YHDC SCT024TS

Contents

YHDC SCT024TS Split Core Current Transformer User Manual

Model: SCT024TS | Brand: YHDC

1. Introduction

The YHDC SCT024TS is an industrial split-core current transformer designed for precise current measurement, monitoring, and protection in various electrical systems. Its innovative split-core design allows for easy installation without the need to power off equipment or cut wires, significantly reducing downtime. This manual provides essential information for the safe and effective installation, operation, and maintenance of your SCT024TS current transformer.

2. Safety Information

  • Voltage Rating: This device is designed for low voltage applications, below 50Vac or 75Vdc.
  • Dielectric Strength: Input (bare conductor)/Output AC 800V/1min 50Hz; Output/housing AC 3.5KV/1min 50Hz.
  • Secondary Circuit: The secondary circuit is not allowed to be open. Ensure proper termination to avoid hazardous conditions.
  • Installation: Installation should only be performed by qualified personnel in accordance with local electrical codes and regulations.
  • Chemicals: This product contains no high-concerned chemicals.

3. Product Overview

The SCT024TS is a compact and robust split-core current transformer featuring a 24mm opening size and a 180° full split latch with a safety buckle for secure and tool-free installation. It utilizes laminated silicon steel core and 0.35mm thin sheets to ensure stable current measurement with low magnetic loss.

YHDC SCT024TS Split Core Current Transformer

Figure 3.1: YHDC SCT024TS Split Core Current Transformer

Video 3.1: Product demonstration highlighting features and quick installation.

4. Specifications

General Characteristics:

  • Mounting Type: Free hanging (In-Line)
  • Core Material: Laminated silicon steel
  • Applicable Standard: GB20840-2014
  • Operating Temperature: -25℃ to +60℃
  • Storage Temperature: -30℃ to +90℃
  • Frequency Range: 50Hz-60Hz
  • Waterproof Grade: IP00
  • Dielectric Strength: Input (bare conductor)/Output AC 800V/1min 50Hz; Output/housing AC 3.5KV/1min 50Hz
  • Coil Structure: Split core current transformer
  • Coil Number: Current Transformer
  • Phase: SINGLE
  • Use: Current

Electrical Parameters (Typical Values):

Parameter50A100A200A300A400A
Rated Input50, 100, 200, 300, 400 A
Rated Output (mA)50100501002050100501005080100
Turns Ratio1:10001:5001:20001:10001:100001:40001:20001:60001:30001:80001:50001:4000
Accuracy (%)0.510.5/0.20.50.5/0.10.5/0.20.50.5/0.20.5/0.20.5/0.20.5/0.20.5/0.2
Sampling Resistance (Ω)20102010502010201020208
Weight (g)204

Dimensions (in mm ±0.5):

SCT024TS Dimensions and Electrical Diagram

Figure 4.1: Front view, side view, and opening angle of the SCT024TS, along with an electrical diagram showing the Transient Voltage Suppressor (TVS) and output screw terminal.

5. Setup and Installation

The SCT024TS is designed for quick and easy installation, often achievable by a single person in under 30 seconds, thanks to its tool-free split-core design.

Installation Steps:

  1. Prepare the Cable: Identify the current-carrying conductor you wish to measure. Ensure the cable is within the 24mm opening size of the transformer.
  2. Open the Transformer: Gently press the safety buckle and open the 180° full split latch. The transformer will open, revealing the core.
  3. Position the Cable: Place the current-carrying conductor through the opening of the transformer. Ensure the cable passes cleanly through the center of the core.
  4. Close the Transformer: Close the split latch until it clicks securely into place with the safety buckle. Verify that the transformer is fully closed and locked.
  5. Connect Output Terminals: Connect the output screw terminals (labeled 'k' and 'l' in diagrams) to your monitoring or protection device. Ensure the secondary circuit is always closed.
SCT024TS Split Core Current Transformer Open

Figure 5.1: The SCT024TS in its open state, ready for cable insertion.

SCT024TS Output Screw Terminals

Figure 5.2: Rear view showing the output screw terminals for connection.

6. Operating Instructions

Once correctly installed and connected to a suitable monitoring or protection device, the SCT024TS will provide an accurate current signal proportional to the primary current flowing through the conductor.

Typical Applications:

  • Current measurement, monitoring, and protection for electrical wiring and equipment.
  • Current and power measurement for electric motors, lighting, air compressors, heating and ventilation systems, air-conditioning equipment, and automation-control systems.
  • Integration into current, power, and energy monitoring devices.
  • Use in relay protection devices.
  • Applications in charging piles and data centers.

Refer to the documentation of your connected monitoring device for specific instructions on interpreting the output signal and configuring measurement parameters.

7. Maintenance

The SCT024TS current transformer is designed for long-term, reliable operation with minimal maintenance. However, periodic checks are recommended:

  • Visual Inspection: Periodically inspect the transformer for any signs of physical damage, corrosion, or loose connections.
  • Cleaning: If necessary, gently clean the exterior of the device with a dry, soft cloth. Do not use abrasive cleaners or solvents.
  • Connection Integrity: Ensure that the output screw terminals remain tight and that the connected wiring is secure.

8. Troubleshooting

If you encounter issues with your SCT024TS, consider the following common troubleshooting steps:

  • No Output/Incorrect Reading:
    • Verify that the primary conductor is correctly routed through the transformer's core.
    • Check all wiring connections to the output terminals for tightness and correct polarity.
    • Ensure the secondary circuit is not open. The secondary must always be connected to a load.
    • Confirm that the connected monitoring device is correctly configured for the SCT024TS's output type (mA) and turns ratio.
  • Intermittent Readings:
    • Inspect for loose connections at the transformer terminals or the monitoring device.
    • Check for any physical obstructions preventing the split core from closing completely.

For persistent issues, consult the documentation of your connected monitoring equipment or contact technical support.

9. User Tips

  • When selecting a current transformer, ensure the rated input current matches or exceeds the maximum expected current of your application.
  • For optimal accuracy, try to center the primary conductor within the transformer's opening.
  • Always double-check the wiring connections before powering on the system to prevent damage to the transformer or connected devices.

10. Certifications

The YHDC SCT024TS Split Core Current Transformer complies with the following international standards and certifications:

  • CE Certified: Meets EU EN 61869-1 Safety Standard.
  • ISO 9001:2015: Quality Management System.
  • REACH Compliant: Registration, Evaluation, Authorisation and Restriction of Chemicals.
  • RoHS Compliant: Restriction of Hazardous Substances.
  • GB20840-2014: China National Standard.

11. Manufacturer Information

YHDC, established in 1992, is a leading manufacturer of electromagnetic components and devices. With over 30 years of production experience, YHDC products are widely used in industrial equipment, precision instruments, aerospace, medical, railway, electric power, and other high-end industries. The company is committed to developing high-performance, reliable products that adapt to severe environments and offer a long service life.

12. Additional Resources

For a more detailed user manual and additional documentation, please refer to the official PDF document:

View User Manual (PDF)

© 2024 YHDC. All rights reserved.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.