GEYA GRL8 Liquid Level Control Relay Instruction Manual

Models: GRL8-01, GRL8-02, GRL8-03

1. Introduction

The GEYA GRL8 series of liquid level control relays are designed for monitoring and controlling liquid levels in various applications such as wells, basins, reservoirs, and tanks. These devices offer reliable and precise control of pumps based on detected liquid levels. The series includes models GRL8-01, GRL8-02, and GRL8-03, each with specific functionalities to suit different control requirements.

GEYA GRL8 Level Control Relay Overview
Figure 1: GEYA GRL8-01/02/03 Level Control Relay overview with key features including 10A/AC1 output, 24V-240V AC/DC voltage, and 1SPDT contact.

2. Setup and Installation

2.1 Mounting

The GRL8 series relays are designed for 1-MODULE, DIN rail mounting (EN/IEC 60715). Ensure the relay is securely fastened to the DIN rail in a suitable enclosure, protected from environmental factors.

2.2 Wiring Diagrams

Proper wiring is crucial for the correct operation of the liquid level control relay. Refer to the specific diagrams for your GRL8 model.

2.2.1 GRL8-01 and GRL8-02 Wiring

GRL8-01 and GRL8-02 Wiring and Panel Diagrams
Figure 2: Wiring Diagram for GRL8-01 and GRL8-02 showing connections for A1, A2 (supply), C, Min, Max (probes), and 11, 12, 14 (output contacts). Panel diagrams illustrate the front face controls and indicators.

Probe Connections:

  • A1, A2: Supply terminals (AC/DC 24-240V).
  • C: Common probe.
  • Min: Minimum level probe.
  • Max: Maximum level probe.
  • 11, 12, 14: SPDT output contacts.

2.2.2 GRL8-03 Wiring (Well-Tank Level Control)

GRL8-03 Panel Diagram for Well and Tank Control
Figure 3: Panel Diagram for GRL8-03 illustrating connections for controlling a pump between a well and a tank. C, Min1, Max1 connect to the well, and C, Min2, Max2 connect to the tank. A manual start button is also shown.

Probe Connections for GRL8-03:

  • A1, A2: Supply terminals (AC/DC 24-240V).
  • C: Common probe (shared between well and tank).
  • Min1, Max1: Minimum and Maximum level probes for the well.
  • Min2, Max2: Minimum and Maximum level probes for the tank.
  • 11, 12, 14: SPDT output contacts for pump control.
  • Manual start: Connect an external button for manual pump operation.

3. Operating Instructions

3.1 General Function Features

  • Supply Voltage: Galvanically separated AC/DC 24-240V.
  • Output: 1 SPDT (Single Pole Double Throw) contact, 10A/AC1.
  • Status Indication: Relay status is indicated by an LED on the front panel.
  • Sensitivity: Adjustable by a potentiometer on the front panel (5-100KΩ).

3.2 Model-Specific Functions

3.2.1 GRL8-01 (2 Level Control Mode)

  • Monitors liquid level between two points (Min and Max).
  • Typically used for maintaining liquid within a specific range.

3.2.2 GRL8-02 (2 or 1 Level Control Mode)

  • Offers flexibility to operate in either 2-level or 1-level control mode.
  • Function Selection: Choice of PUMP UP or PUMP DOWN operation.
  • Time Delay: Adjustable time delay on the output (0.1 - 10s).

3.2.3 GRL8-03 (Well-Tank Level Control)

This model is designed to control high water towers by pumping water from low water wells. The working principle is as follows:

  1. When the water level in the high water tower is lower than Min2, if the water level in the well is higher than Min1, the pump will start working until the water level in the tower reaches Max2, and the pump will stop working.
  2. When the water level in the well reaches Max1, if the water level in the high water tower is lower than Max2, the pump will start working until the water level in the tower reaches Max2, and the pump will stop working. If this function is not required, please do not connect the Max1 probe.
  3. When the water level in the water tower is between Max2 and Min2, the water pump can be started by pressing the 'manual start' button until the water level in the tower reaches Max2, and the water pump stops working.
  4. When the water pump is running, if the water level in the well is lower than Min1, the pump will stop working to avoid empty load to prevent damage to the pump. At this time, the red light will flash to indicate that the well is short of water.

3.3 Functions Diagrams

The following diagrams illustrate the operational logic for each model:

GRL8-01 and GRL8-02 Functions Diagrams
Figure 4: Functions Diagram for GRL8-01 (2 level control) and GRL8-02 (1 level control: pump up on/off, pump down on/off, pump up/down).
GRL8-03 Well-Tank Control Logic
Figure 5: GRL8-03 Panel Diagram and associated control logic for well and tank level management.

4. Maintenance

The GEYA GRL8 series relays are designed for reliable operation with minimal maintenance. However, regular checks can ensure optimal performance:

  • Visual Inspection: Periodically inspect the relay and its connections for any signs of damage, corrosion, or loose wiring.
  • Cleanliness: Ensure the relay and its enclosure are kept clean and free from dust or moisture accumulation.
  • Probe Condition: Check the liquid level probes for any buildup or damage that might affect their conductivity and accuracy. Clean probes as necessary according to the liquid type.

5. Troubleshooting

If the relay is not functioning as expected, consider the following:

  • No Power/LED Off: Check the supply voltage (A1, A2) and ensure it is within the specified AC/DC 24-240V range. Verify all power connections.
  • Incorrect Switching:
    • Check the wiring of the probes (C, Min, Max) for correct connection and ensure they are not short-circuited or open-circuited.
    • Verify the liquid level probes are clean and making proper contact with the liquid.
    • Adjust the sensitivity potentiometer. If sensitivity is too low or too high, it might lead to erratic switching.
    • For GRL8-02, ensure the PUMP UP/PUMP DOWN function is correctly selected.
    • For GRL8-03, ensure all well and tank probes are correctly installed and connected according to the desired control logic.
  • Pump Not Activating: Check the output contacts (11, 12, 14) and the wiring to the pump. Ensure the pump itself is functional.
  • Erratic Behavior: Ensure the relay is not exposed to excessive electrical noise or interference. Check for stable power supply.

6. Specifications

6.1 GRL8-01 and GRL8-02 Technical Parameters

ParameterGRL8-01GRL8-02
Function2 level control mode2 or 1 level control mode
Supply terminalsA1-A2
Voltage rangeAC/DC 24-240V (50-60Hz)
Inputmax. 2VA
Supply voltage tolerance-15%; +10%
Sensitivity (input resistance)adjustable in range 5 kΩ - 100 kΩ
Voltage in electrodesmax. AC 5 V
Current in probeAC <0.1 mA
Time responsemax. 400 ms
Max. capacity length800 m (sensitivity 25kΩ), 200 m (sensitivity 100 kΩ)
Max. capacity of probe cable400 nF (sensitivity 25kΩ), 100 nF (sensitivity 100 kΩ)
Time delay (t)adjustable, 0.1 - 10 s
Accuracy in setting (mechanical)±10%
Temperature coefficient0.05%/°C at 20°C (0.05%/°F at 68°F)
Output1×SPDT
Current rating10A/AC1
Switching voltage250VAC/24VDC
Min. breaking capacity DC500mW
Output indicationred LED
Mechanical life1×107
Electrical life (AC1)1×105
Reset timemax. 200ms
Operating temperature-20°C to +55°C (-4°F to 131°F)
Storage temperature-35°C to +75°C (-22°F to 158°F)
HumidityUp to 95% RH (non-condensing)
Mounting/DIN railDin rail EN/IEC 60715
Protection degreeIP40 for front panel/IP20 terminals
Operating positionany
Overvoltage categoryIII.
Pollution degree2
Max. cable size (mm2)solid wire max. 1×2.5 or 2×1.5 / with sleeve max. 1×2.5 (AWG 12)
Tightening torque0.8Nm
Dimensions90×18×64mm
Weight70g72g
StandardsEN 62055-1

6.2 GRL8-03 Technical Parameters

ParameterGRL8-03
Functionwell-tank level control
Supply terminalsA1, A2
Voltage rangeAC/DC 24-240V (50-60Hz)
Inputmax. 2VA
Supply voltage tolerance-15%; +10%
Sensitivity (input resistance)adjustable in range 5 kΩ - 100 kΩ
Voltage in electrodesmax. AC 5 V
Current in probeAC <0.1 mA
Time responsemax. 400 ms
Max. capacity length800 m (sensitivity 25kΩ), 200 m (sensitivity 100 kΩ)
Max. capacity of probe cable400 nF (sensitivity 25kΩ), 100 nF (sensitivity 100 kΩ)
Supply indicationGreen LED
Accuracy in setting (mechanical)<10%
Output1×SPDT
Current rating10A/AC1
Switching voltage250VAC/24VDC
Min. breaking capacity DC500mW
Output indicationRed LED
Mechanical life1×107
Electrical life (AC1)1×105
Reset timemax. 200ms
Operating temperature-20°C to +55°C (-4°F to 131°F)
Storage temperature-35°C to +75°C (-22°F to 158°F)
Mounting/DIN railDin rail EN/IEC 60715
Protection degreeIP20 terminals
Operating positionany
Overvoltage categoryIII.
Pollution degree2
Max. cable size (mm2)solid wire max. 1×2.5 or 2×1.5 (AWG 12)
Dimensions90×18×64mm
Weight80g
StandardsEN 60255-1

6.3 Dimensions

GRL8-03 Dimensions
Figure 6: Dimensions of the GRL8-03 relay (95mm height, 18mm width, 64mm depth).

7. User Tips

  • The GRL8 relays are compact and effective, making them suitable for projects with limited space.
  • When ordering, ensure you clearly specify if you require both the relay unit and the level sensors, as they may be sold separately.
  • If using DC power, verify the specific DC operating voltage requirements for your model.
  • Regularly check probe cleanliness, especially in environments prone to buildup, to maintain accurate level detection.

8. Warranty and Support

For technical support, warranty information, or service inquiries, please contact GEYA Electrical Co., Ltd. directly.

GEYA Electrical Co., Ltd.
Address: Wenzhou Bridge Industrial Zone, Beibaixiang Town, Yueqing, Zhejiang, China 325603
Mobile: +86 13567770207
E-mail: sale@cngeya.com
Web: www.geya.net

GEYA Contact Information
Figure 7: GEYA contact card with company details.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.