1. Introduction
This manual describes the assembly, installation, operation, and troubleshooting of the PowMr 6.2KW Hybrid Solar Inverter. Please read this manual carefully before installations and operations. Keep this manual for future reference.
1.1 Purpose and Scope
This unit is a multi-function inverter, combining the functions of an inverter, solar charger, and battery charger to offer uninterruptible power support. The comprehensive LCD display offers user-configurable and easy-accessible button operations such as battery charging current, AC or solar charging priority, and acceptable input voltage based on different applications.
This manual provides safety and installation guidelines as well as information on tools and wiring.
1.2 Features
- Pure sine wave inverter
- Dual inputs and dual outputs
- Feed-in to the grid function
- Configurable input voltage ranges for home appliances and personal computers via LCD control panel
- Configurable battery charging current based on applications via LCD control panel
- Configurable AC/Solar Charger priority via LCD control panel
- Compatible with utility mains or generator power
- Smart battery charger design for optimized battery performance
- Optional WiFi with remote monitoring APP
1.3 Basic System Architecture
The inverter can power various appliances in home or office environments, including motor-type appliances such as tube lights, fans, refrigerators, and air conditioners. A complete running system requires a generator or utility mains and PV modules.





2. Safety Instructions
WARNING: All safety instructions in this document must be read, understood and followed. Failure to follow these instructions will result in death or serious injury.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION --To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION - Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.
- One piece of 150A fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
- NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
- WARNING: Because this inverter is non-isolated, only three types of PV modules are acceptable: single crystalline, poly crystalline with class A-rated and CIGS modules. To avoid any malfunction, do not connect any PV modules with possible current leakage to the inverter. For example, grounded PV modules will cause current leakage to the inverter. When using CIGS modules, please be sure NO grounding.
- CAUTION: It's requested to use PV junction box with surge protection. Otherwise, it will cause damage on inverter when lightning occurs on PV modules.
3. Setup and Installation
3.1 Unpacking and Inspection
Before installation, please inspect the content. Be sure that nothing inside the package is damaged. You should have received the following items:
- Inverter x 1
- User manual x 1
- RS232 Communication cable x 1
- Software CD x 1
- DC Fuse x 1
- PV connectors x 1 set
3.2 Preparation
Before connecting all wirings, take off the terminal cover by removing one screw and the bottom cover by removing four screws.
3.3 Mounting the Unit
Consider the following before selecting your placement:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install the inverter at eye level to allow easy LCD display readout.
- For proper air circulation and heat dissipation, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below the unit.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended orientation is to adhere to the wall vertically. Be sure to keep other objects and surfaces clear to guarantee sufficient heat dissipation and enough space for wirings.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

3.4 Battery Connection
CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnection device between battery and the inverter. A disconnection device may not be necessary in some applications, however, it's still recommended to have over-current protection installed. Please refer to typical amperage as required.
WARNING! All wiring must be performed by a qualified electrical technician.
WARNING! It's very important for system safety and efficient operation to use appropriate cables for battery connection. To reduce risk of injury, please use the proper recommended cable in the table below.
Recommended Battery Cable Size:
| Model | Typical Amperage | Wire Size | Cable mm² (each) | Ring Terminal Dimensions D (mm) | Ring Terminal Dimensions L (mm) | Torque Value |
|---|---|---|---|---|---|---|
| 6.2KW | 138.8A | 1*2AWG | 38 | 8.4 | 39.2 | 5 Nm |
| 2*4AWG | 25 | 8.4 | 33.2 |
Follow these steps to implement battery connection:
- This inverter supports a 48VDC system. Connect all battery packs as shown in the diagram. It is recommended to connect a minimum of 200Ah capacity battery.
- Prepare four battery wires depending on cable size (refer to the recommended cable size table). Apply ring terminals to your battery wires and secure them to the battery terminal block with the bolts properly tightened.
- Refer to battery cable size for torque value. Make sure polarity at both the battery and the inverter is correctly connected and ring terminals are secured to the battery terminals.
WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.
CAUTION!! Do not place anything between inverter terminals and the ring terminals. Otherwise, overheating may occur.
CAUTION!! Do not apply anti-oxidant substance on the terminals before terminals are securely tightened.
CAUTION!! Before making final DC connection or closing DC breaker/disconnector, be sure that the positive (+) must be connected to positive (+) and negative (-) connected to negative (-).
3.5 AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between the inverter and the AC input power source. This will ensure that the inverter can be safely disconnected during maintenance and fully protected from over-current. The recommended spec of AC breaker is 32A.
CAUTION!! There are two power terminal blocks with "IN" (Input) and "OUT" (Output) markings. DO NOT mistakenly connect to the wrong connectors.
WARNING! All wiring must be performed by qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable size for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested Cable Requirement for AC Wires:
| Gauge | Cable (mm²) | Torque Value |
|---|---|---|
| 10 AWG | 6 | 1.2 Nm |
Follow these steps to implement AC input/output connection:
- Before making AC input/output connection, be sure to enable DC protector or disconnector first.
- Remove insulation sleeves for about 10mm for the five screw terminals.
- Insert all AC input wires through the terminal cover and connect to terminals according to polarities indicated on the terminal block. Tighten the terminal screws. Be sure to connect the grounding wire (PE) first.
- This inverter is equipped with dual-output. There are four terminals (L1/N1, L2/N2) available on the output port. It's set up through the LCD program or monitoring software to turn on and off the second output. Refer to the "LCD setting" section for details. Insert AC output wires through the terminal cover and connect to terminals according to polarities indicated on the terminal block. Tighten terminal screws. Be sure to connect the PE protective conductor (PE) first.
WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
CAUTION: Appliances such as air conditioners require at least 2~3 minutes to spool up because they need enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short period of time, it may cause damage to your connected appliances. To prevent this from happening, please check with the manufacturer of the air conditioner if it has a time-delay function before installation. Otherwise, this inverter will trigger an overload fault and cut off output to protect your appliance, but sometimes it may still cause damage to the air conditioner.
3.6 PV Connection
CAUTION: Before connecting to PV modules, please install separately DC circuit breakers between the inverter and PV modules.
NOTE1:
Please use a 600VDC/30A circuit breaker.NOTE2:
The overvoltage category of the PV input is II.Please follow the steps below to implement PV module connection:
WARNING: Because this inverter is non-isolated, only three types of PV modules are acceptable: single crystalline and poly crystalline with class A-rated and CIGS modules. To avoid any malfunction, do not connect any PV modules with possible current leakage to the inverter. For example, grounded PV modules will cause current leakage to the inverter. When using CIGS modules, please be sure NO grounding.
CAUTION: It's required to use a PV junction box with surge protection. Otherwise, it will cause damage on the inverter when lightning occurs on PV modules.
- Check the input voltage of PV array modules. This system is applied with two strings of PV array. Please make sure that the maximum current load of each PV input connector is 27A.
- Disconnect the circuit breaker and switch off the DC switch.
- Assemble provided PV connectors with PV modules by following the steps outlined in the manual (crimping tool and spanner required).
- Check the correct polarity of the connection cable from the PV modules and PV input connectors. Then, connect the positive pole (+) of the connection cable to the positive pole (+) of the PV input connector. Connect the negative pole (-) of the connection cable to the negative pole (-) of the PV input connector.
CAUTION: Exceeding the maximum input voltage can destroy the unit!! Check the system before wire connection.
WARNING! For safety and efficiency, it's very important to use appropriate cables for PV module connection. To reduce risk of injury, please use the proper cable size as recommended below.
PV Module Selection Parameters:
- Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than min. start-up voltage.
| Parameter | Value |
|---|---|
| Max. PV Array Power | 6000W |
| Max. PV Array Open Circuit Voltage | 500Vdc |
| PV Array MPPT Voltage Range | 60Vdc~450Vdc |
| Start-up Voltage | 60Vdc +/- 10Vdc |
| Max. PV Current | 27A |
CAUTION: Never directly touch the terminals of inverter. It might cause lethal electric shock.
3.7 Final Assembly
After connecting all wirings, put the bottom cover back by fixing four screws.
3.8 Communication Connection
Serial Connection
Use the supplied communication cable to connect the inverter and PC. Insert the bundled CD into a computer and follow the on-screen instructions to install the monitoring software. For detailed software operation, check the user manual of the software inside the CD.
Wi-Fi Connection
This unit is equipped with a Wi-Fi transmitter. The Wi-Fi transmitter enables wireless communication between solar inverters and a monitoring platform. Users can access and control the monitored inverter with a downloaded APP. You may find the "i.Solar" app from the Apple® Store or Google® Play Store. All data loggers and parameters are saved in iCloud. For quick installation and operation, check Appendix II of the full PDF manual.
BMS Communication
It is recommended to purchase a special communication cable if you are connecting to Lithium-Ion battery banks. For details on BMS Communication Installation, refer to Appendix I of the full PDF manual. This custom-made RJ45 communication cable delivers information and signals between the lithium battery and the inverter, allowing the inverter to re-configure charging voltage, charging current, and battery discharge cut-off voltage, and to start or stop charging based on battery status.
For a comprehensive guide including detailed diagrams for BMS and Wi-Fi setup, please refer to the full user manual available at: PowMr 6.2KW Hybrid Inverter User Manual (PDF).
4. Operation
4.1 Power ON/OFF
Once the unit has been properly installed and the batteries are connected, simply press the On/Off switch to turn on the unit.
4.2 Operation and Display Panel
The LCD module includes four touchable buttons with status indication and an LCD display, indicating the operating status and input/output power information.
Touchable Buttons with Indication:
| Function Key | Description |
|---|---|
| ↩ | To exit setting mode |
| ▲ | To go to previous selection |
| ▼ | To go to next selection |
| ↵ | To confirm the selection in setting mode or enter setting mode |
LED Indicator:
| LED Indicator | Color | Solid/Flashing | Messages |
|---|---|---|---|
| Green | Solid On | Unit is working normally (without any warning or fault codes and charging). | |
| Green/Yellow | Alternatively flashing | Battery is charging. | |
| Yellow | Solid On | Warning code appears. | |
| Red | Solid On | Fault mode. |
4.3 LCD Display Icons
The LCD displays various icons to indicate input source, configuration, output information, battery status, and operating modes. These include AC/PV input indicators, input voltage/frequency/power, setting program numbers, warning/fault codes, output voltage/frequency/load, battery level, and charging status.
4.4 LCD Setting
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Use the UP or DOWN buttons to select setting programs, then press ENTER to confirm or ESC to exit. Key settings include:
- Program 01: Output source priority (Utility first, Solar first, SBU priority)
- Program 02: Maximum charging current (10A to 120A)
- Program 03: AC input voltage range (Appliances: 90-280VAC, UPS: 170-280VAC)
- Program 05: Battery type (AGM, Flooded, User-Defined, Pylontech, WECO, Soltaro, LIA-protocol, LIb-protocol, 3rd party Lithium)
- Program 06: Auto restart when overload occurs (Enable/Disable)
- Program 07: Auto restart when over temperature occurs (Enable/Disable)
- Program 09: Output frequency (50Hz/60Hz)
- Program 10: Output voltage (220V/230V/240V)
- Program 11: Maximum utility charging current (2A to 100A)
- Program 12: Setting voltage point or SOC back to utility source (44V-51V or 5%-95% SOC)
- Program 13: Setting voltage point or SOC back to battery mode (48V-58V or 10%-100% SOC)
- Program 16: Charger source priority (Solar first, Solar and Utility, Only Solar)
- Program 18: Alarm control (On/Off)
- Program 19: Auto return to default display screen (Enable/Disable)
- Program 20: Backlight control (On/Off)
- Program 22: Beeps while primary source is interrupted (On/Off)
- Program 23: Overload bypass (Enable/Disable)
- Program 25: Record Fault code (Enable/Disable)
- Program 26: Bulk charging voltage (C.V voltage) (48.0V-61.0V)
- Program 27: Floating charging voltage (48.0V-61.0V)
- Program 29: Low DC cut-off voltage or SOC (42.0V-48.0V or 0%-90% SOC)
- Program 30: Battery equalization (Enable/Disable)
- Program 31: Battery equalization voltage (48.0V-61.0V)
- Program 33: Battery equalized time (5min-900min)
- Program 34: Battery equalized timeout (5min-900min)
- Program 35: Equalization interval (0-90 days)
- Program 36: Equalization activated immediately (Enable/Disable)
- Program 38: Solar energy feeds to the grid (Enable/Disable)
- Program 60: Low DC cut-off voltage or SOC on second output (0%-95% SOC)
- Program 61: Setting discharge time on the second output (0-990 min)
- Program 63: Setting voltage point or SOC to restart on the second output (L2) (43.0V-61.0V or 0%-95% SOC)
- Program 64: Setting waiting time to turn on the second output (L2) (0-990 min)
4.5 Operating Mode Description
The inverter operates in three main modes:
- Standby Mode: No output is supplied, but the unit can charge batteries.
- Line Mode: The unit provides output power from the mains and charges the battery.
- Battery Mode: The unit provides output power from the battery and PV power.
4.6 Battery Equalization Description
Battery equalization is built into the charge controller to reverse the buildup of negative chemical effects like stratification and remove sulfate crystals, which can reduce battery capacity. It is recommended to equalize the battery periodically.
How to Activate Equalization Function:
You must enable the battery equalization function in LCD setting Program 30 first. You can then apply this function by either one of the following methods:
- Setting the equalization interval in Program 35.
- Activating equalization immediately in Program 36.
When to Equalize:
In the floating charge stage, when the equalization interval (battery equalization cycle) is reached, or equalization is activated immediately, the controller will start to enter Equalize Mode.
Equalize Charging and Timeout:
In Equalize Mode, the controller will supply power to charge the battery until the battery voltage reaches the equalization voltage. Then, constant-voltage regulation is applied to maintain the battery voltage at the equalization level. The battery will remain in Equalize Mode until the equalization timer runs out.
5. Maintenance
5.1 Clearance and Maintenance for Anti-Dust Kit
Every inverter is installed with an anti-dust kit from the factory. This kit keeps dust out of your inverter and increases product reliability in harsh environments.
- Loosen the screw on the side of the inverter.
- Remove the dustproof case and take out the air filter foam.
- Clean the air filter foam and dustproof case. After cleaning, re-assemble the dust-kit back to the inverter.
NOTICE:
The anti-dust kit should be cleaned from dust every one month.6. Troubleshooting
6.1 Fault Reference Code
The following table lists common fault codes and their corresponding events:
| Fault Code | Fault Event | Icon on |
|---|---|---|
| 01 | Fan is locked when inverter is off. | 01 |
| 02 | Over temperature or NTC is not connected well. | 02 |
| 03 | Battery voltage is too high | 03 |
| 04 | Battery voltage is too low | 04 |
| 05 | Output short circuited or over temperature is detected by internal converter components. | 05 |
| 06 | Output voltage is too high. | 06 |
| 07 | Overload time out | 07 |
| 08 | Bus voltage is too high | 08 |
| 09 | Bus soft start failed | 09 |
| 51 | Over current or surge | 51 |
| 52 | Bus voltage is too low | 52 |
| 53 | Inverter soft start failed | 53 |
| 55 | Over DC voltage in AC output | 55 |
| 57 | Current sensor failed | 57 |
| 58 | Output voltage is too low | 58 |
| 59 | PV voltage is over limitation | 59 |
6.2 Warning Indicator
The following table lists warning codes and their corresponding events and audible alarms:
| Warning Code | Warning Event | Audible Alarm | Icon flashing |
|---|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep three times every second | 01▲ |
| 02 | Over temperature | None | 02▲ |
| 03 | Battery is over-charged | Beep once every second | 03▲ |
| 04 | Low battery | Beep once every second | 04▲ |
| 07 | Overload | Beep once every 0.5 second | 07▲ |
| 10 | Output power derating | Beep twice every 3 seconds | 10▲ |
| 15 | PV energy is low. | Beep twice every 3 seconds | 15▲ |
| 16 | High AC input (>280VAC) during BUS soft start | None | 16▲ |
| 30 | Internal communication lost | None | 30▲ |
| 32 | Communication lost | None | 32▲ |
| E9 | Battery equalization | None | E9▲ |
| 6P | Battery is not connected | None | 6P▲ |
6.3 General Troubleshooting
The following table provides solutions for common problems:
| Problem | Explanation / Possible cause | What to do |
|---|---|---|
| Unit shuts down automatically during startup process. | The battery voltage is too low (<1.91V/Cell) | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | 1. The battery voltage is far too low. (<1.4V/Cell) 2. Internal fuse tripped. | 1. Contact repair center for replacing the fuse. 2. Re-charge battery. 3. Replace battery. |
| Mains exist but the unit works in battery mode. | Insufficient quality of AC power. (Shore or Generator) | 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS→Appliance) |
| When the unit is turned on, internal relay is switched on and off repeatedly. | Battery is disconnected. | Check if battery wires are connected well. |
| Buzzer beeps continuously and red LED is on. | Fault code 07: Overload error. The inverter is overload 110% and time is up. | Reduce the connected load by switching off some equipment. |
| Fault code 05: Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
| Fault code 02: Internal temperature of inverter component is over 100°C. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
| Fault code 03: Battery is over-charged. | Check if spec and quantity of batteries are meet requirements. | |
| Fault code 01: Fan fault | Replace the fan. | |
| Fault code 06/58: Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) | 1. Reduce the connected load. 2. Return to repair center. | |
| Fault code 08/09/53/57: Internal components failed. | Return to repair center. | |
| Fault code 51: Over current or surge. | Restart the unit, if the error happens again, please return to repair center. | |
| Fault code 59: PV input voltage is beyond the specification. | Reduce the number of PV modules in series. |
6.4 Code Reference for Lithium Battery Communication
Related information codes will be displayed on the LCD screen when using Lithium batteries:
| Code | Description |
|---|---|
| 60 | If battery status is not allowed to charge and discharge after successful communication between inverter and battery, it will show code 60 to stop charging and discharging battery. |
| 61 | Communication lost (only available when battery type is set to any type of lithium-ion battery). After battery is connected, if communication signal is not detected for 3 minutes, the buzzer will beep. After 10 minutes, the inverter will stop charging and discharging to the lithium battery. Communication loss occurs after the inverter and battery are successfully connected, the buzzer beeps immediately. |
| 62 | Battery number is changed. This is probably due to communication loss between battery packs. Please check the cables between the batteries. |
| 69 | If battery status is not allowed to charge after successful communication between inverter and battery, it will show code 69 to stop charging battery. |
| 70 | If battery status must be charged after successful communication between inverter and battery, it will show code 70 to charge battery. |
| 71 | If battery status is not allowed to discharge after successful communication between inverter and battery, it will show code 71 to stop discharging battery. |
7. Specifications
7.1 Line Mode Specifications
| MODEL | 6.2KW |
|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) |
| Nominal Input Voltage | 230Vac |
| Low Loss Voltage | 170Vac±7V (UPS); 90Vac±7V (Appliances) |
| Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) |
| High Loss Voltage | 280Vac±7V |
| High Loss Return Voltage | 270Vac±7V |
| Max AC Input Voltage | 300Vac |
| Nominal Input Frequency | 50Hz / 60Hz (Auto detection) |
| Low Loss Frequency | 40±1Hz |
| Low Loss Return Frequency | 42±1Hz |
| High Loss Frequency | 65±1Hz |
| High Loss Return Frequency | 63±1Hz |
| Output Short Circuit Protection | Circuit Breaker |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) |
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) |
7.2 Inverter Mode Specifications
| MODEL | 6.2KW |
|---|---|
| Rated Output Power | 6.2KVA/6.2KW |
| Output Voltage Waveform | Pure Sine Wave |
| Output Voltage Regulation | 230Vac±5% |
| Output Frequency | 50Hz |
| Peak Efficiency | 93% |
| Overload Protection | 5s@≥130% load; 10s@105%~130% load |
| Surge Capacity | 2* rated power for 5 seconds |
| Nominal DC Input Voltage | 48Vdc |
| Cold Start Voltage | 46.0Vdc |
| Low DC Warning Voltage @load < 50% | 46.0Vdc |
| Low DC Warning Voltage @load ≥ 50% | 44.0Vdc |
| Low DC Warning Return Voltage @load < 50% | 47.0Vdc |
| Low DC Warning Return Voltage @load ≥ 50% | 46.0Vdc |
| Low DC Cut-off Voltage @load < 50% | 43.0Vdc |
| Low DC Cut-off Voltage @load ≥ 50% | 42.0Vdc |
| High DC Recovery Voltage | 62Vdc |
| High DC Cut-off Voltage | 63Vdc |
| No Load Power Consumption | <55W |
7.3 Charge Mode Specifications
| Utility Charging Mode | |
|---|---|
| MODEL | 6.2KW |
| Charging Current (UPS) @Nominal Input Voltage | 100Amp(@VI/P=230Vac) |
| Bulk Charging Voltage Flooded Battery | 58.4Vdc |
| Bulk Charging Voltage AGM / Gel Battery | 56.4Vdc |
| Floating Charging Voltage | 54Vdc |
| Charging Algorithm | 3-Step |
| Solar Input | |
|---|---|
| MODEL | 6.2KW |
| Max. PV Array Power | 6000W |
| Max. PV Current | 27A |
| Nominal PV Voltage | 360Vdc |
| Start-up Voltage | 60Vdc +/- 10Vdc |
| PV Array MPPT Voltage Range | 60~450Vdc |
| Max. PV Array Open Circuit Voltage | 500Vdc |
| Max Charging Current (AC charger plus solar charger) | 120Amp |
7.4 General Specifications
| MODEL | 6.2KW |
|---|---|
| Operating Temperature Range | -10°C to 50°C |
| Storage temperature | -15°C~60°C |
| Humidity | 5% to 95% Relative Humidity (Non-condensing) |
| Dimension (D*W*H), mm | 136 x 323.6 x 449.3 |
| Net Weight, kg | 10.3 |