1. Introduction
The GEYA GRL8 series of liquid level control relays are designed for monitoring and controlling liquid levels in various applications such as wells, basins, reservoirs, and tanks. These devices offer reliable and precise control of pumps based on detected liquid levels. The series includes models GRL8-01, GRL8-02, and GRL8-03, each with specific functionalities to suit different control requirements.

2. Setup and Installation
2.1 Mounting
The GRL8 series relays are designed for 1-MODULE, DIN rail mounting (EN/IEC 60715). Ensure the relay is securely fastened to the DIN rail in a suitable enclosure, protected from environmental factors.
2.2 Wiring Diagrams
Proper wiring is crucial for the correct operation of the liquid level control relay. Refer to the specific diagrams for your GRL8 model.
2.2.1 GRL8-01 and GRL8-02 Wiring

Probe Connections:
- A1, A2: Supply terminals (AC/DC 24-240V).
- C: Common probe.
- Min: Minimum level probe.
- Max: Maximum level probe.
- 11, 12, 14: SPDT output contacts.
2.2.2 GRL8-03 Wiring (Well-Tank Level Control)

Probe Connections for GRL8-03:
- A1, A2: Supply terminals (AC/DC 24-240V).
- C: Common probe (shared between well and tank).
- Min1, Max1: Minimum and Maximum level probes for the well.
- Min2, Max2: Minimum and Maximum level probes for the tank.
- 11, 12, 14: SPDT output contacts for pump control.
- Manual start: Connect an external button for manual pump operation.
3. Operating Instructions
3.1 General Function Features
- Supply Voltage: Galvanically separated AC/DC 24-240V.
- Output: 1 SPDT (Single Pole Double Throw) contact, 10A/AC1.
- Status Indication: Relay status is indicated by an LED on the front panel.
- Sensitivity: Adjustable by a potentiometer on the front panel (5-100KΩ).
3.2 Model-Specific Functions
3.2.1 GRL8-01 (2 Level Control Mode)
- Monitors liquid level between two points (Min and Max).
- Typically used for maintaining liquid within a specific range.
3.2.2 GRL8-02 (2 or 1 Level Control Mode)
- Offers flexibility to operate in either 2-level or 1-level control mode.
- Function Selection: Choice of PUMP UP or PUMP DOWN operation.
- Time Delay: Adjustable time delay on the output (0.1 - 10s).
3.2.3 GRL8-03 (Well-Tank Level Control)
This model is designed to control high water towers by pumping water from low water wells. The working principle is as follows:
- When the water level in the high water tower is lower than Min2, if the water level in the well is higher than Min1, the pump will start working until the water level in the tower reaches Max2, and the pump will stop working.
- When the water level in the well reaches Max1, if the water level in the high water tower is lower than Max2, the pump will start working until the water level in the tower reaches Max2, and the pump will stop working. If this function is not required, please do not connect the Max1 probe.
- When the water level in the water tower is between Max2 and Min2, the water pump can be started by pressing the 'manual start' button until the water level in the tower reaches Max2, and the water pump stops working.
- When the water pump is running, if the water level in the well is lower than Min1, the pump will stop working to avoid empty load to prevent damage to the pump. At this time, the red light will flash to indicate that the well is short of water.
3.3 Functions Diagrams
The following diagrams illustrate the operational logic for each model:


4. Maintenance
The GEYA GRL8 series relays are designed for reliable operation with minimal maintenance. However, regular checks can ensure optimal performance:
- Visual Inspection: Periodically inspect the relay and its connections for any signs of damage, corrosion, or loose wiring.
- Cleanliness: Ensure the relay and its enclosure are kept clean and free from dust or moisture accumulation.
- Probe Condition: Check the liquid level probes for any buildup or damage that might affect their conductivity and accuracy. Clean probes as necessary according to the liquid type.
5. Troubleshooting
If the relay is not functioning as expected, consider the following:
- No Power/LED Off: Check the supply voltage (A1, A2) and ensure it is within the specified AC/DC 24-240V range. Verify all power connections.
- Incorrect Switching:
- Check the wiring of the probes (C, Min, Max) for correct connection and ensure they are not short-circuited or open-circuited.
- Verify the liquid level probes are clean and making proper contact with the liquid.
- Adjust the sensitivity potentiometer. If sensitivity is too low or too high, it might lead to erratic switching.
- For GRL8-02, ensure the PUMP UP/PUMP DOWN function is correctly selected.
- For GRL8-03, ensure all well and tank probes are correctly installed and connected according to the desired control logic.
- Pump Not Activating: Check the output contacts (11, 12, 14) and the wiring to the pump. Ensure the pump itself is functional.
- Erratic Behavior: Ensure the relay is not exposed to excessive electrical noise or interference. Check for stable power supply.
6. Specifications
6.1 GRL8-01 and GRL8-02 Technical Parameters
| Parameter | GRL8-01 | GRL8-02 |
|---|---|---|
| Function | 2 level control mode | 2 or 1 level control mode |
| Supply terminals | A1-A2 | |
| Voltage range | AC/DC 24-240V (50-60Hz) | |
| Input | max. 2VA | |
| Supply voltage tolerance | -15%; +10% | |
| Sensitivity (input resistance) | adjustable in range 5 kΩ - 100 kΩ | |
| Voltage in electrodes | max. AC 5 V | |
| Current in probe | AC <0.1 mA | |
| Time response | max. 400 ms | |
| Max. capacity length | 800 m (sensitivity 25kΩ), 200 m (sensitivity 100 kΩ) | |
| Max. capacity of probe cable | 400 nF (sensitivity 25kΩ), 100 nF (sensitivity 100 kΩ) | |
| Time delay (t) | adjustable, 0.1 - 10 s | |
| Accuracy in setting (mechanical) | ±10% | |
| Temperature coefficient | 0.05%/°C at 20°C (0.05%/°F at 68°F) | |
| Output | 1×SPDT | |
| Current rating | 10A/AC1 | |
| Switching voltage | 250VAC/24VDC | |
| Min. breaking capacity DC | 500mW | |
| Output indication | red LED | |
| Mechanical life | 1×107 | |
| Electrical life (AC1) | 1×105 | |
| Reset time | max. 200ms | |
| Operating temperature | -20°C to +55°C (-4°F to 131°F) | |
| Storage temperature | -35°C to +75°C (-22°F to 158°F) | |
| Humidity | Up to 95% RH (non-condensing) | |
| Mounting/DIN rail | Din rail EN/IEC 60715 | |
| Protection degree | IP40 for front panel/IP20 terminals | |
| Operating position | any | |
| Overvoltage category | III. | |
| Pollution degree | 2 | |
| Max. cable size (mm2) | solid wire max. 1×2.5 or 2×1.5 / with sleeve max. 1×2.5 (AWG 12) | |
| Tightening torque | 0.8Nm | |
| Dimensions | 90×18×64mm | |
| Weight | 70g | 72g |
| Standards | EN 62055-1 | |
6.2 GRL8-03 Technical Parameters
| Parameter | GRL8-03 |
|---|---|
| Function | well-tank level control |
| Supply terminals | A1, A2 |
| Voltage range | AC/DC 24-240V (50-60Hz) |
| Input | max. 2VA |
| Supply voltage tolerance | -15%; +10% |
| Sensitivity (input resistance) | adjustable in range 5 kΩ - 100 kΩ |
| Voltage in electrodes | max. AC 5 V |
| Current in probe | AC <0.1 mA |
| Time response | max. 400 ms |
| Max. capacity length | 800 m (sensitivity 25kΩ), 200 m (sensitivity 100 kΩ) |
| Max. capacity of probe cable | 400 nF (sensitivity 25kΩ), 100 nF (sensitivity 100 kΩ) |
| Supply indication | Green LED |
| Accuracy in setting (mechanical) | <10% |
| Output | 1×SPDT |
| Current rating | 10A/AC1 |
| Switching voltage | 250VAC/24VDC |
| Min. breaking capacity DC | 500mW |
| Output indication | Red LED |
| Mechanical life | 1×107 |
| Electrical life (AC1) | 1×105 |
| Reset time | max. 200ms |
| Operating temperature | -20°C to +55°C (-4°F to 131°F) |
| Storage temperature | -35°C to +75°C (-22°F to 158°F) |
| Mounting/DIN rail | Din rail EN/IEC 60715 |
| Protection degree | IP20 terminals |
| Operating position | any |
| Overvoltage category | III. |
| Pollution degree | 2 |
| Max. cable size (mm2) | solid wire max. 1×2.5 or 2×1.5 (AWG 12) |
| Dimensions | 90×18×64mm |
| Weight | 80g |
| Standards | EN 60255-1 |
6.3 Dimensions

7. User Tips
- The GRL8 relays are compact and effective, making them suitable for projects with limited space.
- When ordering, ensure you clearly specify if you require both the relay unit and the level sensors, as they may be sold separately.
- If using DC power, verify the specific DC operating voltage requirements for your model.
- Regularly check probe cleanliness, especially in environments prone to buildup, to maintain accurate level detection.