-Var (V-Q) curve enable | Adjustment of the inverter reactive power according to the set grid voltage |
| Watt-Var (P-Q) curve enable | Adjustment of the inverter reactive power according to the set active power |
| Watt-PF (P-PF) curve enable | Adjustment of the power factor of the inverter according to the set active power |
| LVRT/HVRT enable | Adjustment of grid HV ride-through / LV ride-through values |
| Reactive power percentage enable | When this function is enabled, the inverter will adjust its reactive power according to the configured reactive power percentage. |
| Discharge PF enable | When this function is enabled, the inverter will adjust its power factor during battery discharge according to the configured active power. |
| Charge PF enable | When this function is enabled, the inverter will adjust its power factor during battery charging according to the configured active power. |
5.4.5 Advance Setup - Generator
| Parameter Meaning | Description |
|---|---|
| Max charging current by gen. | Maximum battery charging current during generator charging |
| Generator rate power | Setting the power of the generator up to the rated power of the inverter |
| Generator charging enable | Setting whether the generator is charged or not |
| Generator work mode | When connect the Generator, select "Generator input" |
| When connect the Micro inverter, select "Micro inverter input" | |
| When connect the load to the GEN port, select "smart load" | |
| Grid always to smart load enable | Enable the grid supply power to smart load |
5.4.5 Advance Setup - Other
| Parameter Meaning | Description |
|---|---|
| PE-N connect enable | Enable automatic switching of PE-N connections |
| PV Riso check enable | Enable PV insulation impedance detection |
| AFCI check enable | Turn on AFCI check |
| Leakage curr. protection enable | Enable leakage current protection |
| BMS comm. error stop | After turning on, the inverter output turns off when the machine reports 58 communication faults |
| Power saving mode | After turning on the energy-saving mode, if the load is empty or less than 25W, the inverter output will be shut down after a delay of 5min; when the load is more than 40W, the inverter will start automatically. |
| CT auto detect enable | Automatically detect the CT, the result will report to "CT manual setting" |
| CT manual setting | According to the CT installation, select the CT direction |
| Arc fault clear | Clear the AFCI fault |
| Load type | According to the load that you have connected, select the load type |
| Inverter current limiting coefficient | When the inverter soft start, adjust the current coefficient (This setting doesn't recommend to be changed by the customer) |
5.4.5 Advance Setup - Restart Inverter
| Parameter Meaning | Description |
|---|---|
| Restore to factory setting | Reset all inverter settings to factory setting |
| Restart Inverter | Restart the inverter |
5.5 Time-Slot Charging/Discharging Function
The POW-SunSmart series is equipped with a time-slot charging and discharging function, which allows users to set different charging and discharging periods according to the local peak and valley tariffs, so that the utility power and PV energy can be used rationally.
When the utility price is expensive, the battery inverter can be used to supply power to the load; When the utility price is cheap, the utility can be used to supply and charge the load, which can maximize the user's savings in electricity costs.
The users can turn on/off the time-sharing charging/discharging function in the Setup menu parameters Segmented Charging Enable and Segmented Discharging Enable, and set the charging and discharging time periods in the parameters Timed Utility Charging Start/Stop Settings and Timed Battery Discharging Start/Stop Settings. Below is a case example to help users understand the function.
NOTICE
Before using this function for the first time, please set the local time and date, and then users can set the corresponding time slots according to the local peak and valley tariff charges.
6. Communication
6.1 Overview
| No. | Port | No. | Port | No. | Port |
|---|---|---|---|---|---|
| 4 | WIFI port | 7 | CAN port | 20 | Dry contact |
| 5 | RS485 port | 18 | Parallel port A | 21 | USB-B port |
| 6 | External CT port | 19 | Parallel port B | 26 | USB-A port |
6.2 USB-B Port
The user can read and modify device parameters through this port by using the host software. Please contact us for the host software installation package if you require one.
6.3 WIFI Port
The WIFI port is used to connect to the Wi-Fi/GPRS data acquisition module, which allows users to view the operating status and parameters of the inverter through the cell phone APP.
NOTICE
- The Wi-Fi/GPRS data acquisition module needs to be purchased separately.
6.4 RS485 Port
The RS485 port is used to connect to the BMS of Li-ion battery.
6.5 CAN Port
The CAN port is used to connect to the BMS of Li-ion battery.
NOTICE
- If you need the inverter to communicate with the lithium battery BMS, please contact us for the communication protocol or to upgrade the inverter to the corresponding software program.
6.6 External CT Port
- Length of CT Output Line Wrap: 4m
- Normally The CT direction is "to inverter"
6.7 Dry Contact
Dry contact port with 3 functions:
- RSD power supply
- Temperature sampling (reserved)
- Generator remote start/stop
NOTICE
- If you need to use the remote start/stop function of the generator with dry contact, ensure that the generator has ATS and supports remote start/stop.
7. Fault and Remedy (Troubleshooting)
7.1 Fault Code
| Fault code | Fault name | Does it Affect the outputs | Description |
|---|---|---|---|
| 01 | BatVoltLow | Yes | Battery undervoltage alarm |
| 02 | BatOverCurrSw | Yes | Battery discharge average current over-current (software protection). |
| 03 | BatOpen | Yes | Battery not-connected alarm |
| 04 | BatLowEod | Yes | Battery undervoltage stop discharging alarm |
| 05 | BatOverCurrHw | Yes | Battery overcurrent (hardware protection) |
| 06 | BatOverVolt | Yes | Battery overvoltage protection |
| 07 | BusOverVoltHw | Yes | Busbar overvoltage (hardware protection) |
| 08 | BusOverVoltSw | Yes | Busbar overvoltage (software protection) |
| 09 | PvVoltHigh | Yes | PV input overvoltage protection |
| 10 | PvBoostOCSW | No | Boost circuit overcurrent (software protection) |
| 11 | PvBoostOCHW | No | Boost circuit overcurrent (hardware protection) |
| 12 | HESCommErr | Yes | Master-slave HES communication failure |
| 13 | OverloadBypass | Yes | Bypass overload protection |
| 14 | OverloadInverter | Yes | Inverter overload protection |
| 15 | AcOverCurrHw | Yes | Inverter over-current hardware protection |
| 16 | AuxDSpReqOffPWM | Yes | Requesting a shutdown fault from the chip |
| 17 | InvShort | Yes | Inverter short-circuit protection |
| 18 | Bussoftfailed | Yes | Busbar soft start failure |
| 19 | OverTemperMppt | No | MPPT heat sink over-temperature protection |
| 20 | OverTemperInv | Yes | Inverter AC output with load or AC charging radiator over-temperature protection. |
| 21 | FanFail | Yes | Fan blockage or failure fault |
| 22 | EEPROM | Yes | Memory failure |
| 23 | ModelNumErr | Yes | Model setting error |
| 24 | Busdiff | Yes | Positive and negative bus voltage imbalance |
| 25 | BusShort | Yes | Busbar short circuit |
| 26 | Rlyshort | Yes | Inverter AC output backfeed to bypass AC output |
| 28 | LinePhaseErr | Yes | Utility input phase fault |
| 29 | BusVoltLow | Yes | Low bus voltage protection |
| 30 | BatCapacityLow1 | Yes | Alarm given when battery capacity rate is lower than 10% (setting BMS to enable validity). |
| 31 | BatCapacityLow2 | No | Alarm given when battery capacity rate is lower than 5% (setting BMS to enable validity). |
| 32 | BatCapacityLowStop | Yes | Inverter stops when battery capacity is low (setting BMS to enable validity). |
| 34 | CanCommFault | Yes | CAN communication fault in parallel operation. |
| 35 | ParaAddrErr | Yes | Parallel ID (communication address) setting error |
| 37 | ParaShareCurrErr | Yes | Parallel current sharing fault |
| 38 | ParaBattVoltDiff | Yes | Large battery voltage difference in parallel mode |
| 39 | ParaAcSrcDiff | Yes | Inconsistent mains input source in parallel mode |
| 40 | ParaHwSynErr | Yes | Hardware synchronization signal error in parallel mode |
| 41 | InvDcVoltErr | Yes | Inverter DC voltage error |
| 42 | SysFwVersionDiff | Yes | Inconsistent system firmware version in parallel mode |
| 43 | ParaLineContErr | Yes | Parallel line connection error in parallel mode |
| 44 | Serial number error | Yes | No serial number set at factory |
| 45 | Error setting of split-phase mode | Yes | Item "Parallel" setting error |
| 49 | Grid over voltage | Yes | |
| 50 | Grid under voltage | Yes | |
| 51 | Grid over Frequency | Yes | |
| 52 | Grid under Frequency | Yes | Selects the local corresponding grid standard. |
| 53 | Grid loss | Yes | |
| 54 | Grid DC current over | Yes | |
| 55 | Grid standard uninitialized | Yes | |
| 56 | Low insulation resistance fault | No | PV1+, PV2+ and PV- abnormally low impedance to ground. |
| 57 | Leakage current overload fault | Yes | System leakage current exceeds limit. |
| 58 | BMSComErr | No | BMS communication failure |
| 60 | BMSUnderTem | No | BMS alarm battery low temperature. |
| 61 | BMSOverTem | Yes | BMS alarm battery over-temperature. (Effective after successful BMS communication) |
| 62 | BMSOverCur | Yes | BMS alarm battery over-current. (Effective after successful BMS communication) |
| 63 | BMSUnderVolt | No | BMS alarm low battery. (Effective after successful BMS communication) |
7.2 Troubleshooting Table
| Fault code | Faults | Remedy | |
|---|---|---|---|
| Display | No display on the screen | Check if the battery switch or PV switch is closed; whether the switch is in the "ON" state; press any button on the screen to exit the screen sleep mode. | |
| [06] | Battery overvoltage protection | Check that the battery voltage does not exceed the preset value. If it does, discharge the battery until the voltage falls below the battery over-voltage recovery point. | |
| [01] [04] | Battery undervoltage protection | Charge the battery until it returns to the low voltage disconnection recovery voltage. | |
| [21] | Fan failure | Check if the fan is not turning or blocked by foreign object. | |
| [19] [20] | Heat sink over temperature protection | When the temperature of the device is cooled below the recovery temperature, normal charge and discharge control is resumed. | |
| [13] [14] | Bypass overload protection, inverter overload protection | 1. Reduce the use of power equipment. 2. Restart the unit to resume load output. | |
| [17] | Inverter short-circuit protection | 1. Check the load connection carefully and clear the short-circuit fault points. 2. Re-power up to resume load output. | |
| [09] | PV overvoltage | Use a multimeter to check if the PV input voltage exceeds the maximum allowable input voltage rated. | |
| [03] | Battery disconnected alarm | Check if the battery is not connected or if the battery circuit breaker is not closed. | |
| [40] [43] | Parallel connection fault | Check if the parallel line is not connected well, such as loose or wrong connection. | |
| [35] | Parallel ID setting error | Check whether the setting of parallel ID number is repeated. | |
| [37] | Parallel current sharing fault | Check if the parallel current sharing line is not connected well, such as loose or wrong connection. | |
| [39] | Inconsistent AC input source in parallel mode | Check whether the parallel AC inputs are from the same input interface. | |
| [42] | Inconsistent system firmware version in parallel mode | Check whether the software version of each inverter is consistent. | |
| [44] | Serial number error | Incorrect device serial number setting. | |
| [45] | Parallel mode error | There is a device in the parallel system with the wrong parallel mode setting. | |
| [49] | High grid voltage | Check that the grid voltage is within the normal range, if the grid voltage is abnormal, wait until the grid voltage is restored. | |
| [50] | Low grid voltage | Check that the grid voltage is within the normal range, if the grid voltage is abnormal, wait until the grid voltage is restored. | |
| [51] | High grid frequency | Check that the grid frequency is within the normal range, if the grid frequency is abnormal, wait until the grid frequency is restored. | |
| [52] | Low grid frequency | Check that the grid frequency is within the normal range, if the grid frequency is abnormal, wait until the grid frequency is restored. | |
| [53] | Grid unconnected | Check if the grid is correctly connected, e.g. if the switch is closed and if the grid is disconnected. | |
| [54] | Grid-connected current with DC component over | Power down and restart the device, if it continues to report faults, contact the manufacturer after sales. | |
| [55] | Grid standard not set | Setting standards for grid integration | |
| [56] | Low insulation resistance fault | Check that the system is well grounded and that the PV modules and cables are not worn | |
| [57] | Leakage current overload fault | Check that the system is well grounded and that the loads are not operating abnormally. | |
| 58 | BMSComErr | No | BMS communication failure |
| 60 | BMSUnderTem | No | BMS alarm battery low temperature. |
| 61 | BMSOverTem | Yes | BMS alarm battery over-temperature. (Effective after successful BMS communication) |
| 62 | BMSOverCur | Yes | BMS alarm battery over-current. (Effective after successful BMS communication) |
| 63 | BMSUnderVolt | No | BMS alarm low battery. (Effective after successful BMS communication) |
NOTICE
- If you encounter a fault with the product that cannot be solved by the methods in the table above, please contact our after-sales service for technical support and do not disassemble the equipment yourself.
8. Protection and Maintenance
8.1 Protection Features
| No. | Protection Feature | Instruction |
|---|---|---|
| 1 | PV current-limiting protection | When the charge current or power of the configured PV array exceeds the rated current and power of the inverter, it will charge at the rated current and power. |
| 2 | PV input over-voltage | If the PV voltage exceeds the maximum value allowed by the hardware, the machine will report a fault and stop the PV boost to output a sinusoidal AC wave. |
| 3 | PV night reverse current protection | At night, the battery is prevented from discharging through the PV module because the battery voltage is greater than the voltage of PV module. |
| 4 | Utility input overvoltage protection | When the mains voltage exceeds 140Vac, the mains charging will be stopped and the output will be inverted. |
| 5 | AC input under-voltage protection | When the mains voltage falls below 90Vac, the mains charging will be stopped and the output will be inverted. |
| 6 | Battery over-voltage protection | When the battery voltage reaches the over-voltage cut-off point, the PV and the utility will automatically stop charging to prevent the battery from being overcharged and damaged. |
| 7 | Battery under-voltage protection | When the battery voltage reaches the under-voltage cut-off point, the inverter will automatically stop the battery discharge to prevent damage from over-discharging the battery. |
| 8 | Battery over-current protection | After a period when the battery current exceeds that allowed by the hardware, the machine will switch off the output and stop discharging the battery. |
| 9 | AC output short-circuit protection | When a short-circuit fault occurs at the load output for more than 200ms, the output AC voltage will be turned off |
| 10 | Heat sink over-temperature protection | When the internal temperature of the inverter is too high, the inverter will stop charging and discharging; when the temperature returns to normal, the inverter will resume charging and discharging. |
| 11 | Inverter over-load protection | After triggering the overload protection the inverter will resume output after 3 minutes, 5 consecutive overloads will switch off the output until the inverter is restarted. |
| 12 | AC output reverse | Prevents AC back flow from the battery inverter to the bypass AC input. |
| 13 | Bypass over-current protection | Built-in AC input over-current protection circuit breaker. |
| 14 | Bypass phase inconsistency protection | When the phase of the bypass input and the phase of the inverter split do not match, the inverter disables switching to the bypass output to prevent the load from dropping out or short-circuiting when switching to the bypass. |
8.2 Maintenance
To maintain optimum and long-lasting working performance, we recommend that the following items are checked twice a year:
- Ensure that the airflow around the inverter is not blocked and remove any dirt or debris from the radiator.
- Check that all exposed conductors are not damaged by sunlight, friction with other surrounding objects, dry rot, insect or rodent damage, etc. The conductors need to be repaired or replaced if necessary.
- Verify that the indications and displays are consistent with the operation of the equipment, note any faults or incorrect displays and take corrective action if necessary.
- Check all terminals for signs of corrosion, insulation damage, high temperatures or burning/discoloration and tighten terminal screws.
- Check for dirt, nesting insects and corrosion, clean as required, Clean the insect screen regularly.
- If the lightning arrester has failed, replace the failed arrester in time to prevent lightning damage to the inverter or other equipment of the user.
DANGER
- Before conducting any inspection or operation, please ensure the inverter is disconnected from all power sources and that the capacitor is fully discharged to avoid the risk of electric shock.
Our company will not be held responsible for damage due to the following reasons:
- Damage caused by improper use or use in the wrong location.
- Photovoltaic modules with an open circuit voltage exceeding the maximum permissible voltage.
- Damage caused by the operating temperature exceeding the restricted operating temperature range.
- Dismantling and repair of the inverter by unauthorized persons.
- Damage caused by force majeure: damage during transport or handling of the inverter.
9. Specifications (Parameter Table)
| Model | POW-SunSmart LVM8K | POW-SunSmart LVM10K | POW-SunSmart LVM12K | Settable |
|---|---|---|---|---|
Inverter Output | ||||
| Rated Output Power | 8800W | 10000W | @240V 12000W @208V 10400W | |
| Max. Peak Power | 2 times rated power | |||
| Rated Output Voltage | 120/240Vac (Split-phase); 120/208V (Three-phase) | √ | ||
| Output Voltage Error | @240V 36.6A @208V 42.3A | @240V 41.7A @208V 48.1A | 50A | |
| Load Capacity of Motors | 5HP | 6HP | 6HP | √ |
| Rated AC Frequency | 50/60Hz | √ | ||
| Waveform | Pure Sine Wave | |||
| Parallel Capacity | 6 | |||
Battery | ||||
| Battery Type | Li-ion / Lead-Acid / User Defined | √ | ||
| Rated Battery Voltage | 48Vdc | |||
| Voltage Range | 40-60Vdc | √ | ||
| Max. PV Charging Current | 200A | √ | ||
| Max. Grid Charging Current | 120A | √ | ||
| Max. Generator Charging Current | 60A | √ | ||
| Max. Hybrid Charging Current | 200A | √ | ||
PV Input | ||||
| Num. of MPP Trackers | 2 | |||
| Max. PV Array Power | 5500W/5500W | 5500W/5500W | 6600W/6600W | |
| Max. Input Current | 25A/25A | |||
| Max. Voltage of Open Circuit | 550Vdc/550Vdc | |||
| MPPT Voltage Range | 125-450Vdc/125-450Vdc | |||
Grid / Generator Input | ||||
| Input Voltage Range | 90-140Vac | |||
| Frequency Range | 50/60Hz | |||
| Bypass Phase Current | 63A | |||
Efficiency | ||||
| MPPT Tracking Efficiency | 99.9% | |||
| Max Efficiency | 97.5% | |||
| CEC Efficiency | 96.5% | |||
Basic Data | ||||
| Dimensions | 750*440*240mm | |||
| Weight | 42kg | |||
| Protection Degree | IP65 | |||
| Operating Temperature Range | -25~60℃, >45°C derated | |||
| Noise | <60dB | |||
| Cooling Method | Heat sink + intelligent fan cooling | |||
Communication | ||||
| Communication Port | RS485 / CAN / USB / Dry contact | √ | ||
| External Modules (Optional) | Wi-Fi / GPRS | √ | ||
Certified Specifications | ||||
| Safety Standards | UL1741&IEEE1547.1-2020, CEC, RULE 21, HECO | |||
| EMC | FCC 15 class B | |||
| RoHS | Yes | |||
10. Appendix: Parallel Connection
10.1 Parallel Operation
- Up to six units can be connected in parallel.
- When using the parallel operation function, the following connecting lines (package accessories) shall be firmly and reliably connected.
10.2 Precautions for Connecting the Parallel Connecting Lines
Warning:
- PV wiring: In parallel connection, the PV array of each inverter must be independent, and the PV array of PV1 and PV2 for one inverter must also be independent.
- Battery wiring: In single-phase or three-phase parallel connection, all solar storage inverters must be connected to the same battery, with BAT+ connected to BAT+ and BAT- to BAT-, and before power on and start-up, it is necessary to check and ensure correct connection, wiring length, and cable size, so as to avoid the abnormal operation of parallel system output caused by wrong connection.
- LOAD wiring: When connecting the parallel machine, all the inverse control integrated machine must be connected to L and L, N and N line connected, PE and PE connected, and ensure that the power on and off before connecting correctly and the wiring length and wire diameter is the same, to avoid connecting incorrectly caused by the output of the parallel system does not work properly. When connecting three-phase parallel machines, all inverse control integrated machines must be connected N to N wire and PE to PE. The L lines of all machines in the same phase need to be connected together, but the L lines of AC outputs of different phases cannot be connected together. Other precautions are the same as single-phase connection of parallel machines.
- GRID wiring: Parallel connection in single phase: ensure L-to-L, N-to-N and PE-to-PE connection for all solar storage inverters, and that the connection is correct with the same wiring length and line diameter before power on, so as to avoid the abnormal operation of parallel system output caused by wrong connection. Meanwhile, it is not allowed to have multiple different AC source inputs to avoid damage to the external equipment of the inverter. The consistency and uniqueness of AC source input shall be ensured. Parallel connection in three-phase: ensure N-to-N and PE-to-PE connection for all solar storage inverters. The L lines of all inverters connected to the same phase need to be connected together. But L lines of different phases cannot be joined together. Other connection precautions are the same as parallel connection in single phase.
- Wiring of parallel communication line: Our parallel communication cable is a shielded 10Pin network connection cable, which can be used for single-phase or three-phase parallel connection. Each machine must be connected with one out and one in. This means that the machine "Parallel_A" is connected to the machine to be parallelized "Parallel_B", and that the machine "Parallel_A" is not allowed to connect to the "Parallel_B". "Parallel_B" or "Parallel_A" is connected to the machine to be parallelized "Parallel_A". At the same time, the parallel communication cable of each machine should be fastened with 10Pin network connection cable to avoid disconnection or poor contact of the parallel communication cable, which may cause abnormal operation or damage to the system output.
- Before and after connecting the system, please check the following system wiring diagrams in detail to ensure that all wiring is correct and reliable before powering on.
- After the system is correctly wired, powered on, and in normal operation, if a new inverter needs to be connected, make sure to disconnect the battery input, PV input, AC input and AC output, and that all solar storage inverters are powered off before reconnecting into the system.
10.3 Split-Phase Parallel Connection
Setting for each inverter: Select "Parallel" for parallel mode, select "Split Phase" for grid type, when "120V" is selected for output phase voltage, the output L1-L2 voltage is 240V, L1-N voltage is 120V, L2-N voltage is 120V.
10.3.1 Two Inverters in Parallel
Diagrams for two inverters connected in parallel are available in the full user manual.
10.3.2 Three Inverters in Parallel
Diagrams for three inverters connected in parallel are available in the full user manual.
10.3.3 Four Inverters in Parallel
Diagrams for four inverters connected in parallel are available in the full user manual.
10.3.4 Five Inverters in Parallel
Diagrams for five inverters connected in parallel are available in the full user manual.
10.3.5 Six Inverters in Parallel
Diagrams for six inverters connected in parallel are available in the full user manual.
10.4 Three-Phase Parallel Connection
10.4.1 (1) 2 inverters connected in parallel to form a three-phase output (three-phase unbalanced)
P1 machine setting: Parallel mode select "Three phase A", grid type select "Three Phase", when output phase voltage select "120V, the output L1-L2 voltage is 208V, L1-N voltage is 120V, L2-N voltage is 120V.
P2 machine setting: Parallel mode select "Three phase B", grid type select "Three Phase", when output phase voltage select "120V, the output L1-L2 voltage is 208V, L1-N voltage is 120V, L2-N voltage is 120V.
10.4.2 (2) 3 or 6 inverters in parallel to form a three-phase output (three-phase balanced)
P1 machine setting: Parallel mode select "Three phase A", grid type select "Three Phase", when output phase voltage select "120V, the output L1-L2 voltage is 208V, L1-N voltage is 120V, L2-N voltage is 120V.
P2 machine setting: Parallel mode select "Three phase B", grid type select "Three Phase", when output phase voltage select "120V, the output L1-L2 voltage is 208V, L1-N voltage is 120V, L2-N voltage is 120V.
P3 machine setting: Parallel mode select "Three phase C", grid type select "Three Phase", when output phase voltage select "120V, the output L1-L2 voltage is 208V, L1-N voltage is 120V, L2-N voltage is 120V.
11. User Tips
Based on available information, no specific user tips were identified from reviews or Q&A that are not already covered in the main manual sections.
12. Warranty and Support
For technical support, warranty information, or any inquiries regarding your PowMr POW-SunSmart LVM12K Hybrid Solar Inverter, please contact Shenzhen Hehejin Industrial Co., Ltd. using the details below:
- Tel/Fax: +86755-28219903
- Email: support@powmr.com
- Web: www.powmr.com
- Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China