PowMr POW-HVM6.2KP

Contents

PowMr POW-HVM6.2KP Hybrid Solar Inverter User Manual

Model: POW-HVM6.2KP

1. Introduction

This is a multi-function inverter/charger, combining functions of inverter, MPPT solar charger and battery charger to offer uninterruptible power support with portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.

Features:

  • Pure sine wave inverter
  • Inverter running without battery
  • Built-in MPPT solar controller
  • Configurable input voltage range for home appliances and personal computers via LCD setting
  • Configurable battery charging current based on applications via LCD setting
  • Configurable AC/Solar Charger priority via LCD setting
  • Compatible to mains voltage or generator power
  • Auto restart while AC is recovering
  • Overload/ Over temperature/ short circuit protection
  • Smart battery charger design for optimized battery performance
  • Cold start function

Basic System Architecture:

The following illustration shows basic application for this inverter/charger. It also includes following devices to have a complete running system: Generator or Utility, PV modules (option). Consult with your system integrator for other possible system architectures depending on your requirements. This inverter can power all kinds of appliances in home or office environment, including motor-type appliances such as tube light, fan, refrigerator and air conditioner.

Hybrid Power System Diagram
Figure 1: Hybrid Power System Overview. This diagram illustrates the connection of solar panels, the hybrid inverter, a generator or utility grid, external battery packs, and various home appliances.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries and all appropriate sections of this manual.
  2. CAUTION -- To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION - Only qualified personnel can install this device with battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.
  10. Fuse is provided as over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
  12. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
  13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.

3. Package Contents

Upon opening the package, you should find the following items:

  • 1 x PowMr Hybrid Solar Inverter Unit (POW-HVM6.2KP)
  • 1 x User Manual
  • 1 x Parallel Communication Cable (for multi-unit setups)
  • 1 x Current Sharing Cable
  • 2 x Expansion Screws (for mounting)
  • 1 x Battery Fuse
Video: Unboxing and overview of the PowMr POW-HVM6.2KP Hybrid Solar Inverter, showing all included components.

4. Setup and Installation

4.1. Unpacking and Inspection

Before installation, please inspect the unit. Be sure that nothing inside the package is damaged.

4.2. Mounting the Unit

Consider the following points before selecting where to install:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install this inverter at eye level in order to allow the LCD display to be read at all times.
  • The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
  • The recommended installation position is to be adhered to the wall vertically.
  • Be sure to keep other objects and surfaces as shown in the diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.
  • SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Inverter Mounting Dimensions
Figure 2: Recommended mounting clearances. Ensure at least 50cm clearance above and below, and 20cm on each side for proper ventilation and access.

4.3. Battery Connection

CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter.
WARNING! All wiring must be performed by qualified personnel. It's very important for system safety and efficient operation to use appropriate cable for battery connection.

Steps:

  1. Make positive and negative cables based on recommended terminal size.
  2. Connect all battery packs as units require.
  3. Insert battery cable flatly into battery connector of inverter and make sure the bolts are tightened with torque of 2-3Nm. Ensure polarity is correct.
Recommended Battery Cable Specifications
ModelMaximum AmperageBattery CapacityWire SizeCable mm²Terminal Size (L/W/D mm)Torque Value
6.2KVA137A200AH2AWG3837/18/6.42~3 Nm
Battery Connection Diagram
Figure 3: Battery connection diagram. Connect multiple 12V batteries in series to achieve the required 48V system voltage. Ensure correct polarity when connecting to the inverter.

4.4. AC Input/Output Connection

CAUTION! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source (recommended 50A). Do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by qualified personnel.

Steps:

  1. Before making AC input/output connection, be sure to open DC protector or disconnector first.
  2. Remove insulation sleeve 10mm for six conductors.
  3. Insert AC input wires according to polarities (Ground, Line, Neutral) and tighten terminal screws.
  4. Insert AC output wires according to polarities (Ground, Line, Neutral) and tighten terminal screws.
  5. Make sure the wires are securely connected.

CAUTION: Important Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are worked in parallel operation.

Suggested AC Cable Requirements
ModelAWG No.Torque Value
6.2KVA8 AWG1.4~1.6Nm
AC Input/Output Wiring Diagram
Figure 4: AC Input and Output Wiring Diagram. Connect Live/Positive, Neutral/Negative, and Ground wires correctly to the AC input and output terminals. Ensure proper grounding.

4.5. PV Connection

CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.
WARNING! All wiring must be performed by qualified personnel.

Steps:

  1. Remove insulation sleeve 10 mm for positive and negative conductors.
  2. Check correct polarity of connection cable from PV modules and PV input connectors.
  3. Connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.
  4. Make sure the wires are securely connected.
PV Connection Cable Specifications
ModelTypical AmperageCable SizeTorque
6.2KVA27A10 AWG1.4~1.6 Nm
PV Array Specifications
ParameterValue
Max. PV Array Open Circuit Voltage500VDC
PV Array MPPT Voltage Range60VDC~500VDC
PV Module Wiring Diagram
Figure 5: PV Module Wiring Diagram. Connect solar panels to the PV input terminals, ensuring correct polarity. The diagram shows the connection of solar panels to the inverter's PV input.

4.6. Parallel Installation (Optional)

This inverter can be used in parallel with two different operation modes:

  1. Parallel operation in single phase with up to 12 units.
  2. Maximum 12 units work together to support three-phase equipment. 10 units support one phase maximum.

Package Contents for Parallel Kit:

  • Parallel communication cable

Mounting the Unit for Parallel Operation:

For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below each unit. Install each unit at the same level.

Wiring Connection for Parallel Operation:

  • Ensure the length of all battery cables is the same.
  • Connect battery cables using a connector or bus-bar. The cable size from joint to battery should be X times cable size (X = number of inverters).
  • Install breakers at the battery and AC input side for each inverter.

Parallel Operation in Single Phase:

Up to 12 units can be connected in parallel for single-phase output. Communication cables connect units in series.

Support 3-Phase Equipment:

The inverter supports 3-phase output by assigning units to L1, L2, and L3 phases. A maximum of 12 units can be used, with up to 10 units in a single phase.

3 Phase Connection Diagram
Figure 6: 3-Phase Connection Diagram. Three inverters (P1, P2, P3) are connected to a common battery bank, utility grid, and load to provide 3-phase power. Communication connections are also shown.
Up to 9 Units Parallel Operation Diagram
Figure 7: Parallel Operation for up to 9 Units. This diagram illustrates how multiple inverters can be connected in parallel for single or three-phase operation, increasing total power output. Communication connections are also shown.
Comprehensive Wiring Diagram
Figure 8: Comprehensive Wiring Diagram. This diagram shows the complete connection scheme including AC input (utility grid), PV input (solar panel), battery input, and AC output (electrical appliances). It also details the inverter's ports.

5. Operating Instructions

5.1. Power ON/OFF

Once the unit has been properly installed and the batteries are connected well, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.

5.2. Operation and Display Panel

The operation and display panel is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.

LED Indicators:

  • AC/INV (Green): Solid On (Output powered by utility in Line mode), Flashing (Output powered by battery or PV in battery mode).
  • CHG (Green): Solid On (Battery fully charged), Flashing (Battery is charging).
  • FAULT (Red): Solid On (Fault occurs), Flashing (Warning condition occurs).

Function Keys:

  • ESC: To exit setting mode.
  • UP: To go to previous selection.
  • DOWN: To go to next selection.
  • ENTER: To confirm the selection in setting mode or enter setting mode.

LCD Display Icons:

The LCD displays various icons for input source (AC, PV), battery status, load level, operating mode (utility, PV, bypass, charger, inverter), and fault/warning codes. Refer to the detailed icons in the full user manual for specific meanings.

5.3. LCD Settings

After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Use "UP" or "DOWN" to select programs, and "ENTER" to confirm or "ESC" to exit. Key settings include:

  • Output Source Priority (Program 01): Solar first, Utility first, SBU priority (Solar-Battery-Utility), SUB priority (Solar-Utility-Battery).
  • Maximum Charging Current (Program 02): Configures total charging current from solar and utility.
  • AC Input Voltage Range (Program 03): For appliances or UPS.
  • Power Saving Mode (Program 04): Enable/disable.
  • Battery Type (Program 05): AGM, Flooded, User-Defined.
  • Auto Restart (Program 06/07): For overload or over-temperature.
  • Output Voltage (Program 08): 220V, 230V, 240V.
  • Output Frequency (Program 09): 50Hz, 60Hz.
  • Auto Bypass (Program 10): Manual or Auto.
  • Maximum Utility Charging Current (Program 11): Adjustable.
  • Setting Voltage Point Back to Utility (Program 12): For SBU/Solar first priority.
  • Battery Fully Charged Voltage (Program 13): Adjustable.
  • Charger Source Priority (Program 16): Solar first, Utility first, Solar and Utility, Only Solar.
  • Buzzer Mode (Program 18): Various settings for buzzer alerts.
  • Bulk Charging Voltage (Program 26): For C.V voltage.
  • Floating Charging Voltage (Program 27): Adjustable.
  • AC Output Mode (Program 28): Single phase or Parallel.
  • Low DC Cut-off Voltage (Program 29): Adjustable.
  • Battery Equalization (Program 33-36): Enable, voltage, time, timeout.
  • Maximum Discharge Current Protection (Program 46): Enable/disable.

5.4. Operating Mode Description

The inverter operates in several modes:

  • Standby Mode / Power Saving Mode: Inverter not on, but can charge batteries.
  • Fault Mode: Indicates internal circuit errors or external issues.
  • Line Mode: Inverter provides power from mains, also charges battery. Can prioritize solar or battery if configured.
  • Battery Mode: Inverter provides power from battery and PV.

6. Maintenance

6.1. Battery Equalization

Equalization reverses negative chemical effects like stratification and sulfation, which reduce battery capacity.

  • How to Apply: Enable in LCD setting program 33. Set equalization interval (program 37) or activate immediately (program 39).
  • When to Equalize: Starts in float stage when interval is reached or activated.
  • Charging Time and Timeout: Controller charges until battery voltage reaches equalization voltage, then maintains it. If voltage doesn't rise, it extends time. If still low after timeout, it stops.

6.2. Lithium Battery Settings

If using lithium batteries, connect the BMS (Battery Management System) communication cable to the inverter's RS485 port. This allows the inverter to:

  • Re-configure charging voltage, current, and discharge cut-off voltage based on battery parameters.
  • Start or stop charging based on battery status.
  • Set battery type to "Li2" in LCD program 5.
  • Configure SOC (State of Charge) points for utility source and battery mode.
  • Set low DC cut-off SOC.

7. Troubleshooting

This section provides guidance for common issues. For detailed fault codes and warnings, refer to the full user manual.

Troubleshooting Guide
ProblemLCD/LED/BuzzerExplanation / Possible CauseWhat to do
Unit shuts down automatically during startupLCD/LEDs active for 3s then offBattery voltage too low1. Re-charge battery. 2. Replace battery.
No response after power onNo indication1. Battery voltage too low. 2. Battery polarity reversed.1. Check batteries/wiring. 2. Re-charge battery. 3. Replace battery.
Mains exist but unit works in battery modeGreen LED flashingInsufficient AC power quality or "Solar First" priority set.1. Check AC wires. 2. Check generator/input voltage range. 3. Change output source priority.
Fault code 07LCD displayOverload error (110%+)Reduce connected load.
Fault code 02LCD displayInternal temperature > 100°CCheck air flow, ambient temperature.
Buzzer beeps continuously, red LED onBuzzer/Red LEDFault code 03 (Battery over-charged/too high)Check battery specs/quantity. Return to repair center.
Parallel: Host data lossFault code 24Communication cables issueCheck communication cables, restart inverter. Contact installer.

8. Specifications

8.1. Table 1 Line Mode Specifications

Parameter6.2KVA
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage170Vac±7V (UPS) / 90Vac±7V (Appliances)
High Loss Voltage280Vac±7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)

8.2. Table 2 Inverter Mode Specifications

Parameter6.2KVA
Rated Output Power6.2KVA/6.2KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac±5%
Peak Efficiency94%
Nominal DC Input Voltage48Vdc
Cold Start Voltage46.0Vdc

8.3. Table 3 Charge Mode Specifications

Parameter6.2KVA
Max Charging Current (PV+AC)120Amp
Max Charging Current (AC)80Amp
Bulk Charging Voltage (Flooded)58.4Vdc
Bulk Charging Voltage (AGM/Gel)56.4Vdc
Floating Charging Voltage54Vdc
Max. PV Array Open Circuit Voltage500Vdc
PV Array MPPT Voltage Range60Vdc~500Vdc
Max. Input Current (PV)27A
Max Charging Current (PV)120A

8.4. Table 4 General Specifications

Parameter6.2KVA
Safety CertificationCE
Operating Temperature Range-10°C to 55°C
Storage temperature-15°C~60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm450x300x130
Net Weight, kg9.6

9. User Tips

  • Fan Operation: Newer firmware versions allow fans to turn on based on temperature rather than continuously or solely on load, leading to quieter operation at low loads. This is a significant improvement.
  • Neutral Wire: Be aware that some users report the inverter outputs two phases without a true neutral wire, which might require an external switch or specific wiring considerations for certain loads.
  • Firmware: The updated firmware offers a better interface and improved fan control.
  • Battery Compatibility: The inverter offers good options for connecting various types of batteries.
  • Mounting Hardware: Mounting bolts, washers, and anchors are typically not included and need to be purchased separately.
  • Documentation: Some users desire more detailed explanations for abbreviations (e.g., EOD, AOS, EDS) in the manual.

10. Warranty and Support

For technical support, warranty claims, or further inquiries, please contact:

SHENZHEN HEHEJIN INDUSTRIAL CO.,LTD

  • Tel/Fax: +86 755-28219903
  • Email: support@powmr.com
  • Web: www.powmr.com
  • Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China

Please refer to the official user manual PDF for the most up-to-date warranty terms and conditions.
A PDF version of this manual is available for download at: PowMr POW-HVM6.2K-48V-LIP User Manual (PDF)


Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.